Menu
Values
Description
Parity COM1
(15_14)
None, Even or
Odd
Use the same setting as in the communication equipment.
Protocol COM1
(15_15)
AquaCom dialled
Modbus dialled
Comli dialled
Station number / id
(15_1)
001–899
In the SCADA system, the station number is a unique number for the
RTU.
Telephone no. CS/SMS
(15_3)
Enter the telephone number to the SCADA system or MTC-COM.
NOTICE:
If you connect a terminal to the service port in the RTU, you can specify the modem
initialization with the command setcomdata
.
Format: setcomdata <modem init\>
GSM modem and SMS
Communication using a GSM modem. The RTU can be monitored by the SCADA system in
this configuration. However, alarms are sent directly to cell phones as SMS. (Reference:
Observe the limitations for combinations of modems and their configuration strings as
described in the Modem Configuration manual).
Menu
Values
Description
Communication COM1
(15_10)
GSM/Hayes
predef.
Configure the modem using a PC and select GSM/Hayes predefined.
Speed COM1
(15_13)
1200-115200 bps If your modem supports autobauding, set this as high as possible to
get the best communication performances.
Otherwise set this value to the same as the value used in the pre-
configuration of the modem.
Parity COM1
(15_14)
None, Even or Odd Use the same setting as in the communication equipment.
Protocol COM1
(15_15)
AquaCom/SMS
Station name
(15_2)
Enter a name that will be sent in the SMS alarm message.
Telephone no. CS/SMS
(15_3)
Enter the first telephone number to the SMS recipient, i.e. the
personnel.
Telephone no. SMS 2
(15_4)
Telephone number to SMS receiver. The telephone number is
required for alarm handling to more than one SMS receiver.
Only applicable when alarm handling using SMS is selected.
..
..
Telephone no. SMS 5
(15_7)
Telephone number to SMS receiver. The telephone number is
required for alarm handling to more than one SMS receiver.
Only applicable when alarm handling using SMS is selected.
Configure Communication