22
Installer information
FLUE SPILLAGE MONITORING SYSTEM
This fire is fitted with a flue spillage safety device (ODS). If the fire shuts
down during use for no apparent reason then several things may be
suspected. If a door or window has been opened creating a draught,
then pilot disturbance is the problem, and removal of the draught should
resolve this. The gas pressure reaching the fire must also be checked. The
thermocouple connection into the back of the gas control valve may also
have worked loose during installation, simply tighten to remedy if this is
the case.
If pilot disturbance is not the cause, then the ODS safety system may be
in operation. Switch the appliance OFF, check the flue and carry out any
remedial work required. Relight the fire and carry out a spillage test. DO
NOT allow the appliance to be used if it continues to fail a spillage test.
The aeration hole of the pilot must be carefully cleaned out on each annual
service to ensure continued function of the ODS.
For installation in Germany a TTB is required to be fitted in the Front Top
corner of the appliance. This will work in parallel to the ODS system, and
will operate under similar circumstances.
The spillage monitoring systems shall not be adjusted, modified, or put
out of operation by the installer. Any spare parts fitted MUST be of a type
supplied for the purpose by the appliance manufacturer.
If the fire is not spilling, then further guidance should be sought, using the
Troubleshooting section as a guide.
TESTING FOR SPILLAGE
Close all doors and windows to the room containing the appliance. Let the
fire run on HIGH for ten minutes.
Take a smoke match, light it, and using a smoke match tube, hold it at the
top edge of the fire opening, 25mm down and 25mm in. Starting 50mm in
from either side, run the smoke match across the opening. All the smoke
should be drawn away up the flue. Any smoke returning into the room
indicates that spillage is occurring. If the initial spillage test fails, run the
fire for a further 10 minutes and repeat the test. When the test has been
completed satisfactorily, repeat with any extractor fans in the premises
running on the highest setting, and any communicating doors open.
Finally, repeat with all doors open.
NOTE: If spillage is still indicated after undertaking all of the above, there
may be a fault in the flue, or insufficient ventilation is present.
If the problem cannot be rectified immediately, then expert advice should
be sought. Inform the user, disconnect the fire, and attach an explanatory
label.
BRIEFING THE CUSTOMER
All instructions must be handed to the user for safekeeping. Show the
customer how to light and control the fire.
After commissioning the appliance, the customer should be instructed on
the safe use of the appliance and the need for regular servicing. Frequency
of service depends on usage, but MUST be carried out at least once
annually
SERVICING INSTRUCTIONS
This appliance must be serviced at least annually by a qualified engineer.
Ensure that the fire is fully cold before attempting service. A suggested
procedure for servicing is detailed below.
1. Lay out the dust sheet and tools.
2. Inspect the area around the top of the fireplace opening for signs of
spillage.
3. Carefully remove the ceramic components. Use a soft brush to clean
off ceramics, the use of a vacuum cleaner directly on the ceramics is not
recommended. Replace any broken ceramics.
4. Carefully remove the Grate, clean the grate and the top of the burner, a
vacuum cleaner and brush may be used.
5. Isolate the gas supply at the appliance inlet, and disconnect the gas
supply pipe.
6. Remove the screws securing the burner to the hearth.
7. Remove the burner unit from the fireplace opening.
6. Check the base of the fireplace opening for rubble accumulation and
remove. If debris is excessive, initiate remedial work on the flue.
7. Check the flue with smoke pellet for correct operation.
8. Strip off the burner pipes and clean thoroughly.
9. Clean out the injector and pilot assembly. DO NOT attempt to dismantle
the pilot unit.
10. Ensure the injector is aligned squarely in the injector bracket. Re-
assemble and re-fit the burner tray.
11. Re fit and replace the ceramics, using genuine spares where necessary.
12. Turn on the gas supply, and leak test.
13. Check any purpose provided ventilation is un-obstructed.
14. Light the fire and test for spillage.
15. Check setting pressure and safe operation of the appliance.
Содержание Gyrofocus
Страница 1: ...GYROFOCUS GAS ____ ____ INSTALLATION SERVICING AND USER INSTRUCTIONS ...
Страница 14: ...14 Installer information 14 Instructions d installation 10 11 12 9 250 mm ...
Страница 15: ...15 Installer information 15 Instructions d installation 13 14 16 15 ...
Страница 17: ...17 Installer information 17 21 22 24 23 Instructions d installation ...
Страница 31: ...31 WIRING DIAGRAM Appendix ...
Страница 33: ...33 Note ...
Страница 34: ...34 Note ...
Страница 35: ...35 Note ...