28 Service
00981795R03 – FZR20/25 LB, PL
Defrost Settings
Fig. 71
1. Press Menu button.
2. Use
to scroll and highlight
Refrigeration Controls (Fig. 71).
Fig. 72
3. Press and hold Enter and Down ( ) button for 3 seconds, until new
submenu appears with
Calibration highlighted (Fig. 72).
Fig. 73
4. Use
to scroll and highlight
Defrost (Fig. 73) and press Enter to
select.
Fig. 74
5. Defrost Interval will be highlighted (Fig. 74), press Enter to view.
The defrost interval is factory-set to every 4 hours -
consult Technical
Service prior to changing
.
6. Press Back to return to the Defrost Interval screen.
Refrigeration Controls
Password on/off
PIN
Set Time/Date
-30.0C
Back Enter
Calibration
Refrig Setpoint
Differential
High Setpoint Limit
Low Setpoint Limit
-30.0C
Back Enter
Faulty Probe Time
Temp Sensors
Defrost
-30.0C
Back Enter
Defrost Interval
Defrost End Temp
Defrost End Time
Evap Fan Delay
-30.0C
Back Enter