Operating Manual BMGZ710 and BMGZ710.PNET
20.04.2021
14
6
Configuration
6.1
Plant parameters
The plant parameters directly affect the weighing results.
Plant parameters
Parameter Unit
Selection
Default
Min.
Max.
No.
Offset [Digit]
0
-32768 32767 1
Gain [-]
1 0.1 10
2
Belt length
[m]
10
1
5000
3
Diameter [mm]
108
10
1000
4
Pulse [-]
4 1 100
5
Distance [mm]
2000
100
5000
6
Nominal force
[N]
1000
1
5000
7
Table 1: Plant parameters
6.1.1
Description of plant parameters
Parameter
Name
Description
Offset
The evaluation unit saves the value determined during taring /
zero setting in [Digit].
If the electronics unit is replaced, the values determined by the
previous unit can also be entered manually here.
Unit Digit
Min. -32768
Max. 32768
Default 0
Increment 1
Gain
The value determined during calibration is saved under this
parameter. If the automatic calibration cannot be used, a
manually determined value can also be entered here.
Unit -
Min. 0.100
Max. 10.000
Default 1.000
Increment 0.001