Type C32

This boiler is designed for vertical air/flue gas terminals, connected 

to the outside by means of coaxial or split pipes.

The distance between the air intake pipe and the flue gas pipe is 

to be at least 250 mm and both terminals
are positioned within a square having 500 mm sides.

• Air / flue gas coaxial pipe, 60/100 mm diameter.

Allowable configuration:
1 flanged stub pipe
4 meter long coaxial pipe
1 air/flue gas roof terminal.

Notes: 
- Reduce maximum length by 1 meter for each 90° elbow.
- Reduce maximum length by 0.5 meter for each 45° elbow.

• Air / flue gas 80 mm diameter split pipes

Allowable configuration:
2 flanged stub pipes
19 meter long air intake pipe
19 meter long flue gas pipe
1 air intake terminal
1 flue gas terminal

Notes: 
- Reduce maximum length by 1 meter for each 90° elbow.
- Reduce maximum length by 0.5 meter for each 45° elbow.
BTFS 24 model: in installations with an equivalent length of less 
than 2+2 meters, install a 42 mm diaphragm on the air intake.
BTFS 32 and BTFS 36 models: in installations with an equivalent 
length of less than 9+9 meters, install a 40 mm diaphragm on the 
air intake.

Type C42

This  boiler  is  designed  for  a  collective  flue  gas  exhaust  system 

consisting of two pipes, one for air intake and the other for flue gas, 

by means of a coaxial or split pipes.

     
The  collective  flue  gas  exhaust  system  must  comply  with 
current laws.

• Air / flue gas 80 mm diameter split pipes

Allowable configuration:
2 flanged stub pipes
2 meter long air intake pipe
2 meter long flue gas pipe

Notes: 
- Reduce maximum length by 1 meter for each 90° elbow.
- Reduce maximum length by 0.5 meter for each 45° elbow.
BTFS 24 model: install a 42 mm diaphragm on the air intake.
-  BTFS  32  and  BTFS  36  models:  install  a  40  mm  diaphragm  on 
the air intake.

Type C52

This boiler is to be connected to a split pipe system.
The pipes can operate at different pressure. Terminals cannot 
be placed on walls facing each other.

• Air intake/ flue gas 80 mm diameter split pipes

Roof mounted flue gas terminal.
Allowable configuration for max length of split pipes:
2 flanged stub pipes
1 meter long air intake pipe
30 meter long flue gas pipe
1 air intake terminal
1 roof-mounted smoke flue terminal

Notes: 
- 1 meter of air intake pipe is equivalent to 2 meters of vertical 
flue gas pipe.
- Reduce maximum length by 1 meter for each 90° elbow.
- Reduce maximum length by 0.5 meter for each 45° elbow.
- BTFS 24 model: in installations with an equivalent vertical flue 
gas pipe length, less than 18 meters, install a 40 mm diaphragm 
on the air intake.
BTFS 32 and BTFS 36 models: in installations with an equiva-
lent vertical flue pipe length, less than 4 meters, install a 42 mm 
diaphragm on the air intake.

Wall-mounted flue gas pipe
Allowable configuration for max length of split pipes:
2 flanged stub pipes
19 meter long air intake pipe
19 meter long flue gas pipe
1 air intake terminal
1 flue gas terminal

Notes: 
- 1.6 meters long air intake pipe is equivalent to 1 meters hori-
zontal flue gas pipe.
- Reduce maximum length by 1 meter for each 90° elbow.
- Reduce maximum length by 0.5 meter for each 45° elbow.
BTFS 24 model: in installations with an equivalent length of less 
than 9+9 meters, install a 40 mm diaphragm on the air intake.
BTFS 32 and BTFS 36 models: in installations with an equiva-
lent length of less than 2+2 meters, install a 42 mm diaphragm 
on the air intake.

 
Type C82

This boiler is designed to be connected to a terminal for intaking of 
combustion air and an individual or collective flue gas system.
The flue gas system is to comply with current standards.

• Air / flue gas 80 mm diameter split pipes

Allowable configuration for max length of split pipes:
2 flanged stub pipes
4 meter long air intake pipe
1 meter long flue gas pipe
1 air intake terminal

Notes: 
- 1.6 meter long air intake pipe is equivalent to 1 meter long hori-
zontal flue gas pipe.
- Reduce maximum length by 1 meter for each 90° elbow.
- Reduce maximum length by 0.5 meter for each 45° elbow.
BTFS 24 model: install a 42 mm diaphragm on the air intake.
-  BTFS  32  and  BTFS  36  models:  install  a  40  mm  diaphragm  on 
the air intake.

16

Содержание BALI B BTFSE 24

Страница 1: ...IST 03 C 192 01 INSTALLATION USE AND MAINTENANCE BALI B BTNE 25 BTNE 32 BTNE 42 BTFSE 24 BTFSE 32 BTFSE 36 GB...

Страница 2: ...Dear Customer Thank you for choosing and buying one of our boilers Please read these instructions carefully in order to install operate and maintain this equipment properly 1...

Страница 3: ...ment sites Keep the packaging out of the reach of children as by its nature it may represent a hazard In the event of failure and or faulty functioning switch off the boiler Do not attempt to repair i...

Страница 4: ...of temperature probes page 9 1 3 Maintenance page 9 1 4 Information for the user page 9 2 Technical characteristics and dimensions page 10 2 1 Technical characteristics page 10 2 2 Dimensions page 10...

Страница 5: ...operates in CH and instantaneous DHW supply mode only As soon as the probe is replaced the boiler will resume operation 8 Indication light red when the light is on and fixed it indicates that the temp...

Страница 6: ...liters per minute relies upon the boiler thermal output and water main supply temperature according to the fol lowing formula l DHW in liters per minute K T K represents 344 for BTFS 24 model 459 for...

Страница 7: ...t when the boiler is equipped with an external temperature probe the user sets a fictitious room temperature va lue via knob 13 please see SLIDING TEMPERATURE OPERA TION section Knob 13 is used to adj...

Страница 8: ...of the week current time ON and OFF pro grams please see below sections B and C B Setting the day of the week and current time Position selector 2 to RUN and press h and m buttons at the same time unt...

Страница 9: ...will be displayed fixed and symbol will be displayed indicator 4 now the chan nel will be permanently active Rapidly set selector 1 to position O without stopping in position AUTO press once or twice...

Страница 10: ...usehold products Do not use water As provided by law the boiler is to be serviced once a year Correct maintenance ensures boiler to function efficiently environmentally friendly preventing any danger...

Страница 11: ...aracteristics High output cast iron heat exchanger Stainless steel plate DHW heat exchanger Stainless steel horizontal stratification 60 l water tank with sacrificial magnesium anode Glass wool alumin...

Страница 12: ...inlet C DHW flow F Cold water inlet M CH flow R CH return G Gas inlet C DHW flow F Cold water inlet M CH flow R CH return M1 Low temperature zone flow M2 Low temperature zone return D Flue gas outlet...

Страница 13: ...CAST HEAT EXCHANGER BURNER Plate heat exchanger probe Zone 1 high temperature Thermostatic valve DHW Cold water inlet Water tank probe Water tank VM 2 way Cold water inlet Zone 1 high temperature Zon...

Страница 14: ...16 4 Water tank capacity l 60 60 60 60 60 60 DHW supply T 30K EN 625 l 10 220 242 280 215 245 253 prEN 13203 efficiency rating Min DHW flow rate l min 3 3 3 3 3 3 Min DHW pressure bar 1 1 1 1 1 1 Max...

Страница 15: ...manual Four legs with threads 3 2 2 Choosing where to install the boiler When choosing where to install the boiler follow the instructions below indications in paragraph 3 2 5 Air flue gas system conf...

Страница 16: ...lination toward the ground of at least 5 The terminal is to ensure efficient constant evacuation of flue gas in any weather condition The flue gas terminal is to stand at least 0 5 m above any adjacen...

Страница 17: ...0 mm diameter split pipes Roof mounted flue gas terminal Allowable configuration for max length of split pipes 2 flanged stub pipes 1 meter long air intake pipe 30 meter long flue gas pipe 1 air intak...

Страница 18: ...damage or injury cau sed by failure to properly earth the power main Gas lines DHW and CH pipes are not suitable for earthing purpo ses 3 2 9 Hydraulic connections Before connecting the boiler it is a...

Страница 19: ...through water mains inlet tap on the boiler as necessary Water pressure adjustment must be performed when the system is cold The thermo manometer gauge on the boiler allows for che cking the pressure...

Страница 20: ...er P3 boiler operating mode selector P2 DHW temperature adjusting potentiometer P1 CH temperature adjusting potentiometer IG two poled main power switch BC flame detection pcb VG gas valve E RIV flame...

Страница 21: ...NECTION M1 M24 AVAILABLE CONNECTORS X1 X8 AVAILABLE CONNECTORS CT PHONE CONNECTION DEVICE OPTIONAL EQUIPMENT FUSE SP 2 AF 250 Vac FUSE FUSE SZ 2 5 AF 250 Vac FUSE P4 HIGH TEMPERATURE CH CURVES ADJUSTI...

Страница 22: ...ted by qualified personnel In order to verify nozzle and gas inlet pressure connect a mano meter to checks on the gas valve Boilers are factory set according to gas type requested upon order Any later...

Страница 23: ...the plate heat exchanger The boiler has shut down and red light no 4 is flashing Restore correct water pressure Insufficient water pressure Possible water leaks Check system for leaks Pressure switch...

Страница 24: ...has not sufficient pressu re or flow rate Check DHW system Check flow meter filter Flow meter sensor is faulty or discon nected Replace or reconnect it Flow meter is blocked Replace it Burner does not...

Страница 25: ...24...

Страница 26: ...25...

Страница 27: ...26...

Страница 28: ...ax 39 0365 878 576 e mail fondital fondital it www fondital it The MANUFACTURER reserves the right to implement any necessary and or useful variation to products without modifying fundamental characte...

Отзывы: