Operating Manual EMGZ622A/642A
24
Lowpass output
Use:
Each channel provides a low-pass filter to prevent noise which is added to
the output signal. This parameter stores the cut off frequency. The lower
the cut off frequency, the more sluggish the output signal on the terminals
will be (ref. to wiring diagram). Due to this filter, the output signal will be
much more stable in the case of high fluctuations of the force value.
The low-pass filter of each channel is independent to the other filters.
Range:
0.1
to
200.0
Default:
10.0
Increment:
0.1
Unit:
[Hz]
Scale output
Use:
This parameter stores which tension feedback value will give the maximum
signal (10V resp. 20mA) at the output.
Range:
A force value can be input. The value consists of 5 digits. The position of
the decimal point depends on the parameter
Force of sensor.
Default:
1000
Unit:
[N, kN, cN]
or
[lb, klb, clb]
Configuration output
Use:
This parameter configures the analogue output signal.
Range:
0–10V and 0...20mA,
Default:
0–10V
and
0–10V and 4...20mA, –10V...+10V
0...20mA