Annex PRELIMINARY
User Manual EML1101
Important!
Disconnect the instrument from the FRAKO Starkstrombus
by pulling the left connection
(contact 1-3) in the contact compartment. If this is not disconnected the update will be interrupted after
the transfer of the boot loader. If this should have happened follow the following instructions:
1.
Disconnect the EML from the mains for ca. 10 seconds
2.
Turn the EML on again. The display remains empty.
3.
Press the reset button for ca. 5 seconds. (see 19.1 factory settings) in the contact
compartment of the EML.
4.
After ca. 30 seconds the EML should start with the old software version.
5.
You can now start the software update again.
In order to carry out a software update OPT-SW disk 1 must be inserted in drive a:
The FRAKO bus connection (contact 1-3) may not be connected!
Do you wish to continue?
Yes
No
After confirmation of this prompt the settings and the historical data will be saved.
The data transfer is carried out over the serial interface after the settings are saved. The progress of
data transfer is displayed in the form of a status bar.
If problems should arise a message will appear in the dialog window.
Loading progress is shown in two progress windows.
EML Software-update: Transfer from boot loader and program!
Status
Transferring
boot
loader!
728
bytes
Progress Data
transfer
1%
Cancel
EML Software-update: Transfer from boot loader and program!
Status
Transferring
program!
1232
bytes