Before installing the fire, check the flue using a smoke pellet. All of the smoke should travel up the flue and exit correctly from the ter-

minal. If problems are found, DO NOT fit the fire until corrective action is completed. Protect the decorative hearth whilst pushing the

firebox in and out of the opening. Part of the packaging will make an ideal hearth saver pad. Before running the gas supply into the open-

ing, offer up the firebox to the fireplace to check the fit is good. Angle the firebox or adjust the spigot outlet as described in part 8.0 of

these instructions. Ensure that it slides in correctly, the sealing face sits flat and square to the wall or infill panel, and that the base is firm

on the floor of the opening as no leaks are permissible here.  At this stage it is essential to ensure that the spigot outlet of the fire is

not  restricted  in  any  way.  Remove  the  firebox  and  take  any  necessary  measurements  before  making  good  and  preparing  for  final

installation.

CABLE FIXING :  For fixing of the fire by the cable method, see the relevant section. The cable fixing locations should be marked on

the back of the opening and the holes drilled. Fit the wall plugs and eyebolts to these holes.

SCREW FIXING :  For fixing by screw, mark and drill the fireframe or base, and the relevant points in the opening or on the wall. wall

plugs will again be required. Pre-punched holes are not provided for this purpose to allow you to choose the optimum positions.

GAS SUPPLY : Following preparation for the fixing method, the concealed gas supply, where required, can now be put into place. Refer

to the gas supply section for suggested pipe routes. The ends of the sleeving in which the gas pipe is run should be sealed. The ends of

the 8mm supply pipe should be temporarily sealed to prevent the ingress of debris during fixing.

PLEASE NOTE: Ensure fire can be removed for ease of servicing and not siliconed.

When the opening is ready for installation of the fire, the gas supply may be routed as per the examples shown in figure 9. 

IMPORTANT - Wherever a concealed connection is made a rubber grommet must be used to seal the firebox.

The gas pipe must be suitably protected where it passes through fireplace openings. Any sleeving should be sealed to the pipe at its ends.

This appliance is fitted with an inlet restrictor elbow. Using 8mm diameter pipe, connect the appliance to the gas supply point. The appli-

ance must be fitted with rigid or semi-rigid pipe of 8mm external diameter. The appliance is factory fitted with an inlet restrictor elbow.

Use a minimum length of 8mm pipe, less than 1.5m where possible, as a long run of pipe may cause an unacceptable drop in the supply

pressure.The open end of the supply pipe should be sealed temporarily during the installation of the firebox to prevent the ingress of

dirt and dust. Soldered joints are not recommended.

Radiant models only:
To fit the firebox, first check the firebox fits correctly into the opening. For openings
between 545mm and 565mm in height it will be necessary to insert the upper part
of the firebox first, followed by the lower as shown in figure 10. 

If is is still not possible to fit the firebox into the opening then remove the outlet
deflector  screws  using  a  screwdriver,  bend  the  outlet  deflector  down  and  partly
insert the firebox. Now push the outlet deflector back up to the original
position 
under the lip of the fireplace opening and secure with the screws.

The fire is designed to operate correctly with the spigot raised and screwed in its
original position and spillage problems may arise by not realigning correctly once fit-
ted.Secure the firebox by drilling and screwing down the frame or base of the fire-
box, or use the cable fixing method.

9.0 PREPARING THE OPENING

GB IE

7

© 2013 Focal Point Fires plc.

10.0 GAS SUPPLY ROUTING

11.0 FITTING THE FIREBOX

Figure 10

Radiant models

Not to scale

Figure 9

Manual control

Slide control

Remote control

Fireplace opening

Grommets

Firebox

Inlet

restrictor

elbow

Содержание ALVOR FULL DEPTH RADIANT

Страница 1: ...ekeeping Please note Except where otherwise stated all rights including copyright in the text images and layout of this booklet is owned by Focal Point Fires plc You are not permitted to copy or adapt...

Страница 2: ...and under normal usage will need a new battery approximately every twelve months Burner spark generator requirements 1 x AA 1 5 volt Refer to the appropriate section of these instructions for details...

Страница 3: ...rom dam aging wall surfaces Pre cast flues must be checked for mortar fangs and correct installation of joints flue sections in loft space and ter minals These appliances have been tested for use with...

Страница 4: ...may be fixed to the wall above the fire providing that it complies with the dimensions given below A non combustible shelf may be fitted to within 10mm of the top edge of the fireframe Combustible ma...

Страница 5: ...ox does not obscure the flue box outlet The firebox base of the flue box and hearth below may be drilled to allow plugs and screws to secure installation It is important that the sealing requirements...

Страница 6: ...provided figure 4 The screws should locate into the pre punched holes in the sides of the firebox SUPPLY PIPE ENTRY All models Knockout holes are provided in the rear and sides of the firebox for use...

Страница 7: ...siliconed When the opening is ready for installation of the fire the gas supply may be routed as per the examples shown in figure 9 IMPORTANT Wherever a concealed connection is made a rubber grommet...

Страница 8: ...suitable gas route can be achieved Purge the gas supply thoroughly to remove air and dirt debris before connection Disconnect the inlet restrictor elbow from the inlet pipe Connect the previously inst...

Страница 9: ...mediate position To turn the fire OFF move the slide control knob upwards fully to the position marked O The pilot is visible through the left hand side of the ceramic fuel bed When cold the coals or...

Страница 10: ...the HIGH setting To commission the appliance the burner pressure must be in accordance with the figures stated in section 2 0 of these instructions The fire is factory set to achieve these pressures a...

Страница 11: ...ded during this time Advise that the fire is fitted with a spillage safety device O D S If the fire shuts down this system may be in operation If spillage is suspected SWITCH APPLIANCE OFF and call in...

Страница 12: ...t must be used If a large amount of debris is present in the filter then the pipework and con trol should be thoroughly cleaned before re assembly Remove the burner unit as in relevant section and pil...

Страница 13: ...e an air vent Fire is sited on disused chimney breast which has not been adequately sealed up Dirt or lint in pilot aeration hole or on the lint gauze clean thoroughly If the pilot will not stay lit t...

Страница 14: ...e appliance is installed the chimney should be swept All flues should be checked by the installer to ensure there are no defects or obstructions that may prevent the flow of combustion products This a...

Страница 15: ...control knob in fully and turn anti clockwise through both of the SPARK positions keeping fully depressed hold there for a few seconds If the fire has not been used for some time hold the knob in this...

Страница 16: ...lot is extinguished during use of the fire you MUST wait ten minutes before repeating the ignition procedure To turn the main burner OFF whilst keeping the pilot flame lit turn the ignition control kn...

Страница 17: ...igure 11 Care should be taken to ensure that the coals bridge the gap between the front coal and the four coal supports at the front of the matrix Care should also be taken not to push the coals right...

Страница 18: ...oals or change them for a different type Never throw rubbish or other matter onto the coal bed 1 Refer back to section 6 0 Fuel bed layout coal effect and follow steps 1 and 2 The front strip and fuel...

Страница 19: ...ld be checked on an annual basis to ensure all of the products of combustion are entering the flue and that there is no excessive build up of soot The frequency of service will depend on usage but MUS...

Страница 20: ...em Part number Pack of 16 coals F550038 Pack of 16 pebbles F550050 Pack of 9 ceramic logs F550084 Front ceramic strip coal F780008 Front ceramic strip pebble F780017 Front ceramic strip Log F780050 Ce...

Страница 21: ...GI Gas Safe registered installer evidence of which must be provided such as the receipt Please note all consumable items such as any ceramics including coals pebbles the matrix front strips side cheek...

Отзывы: