Operating Instructions EMGZ492.PNET
05.10.2018
19
Analog output scaling
This parameter determines, for which force the analog
output outputs its maximum voltage (10 V).
Note:
If lb (pound) is selected, the system switches from metric
to imperial measuring units.
Unit
N
Min.
0.1
Max.
200‘000.00
Specified value
1‘000.00
7.2
Cyclic Data Traffic
After a successful system start, IO controller and the assigned IO devices can exchange
cyclic process data. The table below shows the measured data and how they are
transmitted.
Parameter
Name
Description
Actual value A in ADC
Value read in via the A/D converter.
Data type
int (signed 16 bit)
Value range
-16384 bis 16383
Value format
±#####
The value is interpreted as integer without decimal place.
E.g. 1000 = 1000 ADC raw value
Actual value A in
Newton
Filtered actual value converted into Newton
Data type
long (signed 32 bit)
Value range
±200‘000‘000
Value format
±######.###
The value is interpreted as decimal number with 3
decimal places. E.g. 1500 = 1.500N (1.5N)
Unit
N
Actual value A in
pound
Filtered actual value converted into pound.
Data type
long (signed 32 bit)
Value range
±200‘000‘000
Value format
±######.###
The value is interpreted as decimal number with 3
decimal places. E.g. 224820 = 224.820lb (224.82lb)
Unit
lb