Operating Manual CMGZ434
15
9.2
Schematic diagram of main operating menu
fig. 11
C434008e
9.3
Checking the parameters
Before the initial setup is done, the following parameters have to be set resp. you have to
check if they correspond with the effective machine conditions (ref. to „11.
Parametrization“):
Measuring amplifier parameters
•
Nominal force
•
Unit of force
•
Sensitivity
•
1 or 2 sensors
PID controller parameters
•
Lowpass output
(reset to default)
•
Line speed overlay
(for the time being set to
None
)
•
PID-configuration
(for the time being set to
PI
; if PID configuration is required, refer
to „9.10 Additional Settings“)
•
Output limit
(set according to the drive used)
•
Output configuration
(set according to the drive used)
•
Position line drive
(depending on machine configuration)
•
Ramp reference
(reset to default)
•
Reference
(depending on machine configuration)
•
Scale ref. input
(if reference potentiometer is used)