1742/1746/1748
Users Manual
14
Table 5. LED Indicators
LED
Color
Status
Note
Start/Stop
green
No user information or warning available.
Logger power from mains.
No connection errors detected.
amber
Information or warning available.
Possible reasons: Logger power from battery or circuit
connection error detected.
Check the actual status with Energy Analyze Plus if
shows
white
Steady: start/stop
Do not turn off the Logger or remove the USB drive
Flashing: file operation in progress
Time
green
Time synchronization status is OK
off
External time synchronization is not in use
red
Time synchronization source not available
Check the time synchronization source and
configuration of the Logger
Ethernet
green
Ethernet link detected and IP address is assigned
The LED flashes during the IP address assignment
blue
Connection to the Fluke Connect Cloud is established
Fluke Connect
blue
Flashing: Receiving data from all configured FC
modules
Rapid flashing indicates loss of connection to one or all
FC modules
WiFi
green
Steady: Connection to a WiFi access point established
Flashing: Configured WiFi access point is out of range
or the connection can not be established
Check the WiFi access point configuration of the
Logger.
Reduce the distance between the Logger and the WiFi
access point.
Verify that the passphrase is correct.
blue
Connection to the Fluke Connect cloud established
WiFi Hotspot
green
The Logger WiFi Hotspot is active
blue
A client is connected to the WiFi Hotspot