Program  

 

 

Program 

Code Function 

Code 

Description 

Entry 

Code 

 

22  

Issue/Rev. 

03 

(8/97) 

103 

Product 2 Alarm Check/Reset 

Read only, Press E to clear 

None 

103 

 
 

Available Alarms  

 
 

BH: Blend High 

LF: Low Flow 

 

BL: Blend Low  

LP: Low Pressure  

 

BP: Back Pressure 

LT: Low Temperature  

 

CF: Not Configured Flow 

OA: Overrun 

 

DA: Program Code 

PR: Pressure Transducer 

 

DR: Density Transducer   

PS: Pulse Security 

 

HD: High Density 

PT: Pulse Transmission Alarm 

 

HF: Excess High Flow 

TP: Temperature Probe 

 

HP: High Pressure 

UF: Unauthorized Flow 

 

HT: High Temperature 

VF: Valve Fault 

 

LD: Low Density 

ZF: Zero Flow 

 
 
104 

Product 3 Alarm Check/Reset 

Read only, Press E to clear 

None 

104 

 
 

Available Alarms  

 
 

BH: Blend High 

LF: Low Flow 

 

BL: Blend Low  

LP: Low Pressure  

 

BP: Back Pressure 

LT: Low Temperature  

 

CF: Not Configured Flow 

OA: Overrun 

 

DA: Program Code 

PR: Pressure Transducer 

 

DR: Density Transducer   

PS: Pulse Security 

 

HD: High Density 

PT: Pulse Transmission Alarm 

 

HF: Excess High Flow 

TP: Temperature Probe 

 

HP: High Pressure 

UF: Unauthorized Flow 

 

HT: High Temperature 

VF: Valve Fault 

 

LD: Low Density 

ZF: Zero Flow 

 
 

Содержание AccuLoad II

Страница 1: ...Preset Delivery System This worksheet applies to AccuLoad II operating with RBU 00 firmware Refer to Operator Reference Manual MN06066L for complete program entry descriptions Security Access Code Company Name Prepared By Date Unit Meter No Location The Most Trusted Name In Measurement ...

Страница 2: ...ation Directory 34 System Input Output Directory 43 System Diagnostic Directory 50 Product Directories 54 Product General Purpose Directory 54 Product Flow Control Directory 54 Product Volume Accuracy Directory 56 Product Temperature Density Directory 59 Product Pressure Directory 61 Product Read Only Directory 64 Product Communications Directory 65 Inputs Outputs Directory 66 Diagnostics Director...

Страница 3: ......

Страница 4: ...Table of Contents i ...

Страница 5: ......

Страница 6: ...ive Injectors 7 Seven Additive Injectors 8 Eight Additive Injectors __ 003 A C Output Relay 1 Enter 00 No Assignment N A 003 Terminals 89 90 01 Additive Relay 1 ADD1 02 Additive Relay 2 ADD2 03 Additive Relay 3 ADD3 04 Additive Relay 4 ADD4 05 Additive Relay 5 ADD5 06 Additive Relay 6 ADD6 07 Additive Relay 7 ADD7 08 Additive Relay 8 ADD8 09 Additive Pump 1 ADP1 10 Additive Pump 2 ADP2 11 Additive...

Страница 7: ...e Pump 6 ADP6 15 Additive Pump 7 ADP7 16 Additive Pump 8 ADP8 17 Alarm Relay ALR __ __ Note When using three or four products this relay must be programmed 00 No Assignment 005 A C Output Relay 3 Enter 00 No Assignment N A 005 Terminals 93 94 01 Additive Relay 1 ADD1 02 Additive Relay 2 ADD2 03 Additive Relay 3 ADD3 04 Additive Relay 4 ADD4 05 Additive Relay 5 ADD5 06 Additive Relay 6 ADD6 07 Addi...

Страница 8: ...e Pump 6 ADP6 15 Additive Pump 7 ADP7 16 Additive Pump 8 ADP8 17 Alarm Relay ALR 22 General Relay GEN 007 A C Output Relay 5 Enter 00 No Assignment N A 007 Terminals 87 88 01 Additive Relay 1 ADD1 02 Additive Relay 2 ADD2 03 Additive Relay 3 ADD3 04 Additive Relay 4 ADD4 05 Additive Relay 5 ADD5 06 Additive Relay 6 ADD6 07 Additive Relay 7 ADD7 08 Additive Relay 8 ADD8 09 Additive Pump 1 ADP1 10 A...

Страница 9: ... ADP7 16 Additive Pump 8 ADP8 17 Alarm Relay ALR 18 Pump Product 1 PMP1 19 Pump Product 2 PMP2 20 Pump Product 3 PMP3 21 Pump Product 4 PMP4 __ __ 009 A C Output Relay 7 Enter 00 No Assignment N A 009 Terminals 124 125 01 Additive Relay 1 ADD1 02 Additive Relay 2 ADD2 03 Additive Relay 3 ADD3 04 Additive Relay 4 ADD4 05 Additive Relay 5 ADD5 06 Additive Relay 6 ADD6 07 Additive Relay 7 ADD7 08 Add...

Страница 10: ...ditive Pump 6 ADP6 15 Additive Pump 7 ADP7 16 Additive Pump 8 ADP8 17 Alarm Relay ALR __ __ Note When using four products this relay must be programmed 00 No Assignment 011 A C Output Relay 9 Enter 00 No Assignment N A 011 Terminals 128 129 01 Additive Relay 1 ADD1 02 Additive Relay 2 ADD2 03 Additive Relay 3 ADD3 04 Additive Relay 4 ADD4 05 Additive Relay 5 ADD5 06 Additive Relay 6 ADD6 07 Additi...

Страница 11: ...ump 6 ADP6 15 Additive Pump 7 ADP7 16 Additive Pump 8 ADP8 17 Alarm Relay ALR 22 General Relay GEN __ __ 013 A C Output Relay 11 Enter 00 No Assignment N A 013 Terminals 121 122 01 Additive Relay 1 ADD1 02 Additive Relay 2 ADD2 03 Additive Relay 3 ADD3 04 Additive Relay 4 ADD4 05 Additive Relay 5 ADD5 06 Additive Relay 6 ADD6 07 Additive Relay 7 ADD7 08 Additive Relay 8 ADD8 09 Additive Pump 1 ADP...

Страница 12: ...ump Product 1 PMP1 19 Pump Product 2 PMP2 20 Pump Product 3 PMP3 21 Pump Product 4 PMP4 __ __ 015 D C Output Relay 1 Enter 00 No Assignment N A 015 Terminals 9 10 01 Additive Relay 1 ADD1 w o Quad OPV 02 Additive Relay 2 ADD2 03 Additive Relay 3 ADD3 Terminals 11 10 04 Additive Relay 4 ADD4 on Quad OPV 05 Additive Relay 5 ADD5 06 Additive Relay 6 ADD6 07 Additive Relay 7 ADD7 08 Additive Relay 8 A...

Страница 13: ...3 ADD3 04 Additive Relay 4 ADD4 05 Additive Relay 5 ADD5 06 Additive Relay 6 ADD6 07 Additive Relay 7 ADD7 08 Additive Relay 8 ADD8 09 Pulse Output POT4 __ __ Note This code is only available for use if the Quad OPV option has been purchased with the AccuLoad II 019 A C Input 1 Enter 00 No Assignment N A 019 Terminals 98 101 01 Additive Feedback 1 AFB1 02 Additive Feedback 2 AFB2 03 Additive Feedb...

Страница 14: ...ct 1 VST1 15 Valve Stem Product 2 VST2 16 Valve Stem Product 3 VST3 17 Valve Stem Product 4 VST4 __ __ Note Or can be used for Master Reset 021 A C Input 3 Enter 00 No Assignment N A 021 Terminals 100 101 01 Additive Feedback 1 AFB1 02 Additive Feedback 2 AFB2 03 Additive Feedback 3 AFB3 04 Additive Feedback 4 AFB4 05 Additive Feedback 5 AFB5 06 Additive Feedback 6 AFB6 07 Additive Feedback 7 AFB7...

Страница 15: ...rogrammed 11 Permissive 1 Contact code 807 must be programmed 5 Remote Start and jumpers must be installed as shown in the Installation Manual MN06064 023 A C Input 5 Enter 00 No Assignment N A 023 Terminals 104 105 01 Additive Feedback 1 AFB1 02 Additive Feedback 2 AFB2 03 Additive Feedback 3 AFB3 04 Additive Feedback 4 AFB4 05 Additive Feedback 5 AFB5 06 Additive Feedback 6 AFB6 07 Additive Feed...

Страница 16: ...ct 1 VST1 15 Valve Stem Product 2 VST2 16 Valve Stem Product 3 VST3 17 Valve Stem Product 4 VST4 __ __ Note Or can be used for Master Reset 025 A C Input 7 Enter 00 No Assignment N A 025 Terminals 106 109 01 Additive Feedback 1 AFB1 02 Additive Feedback 2 AFB2 03 Additive Feedback 3 AFB3 04 Additive Feedback 4 AFB4 05 Additive Feedback 5 AFB5 06 Additive Feedback 6 AFB6 07 Additive Feedback 7 AFB7...

Страница 17: ...uct 1 VST1 15 Valve Stem Product 2 VST2 16 Valve Stem Product 3 VST3 17 Valve Stem Product 4 VST4 __ __ Note Or can be used for Master Reset 027 A C Input 9 Enter 00 No Assignment N A 027 Terminals 108 109 01 Additive Feedback 1 AFB1 02 Additive Feedback 2 AFB2 03 Additive Feedback 3 AFB3 04 Additive Feedback 4 AFB4 05 Additive Feedback 5 AFB5 06 Additive Feedback 6 AFB6 07 Additive Feedback 7 AFB...

Страница 18: ...r can be used for Master Reset Note For Remote Start operation either this code or code 028 must be programmed 11 Permissive 1 Contact code 807 must be programmed 5 Remote Start and jumpers must be installed as shown in the Installation Manual MN06064 029 A C Input 11 Enter 00 No Assignment N A 029 Terminals 111 112 01 Additive Feedback 1 AFB1 02 Additive Feedback 2 AFB2 03 Additive Feedback 3 AFB...

Страница 19: ...7 08 Additive Feedback 8 AFB8 09 First Second High Flow FSC 10 Printer Tray Switch PTS 11 Permissive 1 Contact PRC1 12 Permissive 2 Contact PRC2 13 Valve Power VPW 14 Valve Stem Product 1 VST1 15 Valve Stem Product 2 VST2 16 Valve Stem Product 3 VST3 17 Valve Stem Product 4 VST4 __ __ Note Or can be used for Master Reset 031 RTD 1 Enter 0 RTD Not Used 031 Terminals 14 15 1 Product 1 16 17 2 Produc...

Страница 20: ...digit number indicating 034 Terminals 22 23 the use of this 4 20 Channel First digit 0 Channel Not Used 1 Product 1 2 Product 2 3 Product 3 4 Product 4 Second digit 0 Channel Not Used 1 Temperature 2 Pressure 3 Density e g 11 indicates that this channel would be used by product 1 for a temperature input __ __ 035 4 20 Channel 3 Enter Two digit number indicating 035 Terminals 68 69 the use of this ...

Страница 21: ..._ __ 037 Additive Injector Enter Four digit number indicating 037 1 Plumbing the products that this additive injector is plumbed into 1st digit Product 1 2nd digit Product 2 3rd digit Product 3 4th digit Product 4 A zero in the digit indicates that the injector is not plumbed into that product a one indicates that the injector is plumbed into that product e g 1110 indicates that the injector is pl...

Страница 22: ...put is configured for use and this entry is 0000 the indication is that it is plumbed into the loading arm downstream of the metering system 039 Additive Injector Enter Four digit number indicating 039 3 Plumbing the products that this additive injector is plumbed into 1st digit Product 1 2nd digit Product 2 3rd digit Product 3 4th digit Product 4 A zero in the digit indicates that the injector is...

Страница 23: ...put is configured for use and this entry is 0000 the indication is that it is plumbed into the loading arm downstream of the metering system 041 Additive Injector Enter Four digit number indicating 041 5 Plumbing the products that this additive injector is plumbed into 1st digit Product 1 2nd digit Product 2 3rd digit Product 3 4th digit Product 4 A zero in the digit indicates that the injector is...

Страница 24: ...put is configured for use and this entry is 0000 the indication is that it is plumbed into the loading arm downstream of the metering system 043 Additive Injector Enter Four digit number indicating 043 7 Plumbing the products that this additive injector is plumbed into 1st digit Product 1 2nd digit Product 2 3rd digit Product 3 4th digit Product 4 A zero in the digit indicates that the injector is...

Страница 25: ... plumbed into the loading arm downstream of the metering system 045 089 Unassigned at Present 045 089 090 Input Output Enter 1 One Product 090 Configuration 2 Two Products 3 Three Products 4 Four Products __ Warning If you have already programmed codes 001 through 045 do not program this code It may change what you have already programmed Note Entering the above number will program the AccuLoad II...

Страница 26: ... Code O2 Printer Paper Out DA Software Version O4 Printer Paper Out DA Internal Temperature PA Power Failure DA Keypad Alarm P2 Printer Communication DA Keypad Mismatch P4 Printer Communication DA Program Code SF Storage Full D2 Printer Deselected SP Shared Printer D4 Printer Deselected TK Ticket Alarm E2 Printer Error ZF Zero Flow Note This alarm applies to RBU 07 and above firmware only Note Thi...

Страница 27: ...F Excess High Flow TP Temperature Probe HP High Pressure UF Unauthorized Flow HT High Temperature VF Valve Fault LD Low Density ZF Zero Flow 104 Product 3 Alarm Check Reset Read only Press E to clear None 104 Available Alarms BH Blend High LF Low Flow BL Blend Low LP Low Pressure BP Back Pressure LT Low Temperature CF Not Configured Flow OA Overrun DA Program Code PR Pressure Transducer DR Density...

Страница 28: ...ow Density ZF Zero Flow 106 Recipe Alarms Check Reset Read only Press E to clear None 106 Available Alarms DA Program Code 107 Transaction Alarms To be read only None 107 108 Ready Mode Alarms To be read only None 108 109 Set Time Enter Five digits Two digits 109 for hours Two digits for minutes and one to indicate military time AM or PM The last digit will be 0 AM 1 PM and 2 Military e g 01 130 _...

Страница 29: ...er 0 English 144 Initialization 1 Portuguese __ Note This code applies to RBU 05 and above firmware 145 Ready Run Mode Enter The number of the alarm that is to 145 Clearable Alarms be changed see Appendix for the Selection alarms associated numbers and recording entries When the alarm is displayed enter a 0 if the alarm is allowed to be cleared in the Ready Run Mode Enter a 1 if the alarm is not a...

Страница 30: ...__ 184 Ready Mode Enter Up to 15 characters 184 Message for a prompt message e g Load Arm 1 _________________ 185 Run Ready Mode Enter The number of the display 185 Customized Display that you want to change Press ENTER the default display will appear for that number or you can scroll through the displays by pressing the ENTER key The display can be changed using the character set resident in the ...

Страница 31: ...d in code 201 will be used as the low flow start volume 203 Low Flow Start Rate Enter Four digits in whole 203 units per minute e g 0150 0000 entry will not allow the valve to open __ __ __ __ 204 Low Flow Start Enter 0 Low Flow Start always after 204 zero flow 1 Low Flow Start at beginning of batch only ___ 205 System First High Enter Four digits in whole units 205 Flow Rate e g 0600 0000 Entry w...

Страница 32: ...2 Zero Flow Alarm Enter 0 Zero Flow Alarm Disabled 212 1 Zero Flow Alarm Enabled __ Note This code applies to RBU 08 and above firmware 213 239 Unassigned at Present 213 239 240 Protection of Program Enter 0 for Weights and Measures Mode 240 Codes 280 289 1 for Program Mode __ 280 Clean Line Product Enter 1 for Product 1 280 2 for Product 2 3 for Product 3 4 for Product 4 __ Note If a recipe of 10...

Страница 33: ...imer amount of time between ratio flow adjustments e g 01 __ __ Note This adjustment must not be set to 00 285 299 Unassigned at Present 285 299 300 System Volume Accuracy Directory 300 301 Transaction Control Enter 0 Local Tray Switch 301 1 Print Key 2 Remote 3 Master Reset __ 302 Maximum Preset Enter Five digits in whole units 302 Volume e g up to 99 999 units 00000 disables option __ __ __ __ _...

Страница 34: ... digit Gross at Standard Temperature Volumes GT 3rd digit Net Volumes NT 4th digit Mass Totals MA A zero in the digit indicates that the volume will not be saved in local storage a one indicates the volume will be saved in local storage e g 1100 indicates the raw volumes and the Gross at standard temperature volumes will be stored along with the gross volumes __ __ __ __ 308 339 Unassigned at Pres...

Страница 35: ...rover at Standard Temperature and Pressure Preset Net 4 Mass Preset Whole Units __ 347 Recipes Per Enter 0 Single Recipe Transaction 347 Transaction 1 Multiple Recipes Transaction __ 348 Blend Tolerance Enter Two digits in tenths of a 348 Percentage percentage for the tolerance allowed for all delivered blends e g 5 0 5 __ __ Note The larger of the tolerances as calculated using the percentage ent...

Страница 36: ... Three digits representing 352 Frequency will be output by the combinated pulse output The range of this code is 004 to 999 e g 500 Hz __ __ __ Note This code applies to RBU 02 and above firmware 353 Resolution of Enter 0 Whole Units 353 Volumetric Totals 1 Tenth Units on a Printed Report 2 Hundredth Units __ Note This code applies to RBU 08 and above firmware 354 Number of Batches Enter A single ...

Страница 37: ... 1 Fahrenheit 2 Celsius __ 442 Reference Enter Four digit reference 442 Temperature temperature in tenth degrees e g 060 0 __ __ __ __ 443 Density Units Enter 0 No Density Units 443 1 Lbs Ft3 2 Kgs M3 __ 444 Volume Mass Enter 0 Gallons per Density Units 444 Conversion 1 Dekaliters per Density Units 2 Liters per Density Units 3 Barrels per Density Units 4 Cubic Meters per Density Units __ 445 Mass ...

Страница 38: ...ressure Used 541 1 Psi 2 Bar 3 Kgcm __ 542 599 Unassigned at Present 542 599 600 System Read Only Directory 600 601 Injector 1 To be read only None 601 Non resettable Volumes 602 Injector 2 To be read only None 602 Non resettable Volumes 603 Injector 3 To be read only None 603 Non resettable Volumes 604 Injector 4 To be read only None 604 Non resettable Volumes 605 Injector 5 To be read only None ...

Страница 39: ...tion of Program Enter 0 for Weights and Measures Mode 640 Codes 680 689 1 for Program Mode __ 641 699 Unassigned at Present 641 699 700 System Communication Directory 700 701 EIA 232 Enter 0 No Communications 701 Communication 1 for EIA Type Terminal Type 2 for EIA Type Minicomputer __ 702 EIA 232 Enter 0 for Poll Only 702 Communication 1 for Poll and Authorize Control 2 for Remote Control 3 for A...

Страница 40: ...s Odd 2 EIA 232 7 Bits None 3 EIA 232 8 Bits Even 4 EIA 232 8 Bits Odd 5 EIA 232 8 Bits None __ 705 EIA 485 Enter 0 No Communications 705 Communication 1 EIA Type Terminal Type 2 EIA Type Minicomputer __ 706 EIA 485 Enter 0 for Polling Only 706 Communication 1 for Poll and Authorize Control 2 for Remote Control 3 for Auto Out 4 for Shared Auto Out __ 707 EIA 485 Baud Rate Enter 0 for 110 Baud 707 ...

Страница 41: ...710 Message 1 for prompt message e g Smith Meter Inc _______________ 711 Printer Output Enter Up to 20 characters 711 Message 2 for printer message e g P O Box 10428 _______________ 712 Printer Output Enter Up to 20 characters 712 Message 3 for printer message e g 1602 Wagner Ave _______________ 713 Printer Output Enter Up to 20 characters 713 Message 4 for printer message e g Erie Pa ____________...

Страница 42: ...message e g Connect Ground _______________ 720 Meter ID Enter Up to 20 characters 720 for meter identification e g XX12 _______________ 721 Print Summary Enter 0 Summary w Report 721 1 No Summary w Report 2 Summary only 3 User Configured Report __ Note This Selection applies to RBU 01 and above firmware 722 Print Volumes Enter 0 Print all volumes 722 1 Print recipe volumes only 2 Print product vol...

Страница 43: ...0 000 disables the Communications Alarm Mode __ __ __ 743 Communications Enter 0 Standby Mode 743 Alarm Mode 1 Communications Alarm Mode 2 Standby and Communications Alarm Mode __ 744 Prompt Time out Enter Three digits in seconds 744 of time out allowed with each prompt e g 015 __ __ __ Note Minimum time out is 10 seconds 745 Prompt Data Entry 1 Enter Two digits representing 745 the prompt data re...

Страница 44: ...a Entry 5 Enter Two digits representing 749 the prompt data response First digit 0 Displayed First digit 1 Hidden Display Second digit 0 9 Digits for prompt entry e g 16 __ __ 750 Start Key Enter 0 Start Key Enabled 750 Enable Disable 1 Start Key Disabled __ 751 Shared Printer Enter 0 for No SP Alarm 751 Out Alarm 1 for Local SP Alarm 2 for Program SP Alarm __ 752 Shared Printer Out Enter Two digi...

Страница 45: ...756 Print the totals that will be printed on the Product Receipt Ticket 1st digit Raw Totals 2nd digit Gross Totals 3rd digit Gross at Standard Temperature Totals 4th digit Net Totals 5th digit Mass Totals A zero in the digit indicates the total will not be printed a one indicates the total will be printed e g 01100 indicates that Gross totals and the Gross at Standard Temperature will be printed ...

Страница 46: ...rage Density will be printed on the Product Receipt Ticket __ __ __ 758 Select the Additive Enter Eight digit number indicating 758 Volumes to Print the additive volumes that will be printed on the Product Receipt Ticket 1st digit Additive Volume 1 2nd digit Additive Volume 2 3rd digit Additive Volume 3 4th digit Additive Volume 4 5th digit Additive Volume 5 6th digit Additive Volume 6 7th digit A...

Страница 47: ...79 780 Number of Prompts Enter One digit between 0 and 5 780 representing the number of prompts used in the Standby Mode e g 4 0 disables prompts in the Standby Mode __ 781 Print Transaction Enter Three digit Transaction 781 Number to print the transaction data desired e g 010 will print the tenth transaction back from the current transaction __ __ __ 782 Prompts Printed Enter 0 Standby Blank 782 ...

Страница 48: ... Volume of remaining system volume to be loaded when the Additive Injectors will be stopped e g 75 __ 803 Additive Injector Enter 0 for Raw output 803 Output 1 for Gross output 2 for Gst output 3 for Net output __ 804 Manual Auto Enter 0 for Auto Injectors 804 Additive Injector 1 for Manual Injectors Selection when in the Standby Mode 2 for Manual Injectors per transaction 3 for Manual Injectors p...

Страница 49: ...p to 20 characters 810 for prompt message if no AC power is detected on the AC Input Programmed for Printer Tray Switch or Master Reset e g Please Insert Ticket _______________ 811 Permissive 2 Enter 0 No Permissive 2 811 1 Permissive 2 Transaction start only 2 Permissive 2 Continuously 3 Start Permissive 2 4 Batch Permissive 2 5 Remote Stop __ Note Option 5 requires hardware jumpers see Installat...

Страница 50: ...__ 818 Additive 5 Message Enter Up to nine characters 818 for Additive 5 Message on the Product Receipt Ticket e g Dye ________________ 819 Additive 6 Message Enter Up to nine characters 819 for Additive 6 Message on the Product Receipt Ticket e g Dye ________________ 820 Additive 7 Message Enter Up to nine characters 820 for Additive 7 Message on the Product Receipt Ticket e g Dye _______________...

Страница 51: ...me of product to be injected for each Additive Injector cycle e g 001 000 __ __ __ __ __ __ 845 Additive Injector 3 Enter 0 No Injector 3 Feedback 845 Feedback 1 Injector 3 Feedback Control 2 Injector 3 Feedback Only __ 846 Additive Injector 3 Enter Six digits defining 846 Volume per Cycle the volume of product to be injected for each Additive Injector cycle e g 001 000 __ __ __ __ __ __ 847 Addit...

Страница 52: ... 001 000 __ __ __ __ __ __ 853 Additive Injector 7 Enter 0 No Injector 7 Feedback 853 Feedback 1 Injector 7 Feedback Control 2 Injector 7 Feedback Only __ 854 Additive Injector 7 Enter Six digits defining 854 Volume per Cycle the volume of product to be injected for each Additive Injector cycle e g 001 000 __ __ __ __ __ __ 855 Additive Injector 8 Enter 0 No Injector 8 Feedback 855 Feedback 1 Inje...

Страница 53: ...ditive volumes to the delivered product volumes __ __ __ __ __ __ __ E __ __ __ 859 Additive Injector Enter Two digits defining 859 Feedback Errors the number of errors before alarming __ __ 860 Injector 1 Feedback Enter Three digits in seconds 860 Delay allowed between feedbacks before an alarm __ __ __ 861 Injector 2 Feedback Enter Three digits in seconds 861 Delay allowed between feedbacks befo...

Страница 54: ...its Enter Five digits For 869 4 20 Channel 1 maximum units at 20 mA in tenth units e g 1600 0 __ __ __ __ __ Note If the channel is selected for temperature the first digit entered is the sign or Where 0 1 870 Minimum Units Enter Five digits in tenth units 870 4 20 Channel 2 for minimum units at 4 mA e g 160 0 __ __ __ __ __ Note If the channel is selected for temperature the first digit entered i...

Страница 55: ... the first digit entered is the sign or Where 0 1 875 Maximum Units Enter Five digits in tenth 875 4 20 Channel 4 units for maximum units at 20 mA e g 450 0 __ __ __ __ __ Note If the channel is selected for temperature the first digit entered is the sign or Where 0 1 876 899 Unassigned at Present 876 899 900 System Diagnostic Directory 900 901 Diagnostic Display Test None 901 902 Diagnostic Keypa...

Страница 56: ...ode applies to RBU 10 and above firmware 914 939 Unassigned at Present 914 939 940 Protection of Program Enter 0 for Weights and Measures Mode 940 Codes 980 989 1 for Program Mode __ 941 Diagnostic Communication Test EIA 232 None 941 No Echo Back 942 Diagnostic Communication Test EIA 232 None 942 With Echo 943 Diagnostic Communication Test EIA 485 None 943 No Echo Back 944 Diagnostic Communication...

Страница 57: ...hannel 4 Contact None 952 953 Diagnostic Contact Input Test None 953 954 Diagnostic High Speed Prover Product 1 None 954 955 Diagnostic High Speed Prover Product 2 None 955 956 Diagnostic High Speed Prover Product 3 None 956 957 Diagnostic High Speed Prover Product 4 None 957 958 Diagnostic Pulse Out 1 Test None 958 959 Diagnostic Pulse Out 2 Test None 959 960 Diagnostic Pulse Out 3 Test None 960 ...

Страница 58: ...sent 965 990 991 Diagnostic Relay Test None 991 992 Diagnostic Ram Test None 992 993 Diagnostic Power up Diagnostics None 993 994 Diagnostic See Operator Reference Manual None 994 995 Diagnostic See Operator Reference Manual None 995 996 Diagnostic Watchdog None 996 997 Diagnostic Relay Select Test 1 None 997 998 Diagnostic Relay Select Test 2 None 998 999 Diagnostic See Operator Reference Manual ...

Страница 59: ...ntifier e g Regular Prod 1___________________________ Prod 2___________________________ Prod 3___________________________ Prod 4___________________________ 181 199 Unassigned at Present 200 Product Flow Control Directory 201 Excess Flow Rate Enter Two digits as a percentage e g 10 00 Disables the High Flow Alarm __ __ __ __ __ __ __ __ 202 Overrun Alarm Limit Enter Two digits in whole units e g 15...

Страница 60: ...age e g 3 __ __ __ __ 210 Low Flow Rate Alarm Enter Three digits in whole Limit units per minute e g 050 000 disables the alarm ____ ____ ____ ____ 211 PT VF Time Delay Enter Two digits in seconds of time delay e g 15 Entry must not be 00 __ __ __ __ __ __ __ __ 212 239 Unassigned at Present 240 Protection of Program Enter 0 for Weights and Measures Mode Codes 280 289 1 for Program Mode __ __ __ _...

Страница 61: ...s and Measures Mode Codes 380 389 1 for Program Mode __ __ __ __ 341 Flow Rate for Enter Four digits in whole units Meter Factor 1 per minute e g 0600 _____ _____ _____ _____ 342 Meter Factor 1 Enter Five digits as one whole number followed by four decimals e g 1 0033 _ _____ _ _____ _ _____ _ _____ 343 Flow Rate for Enter Four digits in whole units Meter Factor 2 per minute e g 0400 _____ _____ _...

Страница 62: ... _____ _ _____ _ _____ 350 Meter Factor Enter Four digits representing Reference the temperature that the percent Temperature meter factor variation was determined Three whole units and one decimal in degrees e g 120 1 _____ _ _____ _ _____ _ _____ _ 351 Pulse Output Enter 0 Raw Pulse Out 1 1 Gross Pulse Out 1 2 Gst Pulse Out 1 3 Net Pulse Out 1 4 Mass Pulse Out 1 __ __ __ __ 352 Pulse Resolution ...

Страница 63: ...fining Rate Cutoff the flow rate that the Dual Pulse errors will begin to be counted _ _ _ _ _ _ _ _ _ _ _ _ 357 389 Unassigned at Present 390 Master Meter Factor Enter Five digits as one whole number followed by four decimals e g 1 0040 Restricts meter factors 1 through 4 program codes 353 355 357 and 359 to 2 of this entry Enter 0 0000 to disable this feature _ _____ _ _____ _ _____ _ _____ 391 ...

Страница 64: ...I Table 6A 16 API Table 53B 05 API Table 6B 17 API Table 53D 06 API Table 6C 18 API Table 54 07 API Table 6D 19 API Table 54A 08 API Table 23A 20 API Table 54B 09 API Table 23B 21 API Table 54C 10 API Table 23D 22 API Table 54D 11 API Table 24 ___ ___ ___ ___ 442 Reference Density Enter Five digit density with floating decimal e g 0999 9 to 0 9999 Depending on selection in code 441 _______ _______...

Страница 65: ...n entry of 999 9 will disable this feature e g 0085 0 85 0 _____ _ _____ _ _____ _ _____ _ 446 Temperature Offset Enter Three digits First digit must be 0 or 1 0 positive 1 negative Second and third digits represent the offset temperature in tenth degrees e g 10 5 entered will display at 0 5 degrees offset __ __ __ __ __ __ __ __ __ __ __ __ 447 Low Density Alarm Enter Four digits The range is fro...

Страница 66: ...to achieve a desired flow rate Timer Setting e g 20 00 disables this minimum flow rate timer and the back pressure reduction in code 504 ___ ___ ___ ___ 504 BP Reduction Enter Two digits in reduction of flow rate for back pressure flow control and AFO e g 90 ___ ___ ___ ___ 505 Low Pressure Alarm Enter Four digits indicating the pressure reading that will generate a low pressure alarm The range is...

Страница 67: ...cm2 in tenths of pressure units e g 006 0 Pressure units are dependent on entry made in code 541 of Systems Directory ____ _ ____ _ ____ _ ____ _ 544 Low Product Vapor Enter Four digits in Degrees Pressure P1 C or Degrees F that corresponds Temperature to the low vapor pressure in code 543 First digit 0 Plus Degrees First digit 1 Minus Degrees e g 1150 150 Temperature units are dependent on entry ...

Страница 68: ...entry made in code 541 of the Systems Directory ____ _ ____ _ ____ _ ____ _ Note This entry must not exceed the entry made in 545 or it will be ignored 548 High Product Vapor Enter Four digits in Degrees Pressure P3 C or Degrees F that corresponds Temperature to the high vapor pressure in code 546 First digit 0 Plus Degrees First digit 1 Minus Degrees e g 0600 060 Temperature units are dependent o...

Страница 69: ... Non resettable To be read only None None None None Volume 605 Mass Non resettable To be read only None None None None Totals 606 Load Average To be read only None None None None Temperature 607 Load Average To be read only None None None None Pressure 608 Load Average Density To be read only None None None None 609 Load Average To be read only None None None None Meter Factor 610 639 Unassigned a...

Страница 70: ...________ Prod3______________________________ Prod4______________________________ 703 HM Classification Enter Third 20 characters of for Printout the classification Prod1______________________________ Prod2______________________________ Prod3______________________________ Prod4______________________________ 704 HM Classification Enter Last 20 characters of for Printout the classification Prod1_____...

Страница 71: ...sent 840 Protection of Program Enter 0 for Weights and Measures Mode Codes 880 889 1 for Program Mode __ __ __ __ 841 899 Unassigned at Present 900 Product Diagnostics Directory 901 939 Unassigned at Present 940 Protection of Program Enter 0 for Weights and Measures Mode None Codes 980 989 1 for Program Mode __ __ __ __ 941 999 Unassigned at Present ...

Страница 72: ..._03 Volume __04 Recipe Gross Non resettable To be read only None __04 Volume __05 Recipe Gross at Standard To be read only None __05 Temp Non resettable Volume __06 Recipe Net Non resettable To be read only None __06 Volume __07 Recipe Mass Non resettable To be read only None __07 Total __08 HM Classification Enter 1 Product 1 __08 2 Product 2 3 Product 3 4 Product 4 __ __09 Minimum Preset To be r...

Страница 73: ...et at Standard Temperature and Pressure Net 4 Mass Preset __ __42 Blend Deliver Display Enter 0 Raw Delivery Raw __42 1 Gross Delivery Grs 2 Gross Delivery at Standard Temperature Gst 3 Gross Delivery at Standard Temperature and Pressure Net 4 Mass Delivery __ __43 Product 1 Enter Four digits in tenth __43 Percentage of a percent e g 050 0 __ __ __ __ Note Codes __43 __44 __45 and __46 must add up...

Страница 74: ... zero in the digit indicates the injector will not be used with that product a one indicates the injector will be used with that product e g 0100 indicates that this injector is used with product 2 only __ __ __ __ __48 Product using Enter Four digit number indicating __48 Injector 2 the products this injector is used with 1st digit Product 1 2nd digit Product 2 3rd digit Product 3 4th digit Produ...

Страница 75: ...ector 4 the products this injector is used with 1st digit Product 1 2nd digit Product 2 3rd digit Product 3 4th digit Product 4 A zero in the digit indicates the injector will not be used with that product a one indicates the injector will be used with that product e g 0100 indicates that this injector is used with product 2 only __ __ __ __ __51 Product using Enter Four digit number indicating __...

Страница 76: ...ector 7 the products this injector is used with 1st digit Product 1 2nd digit Product 2 3rd digit Product 3 4th digit Product 4 A zero in the digit indicates the injector will not be used with that product a one indicates the injector will be used with that product e g 0100 indicates that this injector is used with product 2 only __ __ __ __ __54 Product using Enter Four digit number indicating __...

Страница 77: ...tive Injector Enter Three digits in whole units __83 Pulser No 3 of delivered liquid per injector pulse e g 040 __ __ __ __84 Additive Injector Enter Three digits in whole units __84 Pulser No 4 of delivered liquid per injector pulse e g 040 __ __ __ __85 Additive Injector Enter Three digits in whole units __85 Pulser No 5 of delivered liquid per injector pulse e g 040 __ __ __ __86 Additive Injec...

Страница 78: ...__________ _____________ __12 _____________ ______________ _____________ _____________ __13 _____________ ______________ _____________ _____________ __40 __ __ __ __ __41 __ __ __ __ __42 __ __ __ __ __43 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __44 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __45 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __46 __ __ __ __ __ __ __ __ __ __ __ __ ...

Страница 79: ... __ __ __82 __ __ __ __ __ __ __ __ __ __ __ __ __83 __ __ __ __ __ __ __ __ __ __ __ __ __84 __ __ __ __ __ __ __ __ __ __ __ __ __85 __ __ __ __ __ __ __ __ __ __ __ __ __86 __ __ __ __ __ __ __ __ __ __ __ __ __87 __ __ __ __ __ __ __ __ __ __ __ __ __88 __ __ __ __ __ __ __ __ __ __ __ __ Note Codes __09 __10 __11 __12 and __13 are Read Only codes Space has been provided to record the flow rat...

Страница 80: ...__________ _____________ __12 _____________ ______________ _____________ _____________ __13 _____________ ______________ _____________ _____________ __40 __ __ __ __ __41 __ __ __ __ __42 __ __ __ __ __43 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __44 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __45 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __46 __ __ __ __ __ __ __ __ __ __ __ __ ...

Страница 81: ... __ __ __82 __ __ __ __ __ __ __ __ __ __ __ __ __83 __ __ __ __ __ __ __ __ __ __ __ __ __84 __ __ __ __ __ __ __ __ __ __ __ __ __85 __ __ __ __ __ __ __ __ __ __ __ __ __86 __ __ __ __ __ __ __ __ __ __ __ __ __87 __ __ __ __ __ __ __ __ __ __ __ __ __88 __ __ __ __ __ __ __ __ __ __ __ __ Note Codes __09 __10 __11 __12 and __13 are Read Only codes Space has been provided to record the flow rat...

Страница 82: ...___________ _____________ __12 _____________ ______________ _____________ _____________ __13 _____________ ______________ _____________ _____________ __40 __ __ __ __ __41 __ __ __ __ __42 __ __ __ __ __43 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __44 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __45 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __46 __ __ __ __ __ __ __ __ __ __ __ __...

Страница 83: ..._ __ __ __82 __ __ __ __ __ __ __ __ __ __ __ __ __83 __ __ __ __ __ __ __ __ __ __ __ __ __84 __ __ __ __ __ __ __ __ __ __ __ __ __85 __ __ __ __ __ __ __ __ __ __ __ __ __86 __ __ __ __ __ __ __ __ __ __ __ __ __87 __ __ __ __ __ __ __ __ __ __ __ __ __88 __ __ __ __ __ __ __ __ __ __ __ __ Note Codes __09 __10 __11 __12 and __13 are Read Only codes space has been provided to record the flow ra...

Страница 84: ...____________ _____________ __12 _____________ ______________ _____________ _____________ __13 _____________ ______________ _____________ _____________ __40 __ __ __ __ __41 __ __ __ __ __42 __ __ __ __ __43 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __44 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __45 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __46 __ __ __ __ __ __ __ __ __ __ __ _...

Страница 85: ...__ __ __ __82 __ __ __ __ __ __ __ __ __ __ __ __ __83 __ __ __ __ __ __ __ __ __ __ __ __ __84 __ __ __ __ __ __ __ __ __ __ __ __ __85 __ __ __ __ __ __ __ __ __ __ __ __ __86 __ __ __ __ __ __ __ __ __ __ __ __ __87 __ __ __ __ __ __ __ __ __ __ __ __ __88 __ __ __ __ __ __ __ __ __ __ __ __ Note Codes __09 __10 __11 __12 and __13 are Read Only codes space has been provided to record the flow r...

Страница 86: ...____________ _____________ __12 _____________ ______________ _____________ _____________ __13 _____________ ______________ _____________ _____________ __40 __ __ __ __ __41 __ __ __ __ __42 __ __ __ __ __43 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __44 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __45 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __46 __ __ __ __ __ __ __ __ __ __ __ _...

Страница 87: ...__ __ __ __82 __ __ __ __ __ __ __ __ __ __ __ __ __83 __ __ __ __ __ __ __ __ __ __ __ __ __84 __ __ __ __ __ __ __ __ __ __ __ __ __85 __ __ __ __ __ __ __ __ __ __ __ __ __86 __ __ __ __ __ __ __ __ __ __ __ __ __87 __ __ __ __ __ __ __ __ __ __ __ __ __88 __ __ __ __ __ __ __ __ __ __ __ __ Note Codes __09 __10 __11 __12 and __13 are Read Only codes space has been provided to record the flow r...

Страница 88: ...____________ _____________ __12 _____________ ______________ _____________ _____________ __13 _____________ ______________ _____________ _____________ __40 __ __ __ __ __41 __ __ __ __ __42 __ __ __ __ __43 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __44 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __45 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __46 __ __ __ __ __ __ __ __ __ __ __ _...

Страница 89: ...__ __ __ __82 __ __ __ __ __ __ __ __ __ __ __ __ __83 __ __ __ __ __ __ __ __ __ __ __ __ __84 __ __ __ __ __ __ __ __ __ __ __ __ __85 __ __ __ __ __ __ __ __ __ __ __ __ __86 __ __ __ __ __ __ __ __ __ __ __ __ __87 __ __ __ __ __ __ __ __ __ __ __ __ __88 __ __ __ __ __ __ __ __ __ __ __ __ Note Codes __09 __10 __11 __12 and __13 are Read Only codes space has been provided to record the flow r...

Страница 90: ...inue 24 007 Remove Ticket 24 008 Please Wait 24 009 Report Pending to Print 24 010 No Local Start Allowed 24 011 Select Recipe 13 012 Recipe No 10 013 No Recipes Available 20 014 Current Recipe 15 015 Current Products 17 016 Recipe Avg Dens 15 017 Recipe Ld Temp 14 018 LdTmp 5 019 Load Avg Tmp 12 020 Ld 3 021 Avg Pres 8 022 Avg Den 7 023 Load Avg Mfac 13 024 Enter Preset Amount 19 025 AccuLoad II ...

Страница 91: ...36 Summary 7 037 Dyn Display 12 038 Restart in 11 039 Valve Delay 14 040 Not Authorized 24 041 Flow 4 042 Flow 7 043 Flow 7 044 Flow 7 045 Flow 7 046 Min 4 047 Hr 3 048 Temperature 15 049 Ref Density 12 050 Rel Density 18 051 Meter Factor 18 052 Raw 3 053 Grs 3 054 Gst 3 055 Net 3 056 Mass 4 057 Mas 3 058 Raw Transaction 15 059 Grs Transaction 15 060 Gst Transaction 15 ...

Страница 92: ... 3 7 066 Add 4 7 067 Add 5 7 068 Add 6 7 069 Add 7 7 070 Add 8 7 071 Injector 8 072 Select Injector 16 073 Inj On 8 074 No Injectors Selected 24 075 Select Injectors 16 076 Inj 3 077 Prg 3 078 Cal 3 079 Density 7 080 Total 5 081 Valve Requested 17 082 Open 4 083 Closed 6 084 Lock 4 085 Off 3 086 On 3 087 Secs 5 088 Current 7 089 Desired 7 090 of Batch 10 ...

Страница 93: ...ion volume to be exceeded 3 24 117 118 Fatal Entry is out of specified range 2 24 119 Prv Err 7 120 Load Completed 16 121 Load Terminated 16 Note The output length of each table entry signifies the maximum number of characters allowable for that particular message even though the default message may not take up all spaces allowed Note An entry number flagged with an asterisk designates that the en...

Страница 94: ... volumes If the corresponding batch volumes are not saved in local storage the transaction volumes will print as zeros 4 This entry is always saved but the number of bytes depends on the number of batches per transaction Items not marked are user selectable to be saved or not saved in local storage DELIVERY REPORT CONFIGURABLE ENTRY TABLE Entry Description Code Ref Columns Bytes 1 Alarm History Al...

Страница 95: ...Second Batch Run 6 23 Second User Selected Volume for the Recipe Volume for the Third Batch Run 6 24 Second User Selected Volume for the Recipe Volume for the Fourth Batch Run 6 25 Second User Selected Volume for the Recipe Volume for the Fifth Batch Run 6 26 Second User Selected Volume for the Recipe Volume for the Sixth Batch Run 6 27 Third User Selected Volume for the Recipe Volume for the Firs...

Страница 96: ...saction Volume of the Fourth Recipe Run First User Selected Volume 6 43 Transaction Volume of the Fifth Recipe Run First User Selected Volume 6 44 Transaction Volume of the Sixth Recipe Run First User Selected Volume 6 45 Transaction Volume of the First Recipe Run Second User Selected Volume 6 46 Transaction Volume of the Second Recipe Run Second User Selected Volume 6 47 Transaction Volume of the...

Страница 97: ...r Four Name S817 9 61 Additive Number Five Name S818 9 62 Additive Number Six Name S819 9 63 Additive Number Seven Name S820 9 64 Additive Number Eight Name S821 9 65 Additive Injector 1 Volume for the First Batch Run 9 4 66 Additive Injector 1 Volume for the Second Batch Run 9 4 67 Additive Injector 1 Volume for the Third Batch Run 9 4 68 Additive Injector 1 Volume for the Fourth Batch Run 9 4 69...

Страница 98: ...njector 3 Volume for the Fifth Batch Run 9 4 82 Additive Injector 3 Volume for the Sixth Batch Run 9 4 83 Additive Injector 4 Volume for the First Batch Run 9 4 84 Additive Injector 4 Volume for the Second Batch Run 9 4 85 Additive Injector 4 Volume for the Third Batch Run 9 4 86 Additive Injector 4 Volume for the Fourth Batch Run 9 4 87 Additive Injector 4 Volume for the Fifth Batch Run 9 4 88 Ad...

Страница 99: ...r 6 Volume for the Sixth Batch Run 9 4 101 Additive Injector 7 Volume for the First Batch Run 9 4 102 Additive Injector 7 Volume for the Second Batch Run 9 4 103 Additive Injector 7 Volume for the Third Batch Run 9 4 104 Additive Injector 7 Volume for the Fourth Batch Run 9 4 105 Additive Injector 7 Volume for the Fifth Batch Run 9 4 106 Additive Injector 7 Volume for the Sixth Batch Run 9 4 107 A...

Страница 100: ...oduct Name of Product Three P180 9 124 Product Name of Product Four P180 9 125 First User Selected Volume for Product One First Batch 6 126 First User Selected Volume for Product One Second Batch 6 4 127 First User Selected Volume for Product One Third Batch 6 4 128 First User Selected Volume for Product One Fourth Batch 6 4 129 First User Selected Volume for Product One Fifth Batch 6 4 130 First ...

Страница 101: ...olume for Product Four First Batch 6 144 First User Selected Volume for Product Four Second Batch 6 4 145 First User Selected Volume for Product Four Third Batch 6 4 146 First User Selected Volume for Product Four Fourth Batch 6 4 147 First User Selected Volume for Product Four Fifth Batch 6 4 148 First User Selected Volume for Product Four Sixth Batch 6 4 149 Second User Selected Volume for Produ...

Страница 102: ... Product Three Second Batch 6 4 163 Second User Selected Volume for Product Three Third Batch 6 4 164 Second User Selected Volume for Product Three Fourth Batch 6 4 165 Second User Selected Volume for Product Three Fifth Batch 6 4 166 Second User Selected Volume for Product Three Sixth Batch 6 4 167 Second User Selected Volume for Product Four First Batch 6 168 Second User Selected Volume for Prod...

Страница 103: ...or Product Two Third Batch 6 4 182 Third User Selected Volume for Product Two Fourth Batch 6 4 183 Third User Selected Volume for Product Two Fifth Batch 6 4 184 Third User Selected Volume for Product Two Sixth Batch 6 4 185 Third User Selected Volume for Product Three First Batch 6 186 Third User Selected Volume for Product Three Second Batch 6 4 187 Third User Selected Volume for Product Three T...

Страница 104: ...uct Four First User Selected Volume 6 201 Transaction Volume of Product One Second User Selected Volume 6 202 Transaction Volume of Product Two Second User Selected Volume 6 203 Transaction Volume of Product Three Second User Selected Volume 6 204 Transaction Volume of Product Four Second User Selected Volume 6 205 Transaction Volume of Product One Third User Selected Volume 6 206 Transaction Volu...

Страница 105: ...or Product One Fifth Batch 6 2 220 Load Average Temperature for Product One Sixth Batch 6 2 221 Load Average Temperature for Product Two First Batch 6 2 222 Load Average Temperature for Product Two Second Batch 6 2 223 Load Average Temperature for Product Two Third Batch 6 2 224 Load Average Temperature for Product Two Fourth Batch 6 2 225 Load Average Temperature for Product Two Fifth Batch 6 2 2...

Страница 106: ...erage Temperature for Product Four Sixth Batch 6 2 239 Transaction Load Average Temperature First Recipe 6 2 240 Transaction Load Average Temperature Second Recipe 6 2 241 Transaction Load Average Temperature Third Recipe 6 2 242 Transaction Load Average Temperature Fourth Recipe 6 2 243 Transaction Load Average Temperature Fifth Recipe 6 2 244 Transaction Load Average Temperature Sixth Recipe 6 2...

Страница 107: ...wo Second Batch 6 2 263 Load Average Density Product Two Third Batch 6 2 264 Load Average Density Product Two Fourth Batch 6 2 265 Load Average Density Product Two Fifth Batch 6 2 266 Load Average Density Product Two Sixth Batch 6 2 267 Load Average Density Product Three First Batch 6 2 268 Load Average Density Product Three Second Batch 6 2 269 Load Average Density Product Three Third Batch 6 2 2...

Страница 108: ...92 Printer Message Number One S710 20 293 Printer Message Number Two S711 20 294 Printer Message Number Three S712 20 295 Printer Message Number Four S713 20 296 Printer Message Number Five S714 20 297 HM Classification for the First Batch Run P701 704 80 298 HM Classification for the Second Batch Run P701 704 80 299 HM Classification for the Third Batch Run P701 704 80 300 HM Classification for t...

Страница 109: ... Volume for Product Two Non resettable Total Rev 9 firmware and above 9 4 320 Third User Selected Volume for Product Two Non resettable Total Rev 9 firmware and above 9 4 321 First User Selected Volume for Product Three Non resettable Total Rev 9 firmware and above 9 4 322 Second User Selected Volume for Product Three Non resettable Total Rev 9 firmware and above 9 4 323 Third User Selected Volume...

Страница 110: ...n Flag Third Batch Rev 11 firmware and above 16 1 330 Batch Completion Flag Fourth Batch Rev 11 firmware and above 16 1 331 Batch Completion Flag Fifth Batch Rev 11 firmware and above 16 1 332 Batch Completion Flag Sixth Batch Rev 11 firmware and above 16 1 Note The entry in Program Code 354 will affect the number of transactions saved in local storage ...

Страница 111: ...15 O2 Set at entry 755 232 Paper Out 16 A2 Set at entry 755 232 Cover Open 17 D2 Set at entry 755 232 Deselected 18 B2 Set at entry 755 232 Buffer Overflow 19 P2 Set at entry 755 232 Communications 20 E2 Set at entry 755 232 General Error 21 I2 Set at entry 755 232 No Response 22 H4 Set at entry 755 485 Printer Hardware 23 O4 Set at entry 755 485 Printer Paper Out 24 A4 Set at entry 755 485 Cover ...

Страница 112: ...sity Transducer 42 BP Back Pressure 43 LF Low Flow 44 HF High Flow 45 BH Blend High 46 BL Blend Low 47 OA Overrun 48 PT Pulse Transmission 49 VF Valve Fault 50 PS Pulse Security 51 ZF Zero Flow 52 CF Not Configured Flow 53 UF Unwanted Flow Note 1 Alarms that have the statement Set at entry are programmable in their respective program codes as to whether they are clearable or not clearable in the R...

Страница 113: ...s contained herein are subject to change without notice and any user of said specifications should verify from the manufacturer that the specifications are currently in effect Otherwise the manufacturer assumes no responsibility for the use of specifications which may have been changed and are no longer in effect Contact information is subject to change For the most current contact information vis...

Отзывы: