background image

 

5.2. 

Replacement of electrical thermal element.

 

 

 

 

 

 

 

 

 

 

 

 
Disconnect the trigger from electric installation and disconnect connections of the trigger at the valve. 
After  unscrewing  two  M5  screws  (item  4  Fig.  to  section  5.3.)  (optionally  nut  M6),  remove  the  entire 
electrical thermal element from the valve with the plate (item 1), as presented in the drawing below. In 
order to replace the thermal element (item 2),  unscrew  the brass  cylinder or nut  (item  3), place new 
thermal element in the opening or onto the shank (as presented in the drawing), and again screw on 
the cylinder on the micro-switch shank (item 5). 
Assemble the whole to the valve in the reverse order, not forgetting to place the sealing cushion (item 
6). Connect the trigger to the electric installation and open the valve. 

5.3. 

Replacement of the spring. 

Before replacing the spring, unscrew the screw (Fig. to section 5.4., item 3) fixing the manual lever on 
the  drive  shaft,  set  the  valve  partition  in  the  closed  position  so  that  the  spring  tension  is  minimum 
(lever item 1 resting on the limiter, item 4), and next remove lever (item 1) and damaged spring (item 
2).  Place  the  spring  on  the  middle  opening  in  the  manual  lever  and  place  the  whole  on  drive  shaft, 
item 5. During placement on drive shaft, manual lever must be set vertically, namely it should rest on 
the  limiter on the drive board.  Set the  manual lever in  the appropriate  distance from the drive board 
and screw the screw fixing the lever on the drive shaft. Hook the spring on one of the catches (item 6) 
on the drive board, and assess the strength with which the partition is closed. 

 
If necessary, change the spring hooking on the drive board or manual lever, 
and  again  assess  correct  closing  of  the  valve.  Repeat  these  activities  until 
your  assessment  is  positive.  Correct  valve  closure  occurs  where  valve 
partition  freely  closes,  and  the  manual  lever  meets  resistance  on  the  drive 
board  without  excess  noise.  After  replacement  of  the  manual  lever, 
depending  on  valve  version,  reassemble  the  previously  removed  elements, 
and check for their correct operation. 

 

 

 

 

 

 

Electrical glass thermal 
element for valves type 
RK370M 

Electrical soldered 
thermal element for 
valves type RK370M 

Fig. to section 5.2. 

Fig. to s.5.3. 

Содержание RK370

Страница 1: ...CAL OPERATIONAL DOCUMENTATION FIRE SAFETY VALVES type V370 and RK370 MANUFACTURER FRAPOL Sp ka z o o 30 832 Krak w ul Mierzeja Wi lana 8 Phone 012 653 27 66 653 27 67 653 26 92 fax 012 653 27 89 MARCH...

Страница 2: ...ERISTICS 3 3 VERSIONS 4 4 PRINCIPLES FOR INSTALLATION OF FIRE VALVES 6 5 PRINCIPLES FOR FIRE VALVES MAINTENANCE 16 6 PERIODICAL MAINTENANCE 18 7 LIST OF SPARE PARTS 19 8 TECHNICAL DATA OF ACTUATORS AN...

Страница 3: ...BELIMO actuator thermal trigger mechanical or electrical thermal element Valves can be furnished with a thermal trigger adjusted to actuation at the temperatures of 72 5 C or 90 5 C For V370 valves bo...

Страница 4: ...heat responsive device involves air stream flowing round the thermal element glass ball or soldered metal plates causes heating of the liquid inside the ball or solder which causes breaking of the gl...

Страница 5: ...ith a return spring made of wire with diameter of 3 mm are furnished with solenoid with keeper holding strength of 120 N Valves with a return spring made of wire with diameter of 3 5 mm are furnished...

Страница 6: ...s switch the cut off partition of the valve from closed to open position at the same time stretching the closing spring After turning the lever to full opening of the valve hook the lever on manual tr...

Страница 7: ...Fig 1a Fig 1b Fig 1c Type RK370 Fig 2a Fig 2b Fig 2c 4 1 4 Check for the size and shape of openings prepared in the walls to set the valves acc to section 4 2 4 1 5 Check whether after valve installa...

Страница 8: ...cumference 4 3 9 On both sides of the valve partition inside the ventilation duct there must be free space to allow for its opening 4 3 10 Electrical installation of the signalisation and powering of...

Страница 9: ...of the valve should remain within the axis of the partition Assembly of the valves in this version in fire barriers class EI120 but with greater thicknesses must be made observing partition depth acc...

Страница 10: ...rier with class EI120 and thickness of 125 mm the cut off partition of the valve should remain in the axis of barrier thickness Valves of V370 type must protrude from the wall on the drive side to the...

Страница 11: ...aster board 12 5mm 4 layers Plaster board 12 5mm 2 warstwy Screws for plaster Cut off partition Suspended ventilation duct Suspended ventilation duct Mineral wool with thickness of min 100kg m 3 or fi...

Страница 12: ...head with PROMATECT L 500 board with the thickness of 30 mm Before the frontal closure of the insulation coating tightly fill the gaps between the valve body and the internal circumference of the coa...

Страница 13: ...ounts to 0 mm acc to Fig 8c and 8d 4 4 4 2 Further procedure is analogical as in the case of section 4 4 2 except for number of valve suspensions Fig 8c Fig 8d Mineral wool Duct Suspension axis Suspen...

Страница 14: ...Control cabinet Control cabinet Control cabinet Control cabinet Control cabinet Control cabinet Thermal el Thermal el Thermal el Thermal el Thermal el Thermal el solenoid transformer transformer tran...

Страница 15: ...LF24 ST or BF24 ST actuators via BKN230 24 connect clamps 1 and 3 of thermal element with limit switch to clamps 1 and 2 on the BKN230 24 device in place of the keeper which must be removed 4 6 2 Diag...

Страница 16: ...ace the thermal element item 3 unscrew the nut item 4 press the spring item 7 with the element and after the element item 1 is bent to the side remove the glass element item 3 from the steel clip item...

Страница 17: ...ever item 1 resting on the limiter item 4 and next remove lever item 1 and damaged spring item 2 Place the spring on the middle opening in the manual lever and place the whole on drive shaft item 5 Du...

Страница 18: ...en the valve and hook the manual lever item 1 at the element item 2 For valves in HE version during the test observe correct signalling by micro switch item 3 of cut off partition s position If irregu...

Страница 19: ...P42 IP42 IP54 IP54 IP54 Auxiliary switch 2xEPU 6 3 A 250V 2xEPU 6 3 A 250V 2xSPDT 6 1 5 A AC250V 2xSPDT 6 1 5 A AC 250V Socket to connect BKN230 24LON or BKN230 24MP Connection point 5 80 5 80 5 80 5...

Страница 20: ...f the condition of conductors powering the actuator solenoid and limit switches 6 Assessment of the condition of the partition and the seals expansion and ventilation seal 7 Check of correct closing o...

Отзывы: