![FMC Technologies AccuLoad II Скачать руководство пользователя страница 65](http://html.mh-extra.com/html/fmc-technologies/accuload-ii/accuload-ii_programming-workbook_2312619065.webp)
Program
Code
Function
Code Description
Prod 1
Prod 2
Prod 3
Prod 4
60
Issue/Rev.
03
(8/97)
444
High Temperature
Enter:
Four digits. The
Alarm
first digit indicates polarity.
First digit "0" = Positive
First digit "1" = Negative
The last three digits
indicate temperature in whole
degrees. (e.g., 0250 = + 250)
Temperature units are dependent
on entry made in code 441
An entry of 0999 (+999) will
disable this feature.
_____
_____
_____
_____
445
Maintenance Temperature
Enter: Five digits. The
first digit indicates polarity.
First digit "0" = Positive
First digit "1" = Negative
The last four digits
indicate temperature in tenths
of degrees. An entry of -999.9
will disable this feature.
(e.g., 0085.0 = + 85.0)
_____._ _____._ _____._ _____._
446 Temperature
Offset Enter: Three digits. First digit
must be "0" or "1" (0 = positive,
1 = negative). Second and third
digits represent the offset temperature
in tenth degrees (e.g., 10.5 entered
will display at -0.5 degrees offset) __ __.__ __ __.__ __ __.__ __ __.__
447
Low Density Alarm
Enter:
Four digits. The
range is from 0000 to 9999.
Density units are dependent
on entry made in code 445
of the Systems Directory
An entry of 0000 will disable
this
feature.
_____ _____ _____ _____
448
High Density Alarm
Enter:
Four digits. The
range is from 0000 to 9999.
Density units are dependent
on entry made in code 445
of the Systems Directory
An entry of 0000 will disable
this
feature.
_____ _____ _____ _____
449-499
Unassigned at Present