No.
Menu name
Specification
Description
4_4
Current factor P2/P4
Writable
Current factor for P2 and P4. Used when P2 and P4 are difference
sizes. Default is 1.0
5
P3 current A
Read only
Measured current for pump 3.
5_1
P3 high current A
WritableCentral System TextP3 high
current (A)
High current alarm limit for pump 3.
5_2
P3 low current A
WritableCentral System TextP3 low
current (A)
Low current alarm limit for pump 3.
6
P4 current A
Read only
Measured current for pump 4.
6_1
P4 high current A
WritableCentral System TextP4 high
current (A)
High current alarm limit for pump 4.
6_2
P4 low current A
WritableCentral System TextP4 low
current (A)
Low current alarm limit for pump 4.
7
Operating data
Read only
Menu group for operating data
7_1
P1 start counter
Writable
Number of start for first pump.
7_2
P1 run hour h:min
Writable
Run hour for first pump.
7_3
P2 start counter
Writable
Number of starts for second pump.
7_4
P2 run hour h:min
Writable
Run hour for second pump.
7_5
P3 start counter
Writable
Number of start for third pump.
7_6
P3 run hour h:min
Writable
Run hour for third pump.
7_7
P4 start counter
Writable
Number of start for fourth pump.
7_8
P4 run hour h:min
Writable
Run hour for fourth pump.
8
Overflow...
Read only
Menu group for overflow
8_1
Weir select
Writable Alternative0 = No1 =
Rectangular
2 = V-notch3 = ManualCentral
System TextWeir select
Chose between different weir types:(0 = No, 1 = Rectangular, 2 = V-
Notch and 3 = Manual)
8_2
Overflow level ft
WritableCentral System
TextOverflow level (ft)
Overflow level alarm limit.0 - disables the function
8_3
Discharge coeff.
WritableCentral System
TextDischarge coefficient
Discharge coefficient used by the rectangular and v-notch calculation
method to calculate overflow flow and overflow volume.
8_4
Overflow range ft
WritableCentral System
TextOverflow range (ft)
Overflow range (in ft) used by the v-notch and manual calculation
method to calculate overflow flow and overflow volume. NOTE! This is
the maximum overflow level relative to the overflow zero level.
8_5
Weir width ft
WritableCentral System TextWeir
width (ft)
Weir width (in ft) used by the rectangular and v-notch calculation
method to calculate overflow flow and overflow volume.
8_6
Overflow segment 1
GPM
WritableCentral System
TextOverflow segment 1 (GPM)
Overflow segment 1 used by the manual calculation method to
calculate overflow flow and overflow volume.
8_7
Overflow segment 2
GPM
WritableCentral System
TextOverflow segment 2 (GPM)
Overflow segment 2 used by the manual calculation method to
calculate overflow flow and overflow volume.
8_8
Overflow segment 3
GPM
WritableCentral System
TextOverflow segment 3 (GPM)
Overflow segment 3 used by the manual calculation method to
calculate overflow flow and overflow volume.
Appendix A: RTU Descriptions
APP 541 User manual
49