  To achieve desired offset, you may install combinations of 
12,18,36, or 48 inch lengths of double wall pipe (see 

figure 

20 

and 

Rise and Offset Chart

). 

 

 

RISE AND OFFSET CHART

 

 

B 48 

36 

18 

12 

4 3/8 

16 3/8 

 

 

 

 

9 1/2 

25 1/4 

 

 

 

12 1/2 

30 3/8 

 

 

 

14 3/8 

34 

 

 

 

17 5/8 

39 1/4 

 

 

21 1/2 

46 

 

 

 

22 3/4 

48 1/8 

 

 

26 3/8 

54 7/8 

 

 

 

26 3/8 

60 

 

 

31 3/4 

63 3/4 

 

 

34 3/4 

69 

 

 

38 5/8 

75 5/8 

 

 

 

39 7/8 

77 7/8 

 

43 3/4 

84 1/2 

 

 

46 3/4 

87 3/4 

 

 

48 7/8 

93 3/8 

 

 

 

 
Maximum length of pipe between supports is 

6 feet of angled 

run.

 A maximum of 

two 6 foot angled run sections per 

chimney system

 (see figure 

21

). 

 
 
 
 
 
 
 

 

 
 

 
FINISHING YOUR CHIMNEY SYSTEM

 

 

IMPORTANT:

 If an exposed portion of chimney is 

greater than 4 feet above the roof line, 

use support wires to 

keep chimney secure.

 The support wires may be attached to 

the outer pipe of the chimney with screws, provided the 
screws do not penetrate the inner flue pipe. 
 

WARNING:

  DO NOT OPERATE AN UNVENTED GAS 

LOG SET IN THIS FIREPLACE WITH THE CHIMNEY 
REMOVED.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 21

 

 
 
All Joints between 
offset should be secured 
with two screws, only on 
the outer pipe, and shall  
not penetrate the inner 
stainless. 
 
 
 
 
 
 
 
 
 
 

Figure 20 

 
 
 
 
 
 
 
 
 
 

Figure 22

 

10 FOOT RULE 

   All  chimney  termination  must  extend  a 

minimum of 3

feet above the highest point where it passes through the
roof

 and must be at least 

2 feet above the roof within a

10 foot horizontal span

 (see 

figure 22

). 

Содержание The Monterey PN36

Страница 1: ...rom furniture and draperies Do not place clothing or other flammable materials on or near the appliance NEVER leave children unattended when a fire is burning in the fireplace WARNING IMPROPER INSTALL...

Страница 2: ...INSTALLATION PG 5 8 CHIMNEY PIPE INSTALLATION PG 6 9 FINISHING YOUR CHIMNEY SYSTEM PG 8 10 TERMINATIONS PG 10 11 FINISHING YOUR FIREPLACE PG 11 12 OPERATING GUIDELINES AND MAINTENANCE INSTRUCTIONS PG...

Страница 3: ...ough grounding may not be required by code in your area it must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70...

Страница 4: ...TLE CLEARANCES Woodwork such as wood trims mantles and other combustible materials should not be placed within 9 inches of the effective opening of this fireplace The effective opening is considered t...

Страница 5: ...mbustible floor surrounding fireplace You may obtain kit No HE P36 or you may fabricate your own per the dimensions shown on figure 10 The hearth extension must project 20 in min to the front and 12 i...

Страница 6: ...stacles It should also be located beyond the reach of small children The maximum height for the air inlet above platform of fireplace is within 3 feet below the termination flue gas outlet For further...

Страница 7: ...TO COMPLY WITH THE STANDARD FOR UNVENTED ROOM HEATERS ANZI IAS AGA Z21 11 2 ARE TO BE INSTALLED IN THIS FIREPLACE NOTE An appropriate FMI hood as shown in page 13 must be installed when using an unven...

Страница 8: ...penetrating a floor or ceiling at an angle use firestop spacer no 30 FS 10DM refer to section on accessory items at the end of this manual When the pipe passes through a framed opening into a living...

Страница 9: ...ee figure 21 FINISHING YOUR CHIMNEY SYSTEM IMPORTANT If an exposed portion of chimney is greater than 4 feet above the roof line use support wires to keep chimney secure The support wires may be attac...

Страница 10: ...HIMNEY MAINTENANCE Have your chimney system cleaned and inspected regularly to ensure safe and efficient operation Refer to your Owners Manual for further guidelines on maintenance and operation Using...

Страница 11: ...structions supplied with the termination The terminations approved for this fireplace are RTL 10D which can be used for flashing or chase and ETL 10D for chase style termination only Figure 27 shows a...

Страница 12: ...refer to section on clearances and the fireplace opening are not blocked or obstructed in any way see fig 30 Use only heat resistant non combustible mortar or adhesive when securing facing material t...

Страница 13: ...n starting a fire this pro vides adequate outside combustion air Close the mechanism when not in use to prevent cold air from entering the room Periodically check your outside air intake vent hood for...

Страница 14: ...on the rating plate located inside the fireplace see figure 1 Refer to the parts list and diagrams when ordering replacement parts for your fireplace Repair parts or accessory items may be bought from...

Отзывы: