Focal Point ALVOR FULL DEPTH RADIANT Скачать руководство пользователя страница 5

No purpose provided ventilation is normally required for this appliance. The requirements of other appliances operating in the

same room or space must be taken into consideration when assessing ventilation. If spillage is detected when commissioning the appli-

ance, then amongst other problems there may be insufficient natural ventilation for correct operation of the flue. If the appliance does

not spill with the windows open, but spillage is detected with the windows closed, this demonstrates a lack of natural ventilation. If

spillage is still detected with the windows open, the flue is at fault. Installation of an air brick is the best solution to lack of ventilation.

Any ventilation fitted must comply with BS 5871 part 2 and BS 5440 part 2. Vents fitted under or within the immediate vicinity of the

appliance must not be used as adverse effects to the operation of the ODS may occur. Spillage detected during commissioning is almost

always a result of poor flue performance that cannot be corrected by any amount of ventilation. For Republic of Ireland ventilation may

be required, see IS 813, ICP3, IS 327, and any other rules in force.

This appliance can be fitted into a number of proprietary flue boxes

provided that the minimum dimensions shown in figure 2 are com-

plied with.

Constructional Note: The frame of the fire, any back panel or

other infill panels, and the flue box must be sealed together so that

there is no possibility of leakage between them. Adequate clear-

ances to combustible materials (e.g. false chimney breast construc-

tion) must be maintained.

The  manufacturers’  instructions  for  fitting  the  prefabri-

cated box shall be complied with at all times. To fit the fire

using the cable fixing kit, some minor adaption may be necessary

for certain flue boxes. A check should be made to ensure the fire-

box does not obscure the flue box outlet. The firebox, base of the

flue box, and hearth below may be drilled to allow plugs and screws

to secure installation. It is important that the sealing requirements

of the appliance are met at all times and that the flue box is well

sealed to any back or infill panel. Note: The DEPTH dimension is

inclusive of any back or infill panel.

Stand the carton the right way up, cut the strapping bands and remove the top endcap. Read all the instructions before continuing to unpack

or install this appliance.

Remove the box containing the firefront, and the bags containing the ceramic components. Remove the cardboard packing pieces, and any other

bags or boxes containing fittings or other parts. When all loose parts have been removed, the outer sleeve may be lifted off to reveal the appli-

ance. Check that the components supplied correlate with the component checklist given in section 7.1. Please dispose of all the packaging mate-

rials at your local recycling centre.

5.0 VENTILATION

GB IE

6.0 PREFABRICATED FLUE BOXES

7.0 UNPACKING THE APPLIANCE

7.1 COMPONENT CHECKLIST

QUANTITY

DESCRIPTION

1

Firebox and burner tray assembly

1

Decorative frame

1

Firefront (fret)

1

Moulded ceramic fibre combustion matrix

1

Moulded ceramic front strip

16

Individual ceramic coals (Coal models only)

16

Individual ceramic pebbles (Pebble models only)

9

Individual ceramic logs (Log models only)

1

Slide control knob and M4 Nyloc nut (Slide control models only)

1

Cable fixing kit; 2 cables, 2 tensioners, 2 cable clamps, 4 eyebolts, 4 wall plugs

1

Sealing grommet

3

Lengths of adhesive sealing strip

1

Self tapping screw pack; 4 No8 x 5/16

1

Remote control Handset (Remote control models only)

1

Set of manufacturers instructions

5

© 2013 Focal Point Fires plc.

125mm min internal dia twin wall flue

Radiant models :

250mm min depth

Convector models :

265mm min depth

Radiant models : 375mm min opening width

Convector models : 390mm min opening width

Radiant

models :

570mm min

height

Convector

models :

545mm min

height

Figure 2

Содержание ALVOR FULL DEPTH RADIANT

Страница 1: ...ekeeping Please note Except where otherwise stated all rights including copyright in the text images and layout of this booklet is owned by Focal Point Fires plc You are not permitted to copy or adapt...

Страница 2: ...and under normal usage will need a new battery approximately every twelve months Burner spark generator requirements 1 x AA 1 5 volt Refer to the appropriate section of these instructions for details...

Страница 3: ...rom dam aging wall surfaces Pre cast flues must be checked for mortar fangs and correct installation of joints flue sections in loft space and ter minals These appliances have been tested for use with...

Страница 4: ...may be fixed to the wall above the fire providing that it complies with the dimensions given below A non combustible shelf may be fitted to within 10mm of the top edge of the fireframe Combustible ma...

Страница 5: ...ox does not obscure the flue box outlet The firebox base of the flue box and hearth below may be drilled to allow plugs and screws to secure installation It is important that the sealing requirements...

Страница 6: ...provided figure 4 The screws should locate into the pre punched holes in the sides of the firebox SUPPLY PIPE ENTRY All models Knockout holes are provided in the rear and sides of the firebox for use...

Страница 7: ...siliconed When the opening is ready for installation of the fire the gas supply may be routed as per the examples shown in figure 9 IMPORTANT Wherever a concealed connection is made a rubber grommet...

Страница 8: ...suitable gas route can be achieved Purge the gas supply thoroughly to remove air and dirt debris before connection Disconnect the inlet restrictor elbow from the inlet pipe Connect the previously inst...

Страница 9: ...mediate position To turn the fire OFF move the slide control knob upwards fully to the position marked O The pilot is visible through the left hand side of the ceramic fuel bed When cold the coals or...

Страница 10: ...the HIGH setting To commission the appliance the burner pressure must be in accordance with the figures stated in section 2 0 of these instructions The fire is factory set to achieve these pressures a...

Страница 11: ...ded during this time Advise that the fire is fitted with a spillage safety device O D S If the fire shuts down this system may be in operation If spillage is suspected SWITCH APPLIANCE OFF and call in...

Страница 12: ...t must be used If a large amount of debris is present in the filter then the pipework and con trol should be thoroughly cleaned before re assembly Remove the burner unit as in relevant section and pil...

Страница 13: ...e an air vent Fire is sited on disused chimney breast which has not been adequately sealed up Dirt or lint in pilot aeration hole or on the lint gauze clean thoroughly If the pilot will not stay lit t...

Страница 14: ...e appliance is installed the chimney should be swept All flues should be checked by the installer to ensure there are no defects or obstructions that may prevent the flow of combustion products This a...

Страница 15: ...control knob in fully and turn anti clockwise through both of the SPARK positions keeping fully depressed hold there for a few seconds If the fire has not been used for some time hold the knob in this...

Страница 16: ...lot is extinguished during use of the fire you MUST wait ten minutes before repeating the ignition procedure To turn the main burner OFF whilst keeping the pilot flame lit turn the ignition control kn...

Страница 17: ...igure 11 Care should be taken to ensure that the coals bridge the gap between the front coal and the four coal supports at the front of the matrix Care should also be taken not to push the coals right...

Страница 18: ...oals or change them for a different type Never throw rubbish or other matter onto the coal bed 1 Refer back to section 6 0 Fuel bed layout coal effect and follow steps 1 and 2 The front strip and fuel...

Страница 19: ...ld be checked on an annual basis to ensure all of the products of combustion are entering the flue and that there is no excessive build up of soot The frequency of service will depend on usage but MUS...

Страница 20: ...em Part number Pack of 16 coals F550038 Pack of 16 pebbles F550050 Pack of 9 ceramic logs F550084 Front ceramic strip coal F780008 Front ceramic strip pebble F780017 Front ceramic strip Log F780050 Ce...

Страница 21: ...GI Gas Safe registered installer evidence of which must be provided such as the receipt Please note all consumable items such as any ceramics including coals pebbles the matrix front strips side cheek...

Отзывы: