background image

Operating Profile Select Inputs: 

Two (2) profile select inputs are available for selecting up to four (4) different profiles, numbered from 
0 to 3 stored in its non-volatile memory.  Each profile select input is sourced (5 VDC) from the detector 
itself and must be wired to a potential free contact controlled by BMS or other control system. Do not 
connect external power to profile select input terminals.

The stored profiles are intended to allow for easy switching between commonly used burner operating 
conditions without requiring manual re-tuning of the flame amplifier. Each profile contains a full set of 
operating parameters see Table 210 Operating Profiles.

The amplifier reads the profile selected by the Profile Select input code and displays the Active Profile 
number in the lower right corner of the Termiflex / SmartDisplay®.  The Active Profile can be changed 
at any time other than while in the tuning loop by repositioning the Profile Select inputs.  Any tuning 
parameter changes can be saved only to the Active Profile.  Example:  Active Profile 0 is displayed as 
“Set 0”.

Table 2-10 Profile Select Input Encoding

Profile Select 1 

J12-TB 1

Profile Select 2

J12-TB2

ACTIVE PROFILE

OPEN

OPEN

Set 0

CLOSE

OPEN

Set 1

OPEN

CLOSE

Set 2

CLOSE

CLOSE

Set 3

Operating Modes

All operating profiles are initialized via a profile flag and with the default settings shown.  

Table 2-11 Operating Profiles

Termiflex Display

Mode 1: IDD PPS only

Setting Range

IDD GAIN

0

0 through 15

SPECTRAL RANGES

1

CORNER 1

80 Hz

12 -1024

CORNER 2

200 Hz

12 -1024

WEIGHT 1

1

1 through 9

Power PCB installed on the base includes terminals for wiring as well as LEDs 

for troubleshooting

 LED 4 (Yellow)

Steady when 24 VDC input power is present.

 LED 11 (Yellow)

Steady when 15 VDC output power to Detector head is present.

 LED 10 (Yellow)

Steady when 5 VDC output power is present.

 LED 1 (Yellow) 

Steady when 50 VDC output power to detector head is present.

3

372001-24 Rev. A

IDDX Flame Detector Amplifier Manual

Содержание IDDX

Страница 1: ...www forneycorp com BURNERS IGNITERS DAMPERS CONTROLS IDDX Flame Detector Amplifier Manual Publication 372001 24 Rev A...

Страница 2: ...the equipment NOTICE If any of the procedures or instructions provided in this manual are unclear contact Forney for resolution Forney Corporation offers complete on site service solutions to ensure...

Страница 3: ...PM IDD9000 Flame Amplifier 372001 02 Rev Kv TABLE OF CONTENTS...

Страница 4: ...Setup and Configuration Mode IDD Channel Tuning Flame Failure Response Time Delay for Modes 1 Self Check Cycle Time for Modes 1 Saving Configuration Functions Unavailable While Tuning Analog Outputs A...

Страница 5: ...gment when confronted with situations that are not specifically mentioned herein The contents of this publication are proprietary data of Forney Corporation Reproduction or use of any part of the publ...

Страница 6: ...labels are as follows IDD Detector Manual DANGER Indicates a hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a hazardous situation which if not avoide...

Страница 7: ...II IDD IIU IDD IIL Ultra The IDDX is designed to work with any one of the following Forney flame detectors Detector Forney Part Number IDD II 3832121 IDD IIU 3832122 IDD IIL 3832123 IDD Ultra 3832129...

Страница 8: ...ection of fault Thus fault relays contacts are in closed state until any fault is detected The IDDX amplifier checks for broken wire or disconnected IDD detector head or loss of 15 VDC power to detect...

Страница 9: ...an while in the tuning loop by repositioning the Profile Select inputs Any tuning parameter changes can be saved only to the Active Profile Example Active Profile 0 is displayed as Set 0 Table 2 10 Pr...

Страница 10: ...the IDDX This port enable communication between the microprocessors on the board and a hand held Termiflex SmartDisplay via RS422 communication protocols Upon completion of installation the user must...

Страница 11: ...Figure 1 IDDX Flame Amplifier 5 372001 24 Rev A IDDX Flame Detector Amplifier Manual...

Страница 12: ...HD 01 EX Flame Detector 372001 23 Rev A 6 DIMENSIONS 1 2 Figure 2 IDDX Flame Amplifier Dimensions in inches 6 372001 24 Rev A IDDX Flame Detector Amplifier Manual...

Страница 13: ...mA Fuse Required in series SPST 250VAC 5A Conformal Coating No Relay Operating Cycle Min 20 X 106 Operations Flame Failure Response Time FFRT 1 2 3 3 8 second user adjustable Fault Relay 1 Analog Out...

Страница 14: ...D II Filtered IR Detector 700nm 3300nm IDD IIL Low Frequency IR Detector 700nm 3300nm IDD IIU Unfiltered IR Detector 400nm 3300nm IDD Ultra UV Detector 200nm 425nm Table 1 Codes and Standards The IDDX...

Страница 15: ...eratures are expected to exceed specified limits cabinet must be installed in a controlled environment Ensure that the IDDX Flame Amplifier and associated cabling is located at a safe distance from hi...

Страница 16: ...v A IDDX Flame Detector Amplifier Manual WIRING 2 3 Figure 8 IDDX WIRING DAIGRAM Voltage Internal PTC Fuse Description 50V 10mA 0 5W Sensor Bias Supply 15V 50mA 30V 0 6W Sensor Logic Supply 15V 50mA 3...

Страница 17: ...Open for External BMS system J2 Connector Reserved for Future Use 1 GND Electrical Ground return for System 2 B Reserved for Future Use 3 A Reserved for Future Use J1 Connector IDD Head Connector 1 Sh...

Страница 18: ...ifier is tuned in the active mode only Note During tuning any changes that cause loss of flame indication will be transmitted to the main flame relay following the FFRT delay While tuning if the main...

Страница 19: ...ion will also set output gain If lack of gain is realized then gain setting should be increased Note Any flame detector connected to the unselected mode input will receive power but is not monitored f...

Страница 20: ...from the left side to the approximate center of the display while the burner is operating The GAIN value is stored as a number from 0 to 15 where 15 corresponds to the maximum GAIN of 32x Gain setting...

Страница 21: ...available to produce a notch filter function if a difficult application requires this option The incoming detector head signal may be tuned in 1 or 2 ranges The ranges cover from 12Hz to 1024HZ The s...

Страница 22: ...the value entered to the next smaller value that is evenly divisible by 4 For example if the user enters 50Hz the value will be automatically changed to 48Hz when it is accepted Set the lower end firs...

Страница 23: ...cies than the first No overlap between the two ranges is allowed Therefore the upper corner of the lower range cannot be specified to a frequency higher than the low corner of the upper range Corners...

Страница 24: ...he pick up point should be less than the average signal value i e IDD SIGNAL 956 and greater than the minimum signal value i e LO 560 The dropout value should be less than the minimum signal value i e...

Страница 25: ...n to almost nothing more than ON OFF To convey the most information set the HI to the actual high displayed on the IDD Signal screen and the low to a value lower than the dropout DO value which would...

Страница 26: ...below the Drop Out point DO which is programmed into the amplifier during setup On Flame Failure the flame and lamp outputs turn off The alarm output is not changed Signal acquisition continues Flame...

Страница 27: ...ve on both Channels During self check the detectors are blinded for a brief interval After a short delay the signal levels are compared and self check failure occurs if a detector s output is above it...

Страница 28: ...ck out to fail safe as required Press the RESET button on the front panel to restore the original settings and start again If SELF CHECK passes select SAVE NEW and you may want to sweep thru the setti...

Страница 29: ...ity The analog outputs 4 20mA is linearly scaled between the programmed low and high points respectively These will output minimum 4mA if the input channel is off or the signal level is at or below th...

Страница 30: ...licate electronic circuitry Therefore it is advisable to discharge any static electricity prior to handling the unit Additionally the IDDX Detector amplifier should be handled delicately without aggre...

Страница 31: ...turn on TROUBLESHOOTING 4 2 Symptom Indicator Possible Cause Remedy Self Check Cycle Fail ALM LED ON IDD CK FAIL Message on Termiflex IDD Signal Too High 3000 leading to Sensor Saturation Reduce Gain...

Страница 32: ...roviding 24 VDC on these terminals No Change in Profile No change in Profile LEDs status of P1 P2 External PLC System and Amplifier GND not common Check connection with J12 Verify control system conta...

Страница 33: ...provide the contract number or the customer purchase order number To order IDDX Flame Amplifiers or associated equipment contact Forney s Aftermarket Department via any one of the following methods a...

Страница 34: ...dentification Exercise care in packing the materials units to be returned The shipper will be advised of any damage due to improper packing and no further action will be taken in connection with this...

Страница 35: ...frared kHz Kilohertz LED Light Emitting Diode mA Milliampere NPT National Pipe Thread NPTF National Pipe Thread Fine OEM Original Equipment Manufacturer P N Part Number PLTC ER Power Limited Tray Cabl...

Страница 36: ...t Europ enne European Conformity CEC Canadian Electrical Code EN European Norm EOTA European Organization for Technical Assessment FM Factory Mutual Approval IEC International Electro Technical Commis...

Отзывы: