HD-01-EX Flame Detector
372001-23 Rev. A
4
A serial communication port is located on the front of the IDDX. This port enable communication be-
tween the microprocessors on the board and a hand-held Termiflex/ SmartDisplay® via RS422 commu-
nication protocols.
Upon completion of installation, the user must connect the Termiflex/ SmartDisplay® to the amplifier
and revise the tuning parameters suitable to detect the presence and absence of target flame. Us-
er-supplied tuning parameters are stored and remain unchanged until overwritten with new tuning
parameters.
4
372001-24 Rev. A
A serial communication port is located on the front of the IDDX. This port enable communication
between the microprocessors on the board and a hand-held Termiflex/ SmartDisplay® via RS422
communication protocols.
Upon completion of installation, the user must connect the Termiflex/ SmartDisplay® to the amplifier
and revise the tuning parameters suitable to detect the presence and absence of target flame. User-
supplied tuning parameters are stored and remain unchanged until overwritten with new tuning
parameters.
Table 2-11 Operating Profiles
Termiflex Display
Mode 1: IDD PPS only
Setting Range
CORNER 3
1024 Hz
12-1024
CORNER 4
1024 Hz
12-1024
WEIGHT 2
1
1 through 9
IDD PICKUP- PPS
500
1-4095
IDD DROPOUT- PPS
100
1-4085
IDD ANALOG LOW- PPS
0
0-3000
IDD ANALOG HIGH- PPS
3000
0-4095
FFRT
3.8 Seconds
1,2,3.8
CHECK DELAY
120 Seconds
30 to 600 seconds