background image

Operating Manual EMGZ309._.EIP 

 

 

21 

 
The dialog window (Fig. 
14)  will  open  up.  Here, 
one can enter the cycle 
time.  This  determines 
how  often  the  data  will 
be  propagated  in  the 
network.  The  minimal 
cycle  time  is  2  ms. 
Default  setting  is  10 
ms.  Basically  the  cycle 
time  must  be  set  so 
that 

the 

maximum 

speed  requirements  of 
the system are fulfilled. 
A  fast  cycle  time  leads  to  more  data  traffic  in  the  network.  That  can  create 
communication  bottlenecks.  Especially  when  using  several  EMGZ309  amplifiers 
and other EIP devices in the same network a well balanced data speed is important.  
 

6.4

 

Access to the Tension Values 

After  the  integration  of 
the  amplifier  in  the 
network the tension data 
are  available  in  the 
global  input  tags  of  the 
controller and that in the 
defined cycle time. In our 
example  the  amplifier 
was  named 

EMGZ309

The  tension  values  can 
therefore be found under 
the 

controller 

tags 

EMGZ309:I

 

>> 

EMGZ309:I Data

 Index 0 

to  3.  Where  the  values 
are assigned to the indices as follows: 

 

Index   

Value 

 

Tension value in digits 

 

Tension value in Newton with 3 decimals 

 

Tension value in Pounds [lbs] with 3 decimals 

 

Tension value in the configured unit with 3 decimals 

 
The value with Index 4 contains the device state. The access to the data in its value 
is marked red in Fig. 15. 

 

Fig. 14: Module Properties 

E309025 

 

Fig. 15: RSLogix 

E309026 

Содержание EMGZ309.EIP Series

Страница 1: ...e Version V2 11 from S N 1125523 Diese Bedienungsanleitung ist auch in Deutsch erh ltlich Bitte kontaktieren Sie Ihre n chstgelegene FMS Vertretung This operation manual is also available in German Pl...

Страница 2: ...e Device Mode 11 4 5 Offset Compensation 11 4 6 Offset Compensation over the Operating Panel 12 4 7 Calibration 12 4 8 Calibration over the Operating Panel 13 4 9 Analytic Calibration Method 14 5 Netw...

Страница 3: ...er List 27 8 3 Description of Parameters 28 9 Parameter Setting via a PC 33 9 1 Parameterization in an Ethernet Network via Web Browser 34 9 2 Offsetkompensation ber einen Webbrowser 38 9 3 Calibratio...

Страница 4: ...is only guaranteed with the recommended application of the components In case of other arrangement heavy malfunction can be the result Therefore the installation instructions on the following pages mu...

Страница 5: ...0 2 2 Block Diagram Fig 1 Block diagram EMGZ309 Tension Measuring Amplifier E309011e 2 3 System Description EMGZ309 The digital tension measuring amplifiers EMGZ309 are suitable for tension measuremen...

Страница 6: ...echnology as well as on the CIP Common Industrial Protocol The amplifier can be embedded in a standard Ethernet infrastructure Its fast data rate with cycle times down to 2ms makes the device ideal fo...

Страница 7: ...e in the range 18 to 36V DC 4 Perform offset compensation and calibration ref to chapter 4 5 to 4 9 5 If required do additional settings ref to 8 Parameterization over Operating Panel 6 Integration of...

Страница 8: ...ne or two force sensors can be connected to the measuring amplifier When using two force sensors the sensors are internally connected in parallel The output signal of the measuring amplifier will then...

Страница 9: ...sons malfunction of the total system or damage of the electronic unit It is vital to ensure that proper earth connection is done The cable must be installed separate from power lines Note The shield s...

Страница 10: ...erminals 12 13 3 If applicable connect the second force sensor 4 Check whether applying a force in measuring direction on the second sensor results in a positive output signal If not exchange the two...

Страница 11: ...l be stored in the system automatically 4 4 Change the Device Mode The EMGZ309 amplifiers have two Device Modes Display of Force Gauge Tension data are displayed in a force unit Display of Voltage Gau...

Страница 12: ...alue There are two methods of calibrating the system The first method uses a defined weight see Fig 7 This method is the preferred one since it delivers the most accurate results The second method is...

Страница 13: ...flashes indicating that the force can now be changed Use keys to enter the system force 4 Press the key to confirm your input Display will change to 5 Enter the force corresponding to your calibration...

Страница 14: ...of the FMS calculator It delivers the gain factor for easy weightless calibration of FMS amplifiers 1 First the application related parameters must be entered in the FMS calculator e g min max force...

Страница 15: ...tered the parametrisation mode 3 Scroll up or down the parameter menu with the keys until the display show Gain 4 Confirm the parameter with the key 5 The display will start flashing indicating that t...

Страница 16: ...nsion values are cyclically propagated over the network and made available to the Consumer PLC 5 3 Integration of EMGZ309 _ EIP in an Ethernet Network In order to integrate the amplifier in an Etherne...

Страница 17: ...erNet IP is preferred there are two different ways of doing it 1 Initialisation of all parameters at connection establishment with controller 2 Configuration of individual parameters as needed The Bit...

Страница 18: ...GZ309 _ EIP amplifiers or other ErtherNet IP devices can be connected to the same network 6 2 IP Configuration In an industrial environment the IP addresses are normally assigned fix to the EIP device...

Страница 19: ...hardware is used one may find the listing Ethernet in another place However the principal approach is always the same After a right mouse click on Ethernet a dialog window will open up Left mouse clic...

Страница 20: ...K Following window opens up in which the Name EMGZ309_91 the Comm Format DINT and the IP Address eg 192 168 0 91 need to be entered On the Connection Parameters side the values Input 100 with Size 5 O...

Страница 21: ...mportant 6 4 Access to the Tension Values After the integration of the amplifier in the network the tension data are available in the global input tags of the controller and that in the defined cycle...

Страница 22: ...e to offset the roller weight Calibration State Procedure to calculate the amplifier gain Parameterisation State Set or change parameters When using the front panel the user can toggle between these m...

Страница 23: ...s on the display depending on the chosen unit A If a tension has been chosen the reading on the display at overload will be B If the display was set to show the amplifier output following messages wil...

Страница 24: ...e system is configured It can now be put into operation The following state diagrams Fig 17 to 19 help to navigate through the parameter setting menu In the Parameterisation State the EMGZ309 can be b...

Страница 25: ...splay shows the unit of measure that was previously selected 3 Permanent key pressing expedites the changing speed 4 If the Device Mode VoltGauge is set these parameters are deactivated Fig 18 State D...

Страница 26: ...Setting 3rd part E309027e 8 1 Reset to Default Parameter Set Factory settings of your EMGZ309 amplifier can be re established either over the parameter setting menu see 8 3 Description of Parameters...

Страница 27: ...000 DevicMod ForcGaug or VoltGaug ForcGaug Each parameter change requires re calibration Language English or German English Contrast 1 100 65 Ethernet On or Off On If Off reduces power consumpt IP Add...

Страница 28: ...Out Filt Use The EMGZ309 contains a lowpass filter to prevent noise overlaying to the output signal This parameter stores the cut off frequency of the filter The lower the cut off frequency the more...

Страница 29: ...Selection Default Min Max N kN g kg lb 1 1 100 000 1000 1 The display shows the unit of measure that was previously selected Force at max Amplifier Output LCD F OutMax Use This parameter defines what...

Страница 30: ...edure Calibration see 4 7 Calibration over the Operating Panel Alternatively you can input a calculated value using the FMS Calculator described in chapter 4 8 if the material tension cannot be simula...

Страница 31: ...se The Ethernet interface of EMGZ309 can be switched on and off with this parameter The deactivation of this interface reduces the power consumption by 25 and lowers heat generation in the device cons...

Страница 32: ...n Default Min Max 000 000 000 000 255 255 255 255 255 255 255 000 LAN Speed LCD LANSpeed Use LANSpeed determines the data speed of the tension EMGZ309 amplifier to communicate with the receiver Switch...

Страница 33: ...e set over the user interface The IP address is not automatically assigned over DHCP The parameter setting can be carried out with a desktop or laptop computer via a peer to peer connection see chapte...

Страница 34: ...gration of an EMGZ309 amplifier in your EtherNet network please contact your IT system administrator Once the amplifier was integrated in the network you can address the device e g with http 192 168 0...

Страница 35: ...Operating Manual EMGZ309 _ EIP 35 Fig 25 Current Reading for Device Mode Force Gauge Current Reading Force Fig 26 Current Reading for Device Mode Volt Gauge Current Reading Volt...

Страница 36: ...Operating Manual EMGZ309 _ EIP 36 Fig 27 Parameter list for Device Mode Force Gauge Parameters Force Fig 28 Parameter list for Device Mode Volt Gauge Parameters Volt...

Страница 37: ...nual EMGZ309 _ EIP 37 Fig 29 Offset compensation and calibration for Device Mode Force Gauge Offset Calibration Force Fig 30 Offset compensation and calibration for Device Mode Volt Gauge Offset Calib...

Страница 38: ...your measuring roller enter 1000N see chapter 8 3 Descriptions of Parameter SysForce 3 Enter the SysForce in the corresponding box by overwriting the default or previous value 4 Enter the force corre...

Страница 39: ...Operating Manual EMGZ309 _ EIP 39 Fig 31 Ethernet Settings Ethernet Settings Fig 32 System Settings System...

Страница 40: ...s not necessary In such a case apply the procedure described in paragraph 9 1 Parametrization in an Ethernet Network via a Web Browser To establish the connection between your PC and the EMGZ309 follo...

Страница 41: ...General tab is selected Select the radio button Use the following IP address In the IP address box enter the IP address for the computer that could be 192 168 0 1 In the Subnet mask enter 255 255 255...

Страница 42: ...Operating Manual EMGZ309 _ EIP 42 The dialog box will change to look like the following Click the OK button The following dialog box will appear again...

Страница 43: ...desktop or laptop computer 2 Open Microsoft Internet Explorer or Mizilla Firefox 3 The default IP address for the EMGZ309 is 192 168 000 091 as long as it was not changed over the operating penal Ente...

Страница 44: ...Dimensions The EMGZ309 series is available in three different housing options The mechanical dimensions can be seen in the following pages Fig 33 Outline Drawing EMGZ309 R rail mount housing E309006e...

Страница 45: ...Operating Manual EMGZ309 _ EIP 45 Fig 34 Outline Drawing EMGZ309 W wall mount housing E309004 Ethernet connection M12 4 pole D coded...

Страница 46: ...Operating Manual EMGZ309 _ EIP 46 Fig 35 Outline Drawing EMGZ309 S panel mount housing RJ 45 E309005e...

Страница 47: ...Parameter Setting 3 keys and LCD 2x8 characters size 8mm Interface optional EtherNet IP Bus Standard CIP ber IEE 802 3 Tension output 0 10V min 1 2k Current output 0 4 20mA max 500 Power supply 24VDC...

Страница 48: ...m FMS Italy Via Baranzate 67 I 20026 Novate Milanese Tel 39 02 39487035 Fax 39 02 39487035 fmsit fms technology com FMS USA Inc 2155 Stonington Ave Suite 119 Hoffman Estates IL 60169 USA Tel 1 847 519...

Отзывы: