iFlex Probe Specifications
Flexible Current Probe Specifications
i17XX-FLEX1.5KIP
i17XX-FLEX3KIP
i17XX-FLEX6KIP
Measuring range
1 A ac to 150 A ac
10 A ac to 1500 A ac
3 A ac to 300 A ac
30 A ac to 3000 A ac
6 A ac to 600 A ac
60 A ac to 6000 A ac
Weight
170 g (0.38 lb)
170 g (0.38 lb)
190 g (0.42 lb)
Probe Cable Length
610 mm (24 in)
610 mm (24 in)
915 mm (36 in)
Probe Cable Diameter
7.5 mm (0.3 in)
Minimum Bending Radius
38 mm (1.5 in)
Nondestructive current
100 kA (50/60 Hz)
Intrinsic Error at reference condition
±0.7 % of reading [Reference Condition: Environmental: 23 °C
±
5 °C, no external electrical/magnetic field, RH 65 %.
Primary conductor in center position]
Accuracy iFlex
±
(1 % of r 0.02 % of range)
±
(1.5 % of r 0.03 % of range)
Temperature Coefficient over
operating temperature range
0.05 % of reading / °C (0.028 % of reading / °F)
0.1 % of reading / °C (0.056 % of
reading / °F)
Working Voltage
1000 V CAT III, 600 V CAT IV
Output Cable length
2.5 m (8.2 ft)
Probe Cable Material
TPR
Coupling Material
POM + ABS/PC
Output Cable Material
TPR/PVC
Temperature, operating
-25 °C to +70 °C (-13 °F to +158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F)
Temperature, non-operating
-40 °C to +80 °C (-40 °F to +176°F)
Relative humidity, operating
IEC 60721-3-3: 3K6:
-25 °C to +30 °C (-13 °F to +86 °F):
≤
100 %
40 °C (104 °F): 55 %
50 °C (122 °F): 35 %