background image

 

6.  PERIODICAL MAINTENANCE 

The need for and the required frequency of maintenance results from analogical requirements of the 
installation  including  RK370  or  V370  valves.    If  no  specific  requirements  have  been  defined  for 
periodical maintenance of the installation, or if the periods between particular checks are longer than 

six  months,  check  the  RK370  or  V370  valves  at  least  once  every 
six months. This is the responsibility of the Facility Owner. 
Periodical  maintenance  of  RK370  or  V370  valves  comprises  the 
assessment of their physical condition, and correct operation using 
the Inspection Document at the end of this Documentation. 
It is also recommended to assess the condition of the device using 
the  Inspection  Document  after  the  end  of  assembly  works  and 
launch  of  the  installation  including  the  RK370  or  V370  valves.    In 
order to check correct valve operation, do the following: 

6.1. 

HO  and  HE  versions  –  release  manual  lever  (item  1  Fig. 

13)  from  the  catch  (item  2  Fig.  13)  keeping  the  valve  open.  After 
releasing the lever, it moves freely from the open to closed position, 
closing the valve partition. Next, manually open the valve, and hook 
the manual lever (item 1) at the element (item 2). For valves in HE 
version,  during  the  test,  observe  correct  signalling  by  micro-switch 
(item 3) of cut-off partition's position. 
If irregularities are found, set the micro-switch actuation point (item 
3). 

6.2. 

MR  version  –  disconnect  power  supply  to  the  solenoid.  The 

partition  should  move  to  the  closed  position.  Then  disconnect  the 
solenoid’s power  supply. In MR  version,  manually  turn the  manual 

lever,  leading  to  contact  of  the  keeper  and  the  solenoid.  After  the  partition 
achieves  open  position,  the  manual  lever  will  be  blocked  by  resistance  of  the 
keeper against  solenoid coil, and  valve partition  will remain  open, kept by the 
solenoid.  During  the  test,  in  both  cases,  observe  correct  signalling  by  micro-
switch of cut-off partition's position. In the event of problems with sustaining the 
partition, check for cleanliness of keeper and solenoid surface. 

6.3. 

ER  version  –  disconnect  power  supply  to  the  BELIMO

 

actuator.

 

The 

valve must close (signalled by the steel arrow installed at the actuator axle at 
“0°” position of the scale (Fig. 15 item 1). 

 

 

 

 

 

 

 

 

 

Operation of the air-handling installation with dysfunctional fire valves bears the high risk of their 

non-performance in the event of a fire, and makes the installation user liable. 

 

Open 

O

p

e

n

 

C

lo

se

d

 

Close

 

Fig. 13

 

Fig. 15 

Содержание RK370

Страница 1: ...CAL OPERATIONAL DOCUMENTATION FIRE SAFETY VALVES type V370 and RK370 MANUFACTURER FRAPOL Sp ka z o o 30 832 Krak w ul Mierzeja Wi lana 8 Phone 012 653 27 66 653 27 67 653 26 92 fax 012 653 27 89 MARCH...

Страница 2: ...ERISTICS 3 3 VERSIONS 4 4 PRINCIPLES FOR INSTALLATION OF FIRE VALVES 6 5 PRINCIPLES FOR FIRE VALVES MAINTENANCE 16 6 PERIODICAL MAINTENANCE 18 7 LIST OF SPARE PARTS 19 8 TECHNICAL DATA OF ACTUATORS AN...

Страница 3: ...BELIMO actuator thermal trigger mechanical or electrical thermal element Valves can be furnished with a thermal trigger adjusted to actuation at the temperatures of 72 5 C or 90 5 C For V370 valves bo...

Страница 4: ...heat responsive device involves air stream flowing round the thermal element glass ball or soldered metal plates causes heating of the liquid inside the ball or solder which causes breaking of the gl...

Страница 5: ...ith a return spring made of wire with diameter of 3 mm are furnished with solenoid with keeper holding strength of 120 N Valves with a return spring made of wire with diameter of 3 5 mm are furnished...

Страница 6: ...s switch the cut off partition of the valve from closed to open position at the same time stretching the closing spring After turning the lever to full opening of the valve hook the lever on manual tr...

Страница 7: ...Fig 1a Fig 1b Fig 1c Type RK370 Fig 2a Fig 2b Fig 2c 4 1 4 Check for the size and shape of openings prepared in the walls to set the valves acc to section 4 2 4 1 5 Check whether after valve installa...

Страница 8: ...cumference 4 3 9 On both sides of the valve partition inside the ventilation duct there must be free space to allow for its opening 4 3 10 Electrical installation of the signalisation and powering of...

Страница 9: ...of the valve should remain within the axis of the partition Assembly of the valves in this version in fire barriers class EI120 but with greater thicknesses must be made observing partition depth acc...

Страница 10: ...rier with class EI120 and thickness of 125 mm the cut off partition of the valve should remain in the axis of barrier thickness Valves of V370 type must protrude from the wall on the drive side to the...

Страница 11: ...aster board 12 5mm 4 layers Plaster board 12 5mm 2 warstwy Screws for plaster Cut off partition Suspended ventilation duct Suspended ventilation duct Mineral wool with thickness of min 100kg m 3 or fi...

Страница 12: ...head with PROMATECT L 500 board with the thickness of 30 mm Before the frontal closure of the insulation coating tightly fill the gaps between the valve body and the internal circumference of the coa...

Страница 13: ...ounts to 0 mm acc to Fig 8c and 8d 4 4 4 2 Further procedure is analogical as in the case of section 4 4 2 except for number of valve suspensions Fig 8c Fig 8d Mineral wool Duct Suspension axis Suspen...

Страница 14: ...Control cabinet Control cabinet Control cabinet Control cabinet Control cabinet Control cabinet Thermal el Thermal el Thermal el Thermal el Thermal el Thermal el solenoid transformer transformer tran...

Страница 15: ...LF24 ST or BF24 ST actuators via BKN230 24 connect clamps 1 and 3 of thermal element with limit switch to clamps 1 and 2 on the BKN230 24 device in place of the keeper which must be removed 4 6 2 Diag...

Страница 16: ...ace the thermal element item 3 unscrew the nut item 4 press the spring item 7 with the element and after the element item 1 is bent to the side remove the glass element item 3 from the steel clip item...

Страница 17: ...ever item 1 resting on the limiter item 4 and next remove lever item 1 and damaged spring item 2 Place the spring on the middle opening in the manual lever and place the whole on drive shaft item 5 Du...

Страница 18: ...en the valve and hook the manual lever item 1 at the element item 2 For valves in HE version during the test observe correct signalling by micro switch item 3 of cut off partition s position If irregu...

Страница 19: ...P42 IP42 IP54 IP54 IP54 Auxiliary switch 2xEPU 6 3 A 250V 2xEPU 6 3 A 250V 2xSPDT 6 1 5 A AC250V 2xSPDT 6 1 5 A AC 250V Socket to connect BKN230 24LON or BKN230 24MP Connection point 5 80 5 80 5 80 5...

Страница 20: ...f the condition of conductors powering the actuator solenoid and limit switches 6 Assessment of the condition of the partition and the seals expansion and ventilation seal 7 Check of correct closing o...

Отзывы: