22

 

 

 
 
 
 

 

 4.OPERATION AND USE 

 

 

 
 

Fan Motor2 Fault

 

 
 

F032

 

1. Motor is in locked-rotor state 
2.The wire connection between 
DC-fan motor module and fan 
motor is in bad contact

 

 

1. 

Change a new fan motor

 

2. 

Check the wire connection and make sure 

they are in good contact

 

Communication Fault

 

(speed control module)

 

E081

 

Speed control module and main 
board communication fail

 

Checkthe communication connection

 

Frequency conversion board fault table:

 

 

Protection/fault

 

Fault

 

display

 

Reason

 

Elimination methods

 

 

Drv1 MOP alarm

 

F01

 

MOP drive alarm

 

Recoveryafter the 150s

 

 

Inverter offline

 

F02

 

Frequency conversion board and main 
board communication failure

 

Checkthe communicationconnection

 

 

IPM protection

 

F03

 

IPM modular protection

 

Recoveryafter the 150s

 

 

Comp. Driver Failure

 

F04

 

Lack of phase, step or drive hardware 

damag

 

Checkthe measuringvoltage check

 

requencyconversion board hardware

 

 

DC Fan Fault

 

F05

 

Motor current feedback open circuit or 
short circuit

 

Checkwhether currentreturn wires 

connectedmotor

 

 

IPM Overcurrent

 

F06

 

IPM Input current is large

 

Checkand adjustthe current 

measurement

 

 

Inv. DC Overvoltage

 

F07

 

DC bus voltage>Dc bus over-voltage 

protection value

 

Checkthe input voltagemeasurement

 

 

Inv. DC Lessvoltage

 

F08

 

DC bus voltage<Dc bus over-voltage 

protection value

 

Checkthe input voltagemeasurement

 

 

Inv. Input Lessvolt.

 

F09

 

The input voltage is low, causing the 

inputcurrent is high

 

Checkthe input voltagemeasurement

 

 

Inv. Input Overvolt.

 

 

F10

 

The input voltage is too high, more than 

outage protection current RMS

 

Checkthe input voltagemeasurement

 

 

Inv. Sampling Volt.

 

 

F11

 

 

The input voltage sampling fault

 

Checkand adjustthe current 

measurement

 

 

Comm. Err DSP-PFC

 

 

F12

 

DSP and PFC connect fault

 

Checkthe communicationconnection

 

 

Input Over Cur.

 

 

F26

 

The equipment load is too large

 

 

PFC fault

 

 

F27

 

The PFC circuit protection

 

Check the PFC switch tube 

short circuit or 

not

 

IPM Over heating

 

 

F15

 

The IPM module is overheat

 

Checkand adjustthe current 

measurement

 

Weak Magnetic Warn

 

 

F16

 

Compressor magnetic force is not 

enough

 

 

Inv. Input Out Phase

 

 

F17

 

The input voltage lost phase

 

Checkand measurethe voltage 

adjustment

 

IPM Sampling Cur.

 

 

F18

 

IPM sampling electricity is fault

 

Checkand adjustthe current 

measurement

 

Inv. Temp. Probe Fail

 

 

F19

 

Sensor is short circuit or open circuit

 

Inspectand replacethe sensor

 

Inverter Overheating

 

 

F20

 

 

The transducer is overheat

 

Checkand adjustthe current 

measurement

 

Inv. Overheating Warn

 

 

F22

 

Transducer temperature is too high

 

Checkand adjustthe current 

measurement

 

Comp. OverCur. Warn

 

 

F23

 

 

Compressor electricity is large

 

The compressorover-current 

protection

 

Input Over Cur. Warn

 

 

F24

 

 

Input current is too large

 

Checkand adjustthe current 

measurement

 

EEPROM Error Warn

 

 

F25

 

MCU error

 

Checkwhether the chip is damaged 

Replacethe chip

 

V15V over/undervoltage fault

 

F28

 

The V15V is overload or undervoltage

 

Check the V15V input voltage in range 

13.5v~16.5v or not

 

Содержание ASTRALPOOL 78572

Страница 1: ...ntended for use by young children 3 08 2017 VIRON RANGE INVERTER HEAT PUMPS Installation Instruction manual INSTALLATION AND OPERATING INSTRUCTIONS I INSTALLATION AND OPERATING INSTRUCTIONS Viron Rang...

Страница 2: ......

Страница 3: ...ol 10 3 4 Swimming Pool Heat Pumps Plumbing 11 3 5 Swimming Pool Heat Pumps Electrical Wiring 12 3 6 Initial Start up of the Unit 12 4 Operation and Use 13 4 1 Color screen wire controller interface i...

Страница 4: ...type unit The indoor unit can be Discretely hidden or semi hidden to suit a luxury house Our heat pump has following characteristics 1 Durable The heat exchanger is made of PVC Titanium tube which ca...

Страница 5: ...pliance shall be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Appliance sha...

Страница 6: ...seful life must be handled separately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6...

Страница 7: ...Power Input kW 0 25 1 5 0 33 1 95 COP 5 68 4 07 5 7 4 1 Power Supply 220 240V 50Hz 220 240V 50Hz Compressor Quantity 1 1 Compressor rotary rotary Fan Number 1 1 Noise 1m dB A 40 50 42 52 Water Connect...

Страница 8: ...eating Power Input kW 0 45 2 64 0 62 3 62 COP 5 56 4 05 5 45 3 98 Power Supply 220 240V 50Hz 220 240V 50Hz Compressor Quantity 1 1 Compressor rotary rotary Fan Number 1 1 Noise dB A 44 53 45 56 Water...

Страница 9: ...Heating Power Input kW 0 75 4 4 0 87 5 1 COP 5 6 4 05 5 63 4 08 Power Supply 220 240V 50Hz 380 415V 3N 50Hz Compressor Quantity 1 1 Compressor rotary rotary Fan Number 2 2 Noise dB A 46 57 48 58 Water...

Страница 10: ...2 The dimensions for Swimming Pool Heat Pump Unit UNIT 78572 78573 unit mm 1046 615 UNIT 78574 78575 unit mm 1161 790 Water outlet 48 3 Water inlet 48 3 470 Water outlet 48 3 Water inlet 48 3 435 110...

Страница 11: ...8 2 SPECIFICATION 2 2 The dimensions for Swimming Pool Heat Pump Unit UNIT 78576 78577 1161 775 unit mm Water outlet 48 3 Water inlet 48 3 470 97 550 1274...

Страница 12: ...ipe have been filled with water 3 Close the valve and start the unit ATTN It is necessary that the water in pipe is higher than the pool surface The schematic diagram is for reference only Please chec...

Страница 13: ...nlet These locations deny the unit of a continuous source of fresh air which reduces it efficiency and may prevent adequate heat delivery 3 3 How Close To Your Pool Normally the pool heat pump is inst...

Страница 14: ...provide easier access should servicing be required To pool PVC COUPLER RECOMMENDED Provided From pump CONDENSATION DRAIN BARB FTG Condensation Since the Heat pump cools down the air about 4 5 water m...

Страница 15: ...ial startup of the Unit NOTE In order for the unit to heat the pool or spa the filter pump must be running to circulate water through the heat exchanger Start up Procedure After installation is comple...

Страница 16: ...lock button Parameter Click this button to view the unit state and the parameter CLOCK Press to set the clock the timer on or timer off Fault display Click to view fault history Silent setting Click t...

Страница 17: ...ure Setting 2 2 1 Mode switch In the main interface click mode button or inlet water temperature setting button interface displays as follows Click the refrigeration mode button automatic mode button...

Страница 18: ...ing Click on the time Settings button interface displays as follows Click the value to set time directly the click confirm button to save the Settings For example setup time the 30 11 2016 16 00 00 in...

Страница 19: ...End gray Click this button to start or end timing start setting function Timing on setting Click to set start time of the timing Timing end button Open red End gray Click this button to start or end t...

Страница 20: ...nd silent timing setting Click the silent setting button and the interface displays as follows 2 4 1 The silent button Click the silent button the unit will enter the silent mode and interface display...

Страница 21: ...Timing silent start time Click this button to set the timing silent start time Timing silent end time Click this button to set the timing silent end time Start time and end time setting value must be...

Страница 22: ...re record themain interface will display static if you check the failurerecord the main interface will displays static Failure record is in reverse order according to the happening time Press the Clea...

Страница 23: ...2 7 1 Temperature recording curve is as follows 2 7 2 Comp Frequency curve Temperature curve automatically updates every one hour and the curve record can be stored for 60 days Start from the latest...

Страница 24: ...w aterfl owa ndw hether waters ystemi sja mmedo rn ot Primary Anti freezing Prot E19 The ambient temp Is low Secondary Anti freezing Prot E29 The ambient temp Is low Inlet and outlet temp too big E06...

Страница 25: ...low causing the inputcurrent is high Checkthe input voltagemeasurement Inv Input Overvolt F10 The input voltage is too high more than outage protection current RMS Checkthe input voltagemeasurement I...

Страница 26: ...85B G GND power 4 OPERATIONAND USE 2 Parameter list Meaning 4 4 Interface drawin 1 Wire control interface diagram and definition 2 Controller interface diagram and definition 12V 5V 0 10V OUT PWM OUT...

Страница 27: ...input temperature input 14 AI DI07 Water output temperature input 15 AI DI08 System fan coil temperature input 16 AI DI09 Ambient temperature input 17 AI DI10 Mode switch input 18 AI DI11 Master slave...

Страница 28: ...25 4 OPERATIONAND USE Controller interface diagram and definition...

Страница 29: ...26 4 OPERATIONAND USE Controller interface diagram and definition...

Страница 30: ...27 4 OPERATIONAND USE Main board of the input and output interface instructions below Number Sign Meaning 22 23 Color line controller communication...

Страница 31: ...g fl am mabl e refrigerants safety c hecks are neces sary to ens ure that the risk of ignition is mini mised For repai r to t he refrigerating sy stem the foll owing pr ec auti ons shall be complied w...

Страница 32: ...ns tal lati ons us ing fl am mabl e refrigerants The charge si ze is in acc ordanc e with the room s ize wi thin whic h the refr igerant containing parts are i nstalled The ventilation machinery and o...

Страница 33: ...w ith parts spec ifi ed by the manufacturer Other parts may resul t in the ignition of refrigerant i n the atmosphere f rom a leak Cabling Check that cabling will not be s ubject to wear corr os ion...

Страница 34: ...gerants are removed saf ely When t ransferring refrigerant into cy linders ens ure that only appropri ate refr igerant recov ery cy linders are employed Ens ure that the correc t number of cy linders...

Страница 35: ...ac cordance with manufac turer s i nstructions h Do not overfill cyli nders N o more than 80 volume l iquid charge i Do not ex ceed the maximum work ing press ur e of the cy linder even temporari ly j...

Страница 36: ...0A 30mA less than 0 1 sec 186 224A 2 95mm2 95mm2 280A 30mA less than 0 1 sec 2 Three phase unit Nameplate maximum current Phase line Earth line MCB Creepage protector Signal line No more than 10A 3 1...

Страница 37: ...0 3 0 5 0 8 1 1 3 1 5 1 8 2 2 3 Temperature R410A 51 3 20 9 4 11 19 24 31 35 39 Temperature R32 52 5 20 9 3 5 10 18 23 29 5 33 3 38 7 Pressure MPa 2 5 2 8 3 3 3 3 5 3 8 4 4 5 5 5 5 Temperature R410A...

Страница 38: ...Note...

Страница 39: ......

Страница 40: ...Code 83900023...

Отзывы: