22
372001-24 Rev. A
IDDX Flame Detector Amplifier Manual
Saving Configuration
The RESTORE OR SAVE screen gives you 3 options.
• TEST your setup using F4 to do a SELF CHECK.
• SAVE your setup using F2 to do a SAVE NEW.
• DISCARD your setup using F1 to reload the PREVIOUS SETTINGS.
If the SELF CHECK fails, the unit does a lock out, to fail safe, as required. Press the RESET button on
the front panel to restore the original settings, and start again.
If SELF CHECK passes, select SAVE NEW and you may want to sweep thru the settings again for further
tweaking.
• F2 - SAVE NEW
Caution:
If the system is left in tuning mode without saving, it will time out after 10 minutes to the previously
SAVED parameters. However, if the Termiflex is removed without saving the new configurations, it