Fluke 6500
Users Manual
28
PELV Test
The PELV (Protective Extra Low Voltage) test measures
the voltage on the
PROBE PELV
input when the idle
screen is being displayed.
To perform the PELV test, do the following:
1
STOP
Revert to the idle screen if it is not already
being displayed.
2
Connect the test probe to the tester
PROBE
PELV
terminal and connect the appliance to
a mains supply socket.
3
Apply the test probe to the test point.
4
MEM
Store the test result, if required.
The display can show the following specific information:
PELV 30.0 V
PELV FAIL result, the
threshold (25V) is exceeded.
PELV > 39.9 V
PELV overrange.
230 V
50 Hz
If the PELV threshold is not
exceeded the display shows
the mains voltage and
frequency (PASS result)
Tip:
To store a PELV FAIL result press
MEM
and
GO
.
To store a PELV PASS result press
MEM
and select menu
item “SAVE PELV pass result“.
Содержание 6500
Страница 6: ......