Press F1 - CHG
F1 - LO - type in lower corner frequency i.e. “100”
F4 - OK
F2 - HI - type in higher corner frequency i.e. “140”
F4 - OK
F3 - WF - type in “2”
F4 - OK
F4 - OK
F4 - NXT
The second range, if used, must be located at higher
frequencies than the first. No overlap between the two
ranges is allowed. Therefore, the upper corner of the
lower range cannot be specified to a frequency higher
than the low corner of the upper range. Corners and
WF for Range 2 are changed the same as Range 1.
17
372001-24 Rev. A
IDDX Flame Detector Amplifier Manual
Termiflex WF
Multiplying WF
1
1
2
1.5
3
2
4
2.5
5
3
6
3.5
7
4
8
4.5
9
5
Table 3-3 Weight Factor Range