Operating Instructions EMGZ492.PNET
05.10.2018
17
Nominal force A
The nominal force indicates the measuring capacity of
force sensor A. E.g., if a 500 N load cells is installed 500
N must be entered.
Unit
N
Min.
1.00
Max.
200‘000.00
Specified value
1‘000.00
Limit frequency low-
pass filter actual value
A
The amplifier features a low-pass filter that filters the
measured value is relayed via PROFINET. This filter is
used for suppressing undesired interference signals that
are superimposed on the measuring signal. Using this
parameter, the limit frequency of the filter of force sensor
A is adjusted. The lower the limit frequency, the slower
the measuring value.
This low-pass filter is independent from the output filter.
Unit
Hz
Min.
0.1
Max.
200.0
Specified value
10.0
Low-pass filter active B
Here, the status of the low-pass filter active value for the
force sensor B is indicated.
This parameter cannot be accessed via the web interface.
Min.
0
Max.
1
Specified value
1
0 = no, inactive, 1 = yes, active
Offset B
The values determined with the “Offset Compensation”
procedure are stored in the form of a digital value in the
[Offset] parameter. The value is used for compensating
for the roller weight of force sensor B.
Min.
-16’000
Max.
16’000
Specified value
0
Gain B
The gain factor ensures that the displayed force matches
the effective force on sensor B.
Min.
0.100
Max.
20.000
Specified value
1.000