background image

12 

 

 
 

OPERATING GUIDELINES AND 

MAINTENANCE INSTRUCTIONS 

 

GLASS DOORS 

 

  Only the cabinet type doors can be opened, the front glass 
panel assembly is stationary and must be installed with doors. 
  When fireplace is in operation, both sets of cabinet doors on 
each side of fireplace, must be in the 

FULLY OPEN

 or 

FULLY CLOSED

 position only or a fire hazard may be 

created (see 

figure 32

). 

 

 

DAMPER MECHANISM

 

  The damper control lever is located inside the fire chamber 
(see 

figure 33

). Make sure lever is cool before handling. 

Pull 

down to CLOSE, push up to OPEN.

 The damper must be 

open when lighting a fire; not doing so will cause smoke spill-
age into the room. 
  When the fireplace is not in use, close the damper to prevent 
downdrafts to enter room. 

 
The damper mechanism should be per the following fig-
ure. 
 

OUTSIDE AIR MECHANISM

 

 
  The outside air handle is located at the right hand side of the 
fireplace rear refractor (fig. 

33

). Pull to close, push to open, 

Always open the mechanism when starting a fire, this pro-
vides adequate outside combustion air.  Close the mechanism 
when not in use to prevent cold air from entering the room. 
  Periodically check your outside air intake vent hood for any 
possible obstructions (snow, bushes, etc.). 
 
 
 
 
 
 

 
 

 
 

 
 
GRATE

 

 
  The grate is designed to provide you with the maximum solid 
fuel capacity, do not attempt to defeat its purpose, doing so 
may cause smoke spillage and may cause a fire hazard. 
  Do not overload the grate or obstruct the required air space 
beneath it. Always keep ashes from building up under the 
grate. 

 
WARNING: RISK OF FIRE! REPLACE GRATE WITH 
FMI MODEL 36PN GR GRATE ONLY. 
 
Never obstruct the flow of combustion and ventilation air. 
Keep the front of the fireplace clear of all obstacles and 
materials. 
 

WARNING: 

  CHILDREN AND ADULTS SHOULD BE ALERTED 
TO THE HAZARDS OF HIGH SURFACE TEMPERA-
TURES AND TO STAY AWAY FROM THESE TO 
AVOID BURNS OR CLOTHING IGNITION. 
  YOUNG CHILDREN SHOULD BE CAREFULLY SU-
PERVISED WHEN THEY ARE IN THE SAME ROOM 
AS THE FIREPLACE. 

 
  FOR  FURTHER  OPERATING  GUIDELINES,  INSTRUC-
TIONS AND WARRANTY INFORMATION PLEASE RE-
FER TO YOUR OWNERS’ MANUAL OR CONTACT 
YOUR AUTHORIZED DEALER.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 33

 

 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 32

 

Содержание The Monterey PN36

Страница 1: ...rom furniture and draperies Do not place clothing or other flammable materials on or near the appliance NEVER leave children unattended when a fire is burning in the fireplace WARNING IMPROPER INSTALL...

Страница 2: ...INSTALLATION PG 5 8 CHIMNEY PIPE INSTALLATION PG 6 9 FINISHING YOUR CHIMNEY SYSTEM PG 8 10 TERMINATIONS PG 10 11 FINISHING YOUR FIREPLACE PG 11 12 OPERATING GUIDELINES AND MAINTENANCE INSTRUCTIONS PG...

Страница 3: ...ough grounding may not be required by code in your area it must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70...

Страница 4: ...TLE CLEARANCES Woodwork such as wood trims mantles and other combustible materials should not be placed within 9 inches of the effective opening of this fireplace The effective opening is considered t...

Страница 5: ...mbustible floor surrounding fireplace You may obtain kit No HE P36 or you may fabricate your own per the dimensions shown on figure 10 The hearth extension must project 20 in min to the front and 12 i...

Страница 6: ...stacles It should also be located beyond the reach of small children The maximum height for the air inlet above platform of fireplace is within 3 feet below the termination flue gas outlet For further...

Страница 7: ...TO COMPLY WITH THE STANDARD FOR UNVENTED ROOM HEATERS ANZI IAS AGA Z21 11 2 ARE TO BE INSTALLED IN THIS FIREPLACE NOTE An appropriate FMI hood as shown in page 13 must be installed when using an unven...

Страница 8: ...penetrating a floor or ceiling at an angle use firestop spacer no 30 FS 10DM refer to section on accessory items at the end of this manual When the pipe passes through a framed opening into a living...

Страница 9: ...ee figure 21 FINISHING YOUR CHIMNEY SYSTEM IMPORTANT If an exposed portion of chimney is greater than 4 feet above the roof line use support wires to keep chimney secure The support wires may be attac...

Страница 10: ...HIMNEY MAINTENANCE Have your chimney system cleaned and inspected regularly to ensure safe and efficient operation Refer to your Owners Manual for further guidelines on maintenance and operation Using...

Страница 11: ...structions supplied with the termination The terminations approved for this fireplace are RTL 10D which can be used for flashing or chase and ETL 10D for chase style termination only Figure 27 shows a...

Страница 12: ...refer to section on clearances and the fireplace opening are not blocked or obstructed in any way see fig 30 Use only heat resistant non combustible mortar or adhesive when securing facing material t...

Страница 13: ...n starting a fire this pro vides adequate outside combustion air Close the mechanism when not in use to prevent cold air from entering the room Periodically check your outside air intake vent hood for...

Страница 14: ...on the rating plate located inside the fireplace see figure 1 Refer to the parts list and diagrams when ordering replacement parts for your fireplace Repair parts or accessory items may be bought from...

Отзывы: