User Manual EML1101
Annex
Pos. Designation
Description
Units Value
range
Options
1
Number of profiles
used.
Limits profile dependant entries in the
basic and load settings.
1-4
2 Highest
add-on
address
Limits the add-on stations to the set value.
0-2, M 0-4, L 0-10
3
Type of profile
switching
Determines how the profile switching
affects the control system.
1)
Immediate
switching
2) Immediate
switching.
P_acc= 0
3) Switching at
beginning of
next measuring
period
4
Reset pulse edge
Determines the edge of the reset pulse
positive/negative
5
Self adjusting
target maximum
demand
Menu for setting the self adjusting target
maximum demand.
5a
Activation
Determines if the self adjusting target
maximum demand is to be carried out.
active/
inactive
5b
Reset by date Reset takes place at a particular date.
Day: 1-31
Hour: 0-24
Minute: 0-59
5c
Reset by
contact
Reset takes place over contact 8.
Grouping function
positive / negative /
both
6 Active
pulse
monitoring
Monitors if this time period between 2
active pulses is exceeded.
s 0-9999
0 = OFF
7
Grouping
function
Activates / deactivates the grouping
function.
Yes/No
8
Units
Determines whether the power settings
are in kW or MW.
kW/MW
Load related programming
1
Priority
Importance of load.
Cyclic switching: equal importance
0-99
2
Channel inversion Determines the switching polarity.
NC/NO contact
3
Group
Identifies to which group the load is
assigned.
0-8
0 = No groups
assigned
2
Power
Maximum power drawn by load
kW
0-6500
3
Min. ON
Minimum ON time.
min:sec 0-999:59
4
Max. OFF
Maximum OFF time
min:sec 0-999:59
5
Min. OFF
Minimum OFF time
min:sec 0-999:59
6
Preference
Determines if the switching times are kept
to in emergency mode.
Time preference /
Power preference
Time/ Date
1 Date
Current
date
TT.MM.YY
2 Time
Current
time
HH.MM.SS