Operating Manual EMGZ309._.EIP
15
Fig. 9: Gain calculation tool
E309_gain_e.jpg
Calibration Procedure:
1.
Calculate the gain factor with the FMS-calculator as described.
2.
Press the PARA key for longer then 3 seconds to entered the parametrisation
mode.
3.
Scroll up or down the parameter menu with the
keys until the display
show [Gain].
4.
Confirm the parameter with the
key
5.
The display will start flashing indicating that the gain factor can now be entered.
6.
Use the
keys to enter the calculated value.
7.
Press the
key to confirm the input. Or if no action is taken after 30 seconds,
the value will be stored in the system automatically.