00981795R03 – FZR20/25 LB, PL
Appendix
37
Appendix
Control key functions
Scroll up
Enter main menu
Scroll down
Return to prior
Select
Mutes alarm
Buttons to select
screen options
Cabinet light ON/OFF
Alarm light
Back
MENU
MUTE
ENTER
Menu Navigation table
Main Menu
Submenu
Default
Setting
Range
Notes
Alarm Settings
High Alarm Set
40 C
40 C to Lo Alarm
Default is set high to not alarm on initial cool
down
Low Alarm Set
-40 C
-40 C to Hi Alarm
Display Settings
Show Bottom Temp
No
Yes / No
—
Display Inverse
Yes
Yes / No
Yes = light lettering with dark background
Degrees F/C
C
F or C
Displays temperatures in F or C
Min/Max Temp
Min
—
—
Records min/max temperature and time of top
probe. Up/down arrow displays min/max. Enter to
reset.
Batt = _V OK
—
—
—
Shows status of (2) 9 V batteries
Refrigeration
Controls
(ENTER +
▼
for
3 s)
Calibration
Cal Top Probe
—
—
Adjust with up/down arrow, press enter to set
Cal Bottom Probe
—
—
Adjust with up/down arrow, press enter to set
Refrigeration Setpoint:
PL
LB
-31 C
-24 C
40 C to -40 C
40 C to -40 C
—
Differential
1 C
1 to 2 C
—
Hi Setpoint Limit
-15 C
40 C to Lo Set Pt
—
Lo Setpoint Limit
-32 C
-40 C to Hi Set Pt
—
Door Heater Cycle
75%
0 to 100%
0 to 100% of 20 minute cycle
Faulty Probe
Cycle
On Time
6 min
2 to 14 min
Compressor On time
Off Time
5 min
2 to 14 min
Compressor Off time
Temp Sensors
—
—
RTD1, RTD2, NTC1 and NTC2 displayed
Defrost
Defrost Interval
4 hrs
2 to 6 hrs
Time between defrosts.
Defrost End Temp
5 C
5 to 10 C
Temperature that terminates defrost
Defrost End Time
30 min
10 to 60 min
Time that terminates defrost
Evap Fan Delay
6 min
4 to 6 min
Fan start delay after defrost terminates
Drip Delay
2 min
0 to 2 min
Delays compressor start after defrost terminates
Test Defrost
—
—
Press ENTER +
▼
for 3 seconds to initiate
Password On/Off
—
Off
On / Off
—
PIN
—
3843
0000 to 9999
Any four digit PIN can be stored in addition to the
permanent factory default. Adjust with up/down
arrow, NEXT moves to next digit, press ENTER
to set.
Set Time / Date
YYYY MM DD HH:MM
00:00 to 24:00
Adjust with up/down arrow, NEXT moves to next
digit, press ENTER to set.
Set Alarm Volume
—
High
High/Med/Low
Buzzer Volume
Alarm Silence
Audible alarm
On
On / Off