www.fmiproducts.com
110398-01F
15
* Purchase the optional equipment shutoff
valve from your dealer.
** Minimum inlet pressure for purpose of input
adjustment.
Figure 14 - Gas Connection
Gas Control
3" Minimum
Equipment Shutoff
Valve With 1/8"
NPT Tap*
Approved Flexible Gas Hose
(if allowed by local codes)
Pipe Tee
Nipple Cap Joint
Sediment Trap
Natural Gas
From Gas Meter
(5" W.C.** to 10.5" W.C.
Pressure)
Propane/LP Gas
From External Regulator
(11" W.C.** to 14" W.C.
Pressure)
to freeze. A sediment trap traps moisture and
contaminants. This keeps them from going
into heater controls. If sediment trap is not
installed or is installed wrong, heater may
not run properly.
CAUTION: Avoid damage to
control. Hold fitting with wrench
when connecting it to gas piping
and/or fittings.
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
WARNING: Never use an
open flame to check for a leak.
Apply a noncorrosive leak detec
-
tion fluid to all joints. Bubbles
forming show a leak. Correct all
leaks at once.
INSTALLATION
Continued
CAUTION: For propane/LP
gas, make sure external regula-
tor has been installed between
propane/LP supply and heater.
See guidelines under
Connect-
ing to Gas Supply
, page 14.
PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2
PSIG (3.5 kPa)
1. Disconnect appliance with its appliance
main gas valve (control valve) and equip-
ment shutoff valve from gas supply piping
system. Pressures in excess of 1/2 psig
will damage heater regulator.
2. Cap off open end of gas pipe where equip
-
ment shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas, or opening main gas
valve located on or near gas meter for
natural gas, or using compressed air.
4. Check all joints of gas supply piping sys
-
tem. Apply a noncorrosive leak detection
fluid to gas joints. Bubbles forming show
a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff
valve to gas supply. Check reconnected
fittings for leaks.
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig-
ure 15).
2. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas, or opening main gas
valve located on or near gas meter for
natural gas, or using compressed air.
Figure 15 - Equipment Shutoff Valve
Open
Closed
Equipment
Shutoff
Valve