No.
Menu name
Specification
Description
15_6
Telephone no. SMS 4 WritableCentral System
TextTelephone SMS 4
Telephone number to SMS receiver. The telephone number is
required for alarm handling to more than one SMS receiver.Only
applicable when alarm handling using SMS is selected.
15_7
Telephone no. SMS 5 WritableCentral System
TextTelephone SMS 5
Telephone number to SMS receiver. The telephone number is
required for alarm handling to more than one SMS receiver.Only
applicable when alarm handling using SMS is selected.
15_8
SMS Acknowledge
time min
WritableCentral System TextSMS
Acknowledge time (min)
The time the RTU waits for an acknowledge re-calling or SMS before
sending the SMS alarm to the next telephone number in the list.0 -
disables the function. I.e. the SMS is send directly to all valid
telephone numbers.Only applicable when alarm handling using SMS
is selected.
15_9
SMS P-alarm
Writable Alternative0 = No1 =
YesCentral System TextSMS P-alarm
Send SMS on deactivation of an alarm.Only applicable when alarm
handling using SMS is selected.
15_10
Communication
COM1
Writable Alternative0 = None1 =
Hayes modem2 = GSM/Hayes
predefined3 = RS232 HDX4 =
RS232 FDX5 = User modem6 =
GPRS
Type of communication to use for the communication with the Central
System/SMS.
15_11
Modem init 1
Writable
Initialization string for the modem. (part 1)Applies only when 'User
modem' is selected as communication.
15_12
Modem init 2
Writable
Initialization string for the modem. (part 2)Applies only when 'User
modem' is selected as communication.
15_13
Speed COM1bps
Writable Alternative0 = 12001 =
24002 = 48003 = 96004 =
192005 = 384006 = 576007 =
115200
Speed to use for the communication with the Central System.
15_14
Parity COM1
Writable Alternative0 = None1 =
Even2 = Odd
Parity COM1
15_15
Protocol COM1
Writable Alternative0 = AquaCom
polled fixed1 = AquaCom dialled2
= AquaCom/SMS3 = Modbus
fixed4 = Modbus dialled5 = Comli
fixed6 = Comli dialled7 =
AquaCom unpolled fix
Choice of transmission protocol to use for the communication with the
Central System/SMS.
15_16
RTS delay COM1 ms
Writable
Delay for the RTS signal (request to send) in the communication with
the Central System. Only in choice of RS 232 HDX.
15_17
CS IP address
Writable
The IP address to the Central System.Applies to communication with
GPRS only
15_18
CS IP port
Writable
The IP port of the Central systemApplies to communication with GPRS
only
15_19
Access point name 1 Writable
Access point name. (part 1)Applies to communication with GPRS only
15_20
Access point name 2 Writable
Access point name. (part 2)Applies to communication with GPRS only
15_21
Max buffer sizebytes Writable
Limits the data size when collecting trend.
16
General...
Read only
Menu group for general set-points
16_1
Date and time
Writable
Setting of date and time.
Appendix A: RTU Descriptions
APP 541 User manual
55