Operating Manual CMGZ434
30
Nominal force of sensor
Use:
To get the correct force value,, the electronic unit has to know the
nominal force of the sensors.
Range:
1
to
9999
Default:
1000
Increment:
1
Unit:
[N,kN]
Unit of force
Use:
This parameter stores the force unit of the sensor.
Range:
N,
kN
Default:
N
Sensitivity of sensor
Use:
To get the correct force value,, the electronic unit has to know the
sensitivity of the force sensors, that means how much signal the sensor
will answer by nominal force. Standard for FMS force sensors is
1.8mV/V.
Range:
0.1
to
3.0
Default:
1.8
Increment:
0.1
Unit:
[mV/V]
1 or 2 sensors
Use:
To get the correct force value, the electronic unit has to know if the
measuring roller is beared by one or two force sensors.
Range:
1
to
2
Default:
1
Increment:
1
Unit:
[-]
Lowpass output
Use:
The electronic unit provides a lowpass filter to prevent noise which is
added to the feedback signal, caused by unbalanced rollers or
interference. This parameter stores the limit frequency. The filtered
feedback value will be fed to the PI controller.
The lowpass output filter is independent of the other filters.
Notice:
The lower the cut-off frequency, the more sluggish the output
signal will be. If the limit frequency is set too low, the control
dynamics may be reduced dramatically!
Range:
0.1
to
200.0
Default:
50.0
Increment:
0.1
Unit:
[Hz]