FPI P36D Zero Clearance Direct Vent Gas Fireplace

32

INSTALLATION

Diagram 3

Diagram 5

Diagram 1

Diagram 2

Note: Apply sealant "Mill-Pac" to inner

pipe and high temperature sili-
cone sealant to outer pipe on eve-
ry twist-lock joint.

Diagram 5

Diagram 6

VERTICAL

TERMINATION

1) Maintain the 1-1/4" clearances

(air spaces) to combustibles
when passing through ceilings,
walls, roofs, enclosures, attic
rafter, or other nearby com-
bustible surfaces. Do not pack
air spaces with insulation.
Check for the maximum vertical
rise of the venting system and
the maximum horizontal
offset limitations.

Diagram 7

The four wood screws provided should be
replaced with appropriate fasteners for
stucco, brick, concrete, or other types of
sidings.

Note: If  installing termination on a siding

covered wall, a vinyl siding stand-
off or furring strips must be used
to ensure that the termination is
not recessed into the siding.

7) Before connecting the horizontal run of

vent pipe to the vent termination, slide the
Wall Thimble over the vent pipe.

8) Slide the appliance and vent assembly to-

wards the wall carefully inserting the vent
pipe into the vent cap assembly. It is impor-
tant that the vent pipe extends into the vent
cap sufficient distance so as to result in a
minimum pipe overlap of 1-1/4 inches. Se-
cure the connection between the vent pipe
and the vent cap by attaching the two sheet
metal strips extending from the vent cap
assembly into the outer wall of the vent
pipe. Use the two sheet metal screws
provided to connect the strips to the pipe
section. See Diagram 6.

9) Install wall thimble

in the center of the
10" square and
attach with wood
screws (Diagram
7).

2) Set the gas appliance in

its desired location. Drop
a plumb bob down from
the ceiling to the position
of the appliance flue exit,

and mark the location where the vent will
penetrate the ceiling. Drill a small hole at his
point. Next, drop a plumb bob from the roof
to the hole previously drilled in the ceiling,
and mark the spot where the vent will
penetrate the roof. Determine if ceiling joists,
roof rafters or other framing
will obstruct the venting sys-
tem. You may
wish to relocate
the appliance or
to offset, as
shown in Dia-
gram 2 to avoid
cutting load
bearing mem-
bers.

3) A Firestop spacer must be installed in the

floor or ceiling of every level. To install the
Firestop spacer in a flat ceiling or wall, cut
a 10 inch square hole. Frame the hole as
shown in Diagram 3 and install the firestop.

4) Assemble the desired lengths of pipe and

elbows. Ensure that all pipes and elbow
connections are in the fully twist-locked
position and sealed.

5) Cut a hole in the roof centered on the small

drilled hole placed in the roof in Step 2. The
hole should be of sufficient size to meet the
minimum requirements for clearance to com-
bustibles of 1-1/2". Slip the flashing under
the shingles (shingles should overlap half
the flashing) as per Diagram 4.

    Roof Pitch                  Minimum Vent Height

                                           Feet         Meters

flat to 7/12

2

      0.61

over 7/12 to 8/12

2

0.61

over 8/12 to 9/12

2

0.61

over 9/12 to 10/12

2.5

0.76

over 10/12 to 11/12

3.25

0.99

over 11/12 to 12/12

4

1.22

over 12/12 to 14/12

5

1.52

over 14/12 to 16/12

6

1.83

over 16/12 to 18/12

7

2.13

over 18/12 to 20/12

7.5

2.29

over 20/12 to 21/12

8

2.44

Diagram 4: The upper half of the flashing is

installed under the roofing material and not

nailed down until the chimney is installed.

This allows for small adjustments.

6) Continue to assemble pipe lengths.

Note: If an offset is necessary in the attic

to avoid obstructions, it is impor-
tant to support the vent pipe every
3 feet, to avoid excessive stress
on the elbows, and possible sep-
aration.  Wall straps are available
for this purpose (Diagram 2).

Galvanized pipe is desirable above the roof-
line due to its higher corrosion resistance.
Continue to add pipe sections through the
flashing until the height of the vent cap meets
the minimum height requirements specified in
Diagram 5 or local codes.  Note that for steep

Содержание P36D-LP

Страница 1: ...llowed exactly a fire or explosion may result causing property damage personal injury or loss of life FORYOURSAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity o...

Страница 2: ...me Construction and Safety Standard Title 24 CFR Part 3280 or the current Standard of Fire Safety Criteria for Manufactured Home Installations Sites and Communities ANSI NFPA 501A and with CAN CSA Z24...

Страница 3: ...nds 42 Lighting Plate Instructions 43 SAFETY LABEL Safety Label 5 INSTALLATION Unit Dimensions 6 Before You Start 7 General Safety Information 7 Installation Checklist 7 Locating Your Gas Fireplace 8...

Страница 4: ...h Glass Replacement 44 Bay Glass Replacement 44 Removing Valve 45 Installing Valve 45 REGENCY FLUSH BAY DOOR OPTIONS Flush Trim 47 Louvers Flush 47 Double Screen Door 47 Bay Front 48 Bay Trim 48 Louve...

Страница 5: ...OTE FPI unitsareconstantlybeingimproved Check the label on the unit and if there is a difference the label on the unit is the correct one SAFETY LABEL Copy of Safety Decal for P36D For the State of Ma...

Страница 6: ...FPI P36D Zero Clearance Direct Vent Gas Fireplace 6 UNIT DIMENSIONS...

Страница 7: ...rstothisappliance should be done by a qualified service per son A professional service person should be called to inspect this appliance annually Make it a practice to have all of your gas appliances...

Страница 8: ...ce is Listed for bedroom instal lations when used with a Listed Millivolt Thermostat Some areas may have further requirements check local codes before installation 6 The P36D Direct Vent Gas Fireplace...

Страница 9: ...urface of the carpeting tile etc Minimum Clearance from Top of Unit to Ceiling from top of unit 32 1016mm Side Wall Clearances Bay or Flush Front 6 152mm Barcelona Trim 6 152mm Cast Faceplate 6 152mm...

Страница 10: ...10 INSTALLATION Clearances for Bay or Flush Front Clearances for Barcelona Trim REGENCY CLEARANCES PALACE SERIES CLEARANCES Clearances for The Balmoral The Westminster Front Clearances for The Kensing...

Страница 11: ...L CLEARANCES These drawings are to scale at 1 6 one inch 6 inches Mantel can be installed anywhere in shaded area or higher using the above scale Note Ensure the paint that is used on the mantel and t...

Страница 12: ...t are shown in the diagram below Note A non combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non combustible board These drawings are to scale...

Страница 13: ...the mantel and the facing is heat resistant or the paint may discolour HAMPTON COMBUSTIBLE MANTEL CLEARANCES Because of the extreme heat this fireplace emits the mantel clearances are critical Combust...

Страница 14: ...mantel and the facing is heat resistant or the paint may discolour PALACE SERIES COMBUSTIBLE MANTEL CLEARANCES Because of the extreme heat this fireplace emits the mantel clearances are critical Comb...

Страница 15: ...leg clearances as per diagram Maximum 1 1 2 projection at 2 minimum clearance PALACE SERIES MANTEL LEG CLEARANCES Combustible mantel leg clearances as per diagram Maximum 1 1 2 projection at 2 minimu...

Страница 16: ...6mmhighx921mmwidex441mmdeep Framing Dimensions A B C D 36 1 4 37 1 4 17 3 8 46 1 2 921mm 946mm 441mm 1181mm D isMinimumheighttocombustiblematerials including the Minimum 2 1 2 64mm Top clearance to th...

Страница 17: ...r Palace Series a non combustible material 12 305mm above the unit and 6 153mm on each side must be used See diagram 1 The Barcelona Front and Palace Series also requires steel stud framing above and...

Страница 18: ...ptional Arch Door Series a non combustible material 12 305mm above the unit and 6 153mm on each side must be used See diagram 2 The Arch Door Series also requires steel stud framing above and on each...

Страница 19: ...epending on your facing depth VENTING INTRODUCTION The P36D uses the balanced flue technology Co Axial system The inner liner vents products of combustion to the outside while the outer liner draws ou...

Страница 20: ...ce to inside corner with AstroCap Termination Cap min 6 15cm with Dura Vent Termination Cap 12 30cm H Not to be installed above a meter regulator assembly within 3 90cm horizontally from the centerlin...

Страница 21: ...le liner 4 ft length 2 4 dia flexible liner 4 ft length 3 spring spacers 4 4 thimble 2 5 AstroCap termination cap 1 6 screws 12 7 tube of Mill Pac 1 8 plated screws 8 9 screws 8 x 1 1 2 Drill Point St...

Страница 22: ...gth 7 Galvinized N A N A 4D7A Adjustable Length 7 Black N A N A 4D7AB Adjustable Length 12 Galvinized N A N A 4D12A Adjustable Length 12 Black N A N A 4D12AB 45O Elbow Galvinized 945 4DT EL45 4D45L 45...

Страница 23: ...inches Alternate Horizontal Termination Caps Flat Wall Installation Wall Thickness Vent Length inches Required inches 4 5 1 2 6 7 8 1 2 9 10 11 1 2 12 9 14 1 2 11 14 5 8 Adj Pipe 15 23 1 2 17 24 Adj...

Страница 24: ...7 8 inner diameter Maintain clearances to combustibles Horizontal vent must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall NOTE If you are ins...

Страница 25: ...rances to combustibles Note Must use optional rigid pipe adaptor when using rigid pipe vent systems Part 510 994 VENTING ARRANGEMENTS VERTICAL TERMINATIONS RIGID PIPE SYSTEM Propane Natural Gas The sh...

Страница 26: ...diagram 1 The shaded area in the diagram 1 shows all allowable combinations of straight vertical and offset to vertical terminations with rigid pipe vent systems for Propane and Natural Gas Maximum tw...

Страница 27: ...s is required Horizontal Venting with Three 3 90o Elbows Option V H V V1 H H1 A 0 Min 1 Max 1 Min 2 Max B 1 Min 2 Max 3 Min 3 Max C 2 Min 2 Max 5 Min 4 Max D 3 Min 2 Max 7 Min 5 Max E 4 Min 3Max 9 Min...

Страница 28: ...x 3 Min C 2 Min 3 Max 4 Min D 3 Min 4 Max 6 Min E 4 Min 5 Max 7 Min F 5 Min 6 Max 8 Min G 6 Min 7 Max 9 Min H 7 Min 8 Max 10 Min With these options max total pipe length is 30 feet with min of 10 feet...

Страница 29: ...of the termination cap Required Parts Part Description 946 529 Co linear DV Vertical TerminationCap 948 305 3 Flex 35 ft 946 563 Co Axial to Co Linear Adapter Kit which contains the following Co line...

Страница 30: ...Gas Fireplace 30 INSTALLATION Venting Arrangements Vertical Terminations with Co linear Flex System for both Residential Manufactured Homes into Masonry Fireplaces The shaded area in the diagrams show...

Страница 31: ...ocedure Fourindentations located on the female ends of pipes and fittings are designed to slide straight ontothemaleendsofadjacentpipesand fittings by orienting the four pipe inden tations so they mat...

Страница 32: ...his point Next drop a plumb bob from the roof to the hole previously drilled in the ceiling and mark the spot where the vent will penetratetheroof Determineifceilingjoists roof rafters or other frami...

Страница 33: ...nt System Flex 1 Locate the unit in the framing rough in the gas preferably on the right side of the unit and the electrical Junction block is on the left side on the left Locate the centerline of the...

Страница 34: ...oming into proper contact with the rear burner or thermopile or thermocouple it is always best to consult with your local authorities and the CAN CGA B149 installation code For USA installations follo...

Страница 35: ...6 Pull off the pilot cap to expose the pilot orifice Burner Orifice 7 Unscrew the pilot orifice with the allen key and replace with the LP pilot orifice in the kit and replace pilot cap 9 Reinstall n...

Страница 36: ...al Brick Panels install the Brick Pan els prior to installing the logs 1 Carefully remove the logs from the box and unwrap them The logs are fragile handle with care do not force into position 3 Place...

Страница 37: ...right end sits behind the rear grate tab Front Brackets Notch 02 50 02 55 02 53 02 50 02 55 02 53 9 Sit Log 02 50 on the front left side of the burner Push the back of the log against the 2 front bra...

Страница 38: ...flush door comes with a black frame To install the frame simply hook the top door flange onto the top of the unit and swing the door towards the unit see diagram 1 Be careful that the glass gasket doe...

Страница 39: ...ntrol kit comes with a hand held transmitter a receiver and a wall mounting plate 1 Choose a convenient location on the wall to install the receiver and the receptacle box protection from extreme heat...

Страница 40: ...o bring power to the receptacle box provided with the unit in case the fan is installed at a later date CAUTION Label all wires prior to disconnectionwhenservicingcon trols Wiring errors can cause im...

Страница 41: ...approximately 4 from the control box Ensure that there is no interference with the wires when the louver is closed and that no wire will touch the hot metal surfaces or sharp edges 13 Plug the fan pow...

Страница 42: ...rst time before you use it with the fan on When first operated the unit will release an odour caused by the curing of the paint the burning off of any oils remaining from manufac turing Smoke detector...

Страница 43: ...abel 1 Push in gas control knob slightly and turn clockwise to OFF Knob cannot be turned from PI LOT to OFF unless knob is pushed in slightly Do not force 2 Wait five 5 minutes to clear out any gas If...

Страница 44: ...lacement you must use the proper replacementlog Thepositionoftheselogsmust be as shown in the diagrams under Log Instal lation Note Improper positioning of logs may create carbon build up and will sev...

Страница 45: ...appliance performance 9 Reinstall the 10 hold down screws 10 Hook up the 2 TP and 2 TH wires to the appropriate connections on the valve 11 Reinstall the bottom brick panel and the front log stand 12...

Страница 46: ...FPI P36D Zero Clearance Direct Vent Gas Fireplace 46 FLUSH BAY DOOR OPTIONS...

Страница 47: ...of the bottom louver Push down to lock into place Tighten the screws Screws on louver bracket Burner ON OFF control box attached to bottom flush louver Burner ON OFF control box FLUSH TRIM Attach the...

Страница 48: ...andard flush door and glass must remain on the unit 1 Slide the Bay Deflector into the 2 Bay Deflector brackets in the top of the unit 2 Hook the top of the bay door over the flush door flange and swi...

Страница 49: ...e the inner cut outs to secure the base of the Frame using the 2 x Hex Head Drill Point Screws provided Backside of Full Screen Door Frame Shown Inside Top of Outer Frame Hinge Bracket Inner Hinge Bra...

Страница 50: ...Install the Left and Right Side Screen Doors in the fully open position by placing over top of the hinges on the Full Screen Door Frame NOTE Failuretoinstallthedoorsinthefullyopenpositioncouldresult...

Страница 51: ...terial has to go on after the unit is set 1 Remove Glass Door Refer to P36 Manual 2 Remove 2 screws and bracket as indicated 3 Install On Off switch 4 Place bracket under the Flange Secure with 2 scre...

Страница 52: ...nding hole on the Top Support Frame then secure with 1 screw b Repeat step on the other side Diagram 2 10 Change in Logo Replace existing logo with Regency logo a Mount Side Support Frame to unit as s...

Страница 53: ...FPI P36D Zero Clearance Direct Vent Gas Fireplace 53 CAST FACEPLATE...

Страница 54: ...f faceplate with screw 4 Repeat step 3 for the right side faceplate Secure bottom of faceplate with screw 5 Slide top piece of faceplate into side faceplates by fitting mounting plates into brackets 6...

Страница 55: ...emoved in step 3 5 Install hinge to bracket then secure with screw New hinge bracket Left side shown 6 Place something underneath bottom grill to prevent scratching 7 Line up hinge holes in bottom gri...

Страница 56: ...FPI P36D Zero Clearance Direct Vent Gas Fireplace 56 The Westminster Front INSTALLATION The Kensington Front The Balmoral Front...

Страница 57: ...on the inside top of the firebox Bracket inside top of firebox Kensington Front frame 4 Remove existing control switch box from under firebox by discon necting wires connected to the valve at TH TH T...

Страница 58: ...eft and right side of the firebox Slide frame in place and secure Left Side Shown Hinge bracket on bottom of firebox 4 Slide tabs into louver brackets located on the inside top of the firebox Westmins...

Страница 59: ...and secure Left Side Shown Hinge bracket on bottom of firebox 4 Remove existing control switch box from under firebox by discon necting wires connected to the valve at TH TH TP terminals and discard...

Страница 60: ...er 3 Connect new fan control box wires to the existing fan plug wires red to red black to black Disconnect Wires Fan Control Box Fan Control Box Vertical Hinge Bracket Discard Fan Cover with Wires New...

Страница 61: ...s 1 Install sub frame by hooking top over glass door push in bottom of frame and secure with 2 screws Sub Frame 2 Mount 2 panel door frame to flange on sub frame ensuring to line up holes Secure using...

Страница 62: ...FPI P36D Zero Clearance Direct Vent Gas Fireplace 62 REPLACEMENT PARTS LIST...

Страница 63: ...241 Switch Burner ON OFF 3 way 910 899 Wire Harness Valve to Burner 432 917 Fan Speed Control Assy 120 Volts Optional 42 910 331 P Fan Motor 432 966 Fan Switch Assy 120 Volts Optional 43 910 813 Powe...

Страница 64: ...P 57 910 378 Valve S I T Natural Gas 910 380 Valve S I T Propane 58 Valve Bracket 65 Pilot Bracket 66 910 038 Pilot Assy S I T 3 Flame NG 910 039 Pilot Assy S I T 3 Flame LP 67 PilotHolder 68 W840470...

Страница 65: ...rick Panel Standard Brown 780 906 Bay Brick Panel Standard Red 780 938 Bay Front Trim Set Brass 780 936 Bay Front Trim Set Steel 112 Bay Front Trim Top Bottom 780 934 Bay Front Trim Set Gold 113 Bay F...

Страница 66: ...Set Steel Black 138 Flush Louver Assy Top 139 Flush Louver Assy Btm 146 Barcelona Assy Black 148 Barcelona Louver Assy Black 510 934 Flush Glass Trim Set Brass 510 947 Flush Glass Trim Set Steel 152...

Страница 67: ...LY Part Description 513 971 Cast Faceplate Set 201 Cast Faceplate Right 202 Cast Faceplate Top 203 Cast Faceplate Left 513 981 Cast Grills Set 204 Top Grill 205 BottomGrill Not available as a replacem...

Страница 68: ...______________________________________________________ ______________________________________________________ _______________________________________________________________ __________________________...

Страница 69: ...______________________________________________________ ______________________________________________________ _______________________________________________________________ __________________________...

Страница 70: ...______________________________________________________ ______________________________________________________ _______________________________________________________________ __________________________...

Страница 71: ...ed and inspected by an authorized dealer within three days of installation Reported damage after this time will be subject to rejection It is the general practice of FPI to charge for larger higher pr...

Страница 72: ...pton and Panorama are trademarks of FPI Fireplace Products International Ltd FPI fireplaces are designed with reliability and simplicity in mind In addition our internal Quality Assurance Team careful...

Отзывы: