Menu
Values
Description
Protocol COM1 (15_1
5)
AquaCom dialled
Modbus dialled
Comli dialled
Station
number / id
(15_1
)
001–899
In the SCADA system, the station number is a unique number for the
RTU.
Telephone no.
CS/SMS
(15_3
)
Enter the telephone number to the SCADA system or MTC-COM.
GSM modem
Communication using a GSM or telephone modem. (Reference: Observe the limitations for
combinations of modems and their configuration strings as described in the Modem
Configuration manual).
Menu
Values
Description
Communication
COM1
(15_1
0)
GSM/Hayes
predef.
Configure the modem using a PC and select GSM/Hayes predefined.
Speed COM1
(15_1
3)
1200-115200 bps If your modem supports autobauding, set this as high as possible to
get the best communication performances. Otherwise set this value
to the same as the value used in the pre-configuration of the modem.
Parity COM1
(15_1
4)
None, Even or
Odd
Use the same setting as in the communication equipment.
Protocol COM1 (15_1
5)
AquaCom dialled
Modbus dialled
Comli dialled
Station
number / id
(15_1
)
001–899
In the SCADA system, the station number is a unique number for the
RTU.
Telephone no.
CS/SMS
(15_3
)
Enter the telephone number to the SMS recipient, i.e. the personnel.
User modem
Communication using a GSM modem or a telephone modem when you want the RTU to
configure the modem. (Reference: Observe the limitations for combinations of modems
and their configuration strings as described in the Modem Configuration manual).
Menu
Values
Description
Communication COM1
(15_10)
User modem
Modem init 1
(15_11)
Enter the initialization string for the modem. The string can be split in
two. Enter the first piece in the Modem init 1 menu, and the second
piece in the Modem init 2 menu. Note! See “Systems” on page17.
Modem init 2
(15_12)
Speed COM1
(15_13)
1200-115200 bps If your modem supports autobauding, set this as high as possible to
get the best communication performances. Otherwise set this value
to the same as the value used in the initialization string for the
modem.
Configure Communication