4.OPERATION AND USE

 

 

4.3  Parameter list and breakdown table 

(1)  Electronic control fault table 

Can be judged according to the remote controller failure code and 
troubleshooting

 

 

Protect/fault

 

Fault

 

display

 

Reason

 

Elimination methods

 

Standby

 

Non

 

 

 

Normal boot

 

 

Non

 

 

 

Inlet Temp. Sensor Fault

 

P01

 

The temp. Sensor is broken 
or short circuit

 

Check or change the temp. Sensor

 

Outlet Temp. Sensor Fault

 

P02

 

The temp. Sensor is broken 
or short circuit

 

Check or change the temp. Sensor

 

Amibent Temp. Sensor Fault

 

P04

 

The temp. Sensor is broken 
or short circuit

 

Check or change the temp. Sensor

 

 

Coil Temp. Sensor Fault

 

 

P05

 

The temp. Sensor is broken 
or short circuit

 

Check or change the temp. Sensor

 

Suction Temp. Sensor Fault

 

P07

 

The temp. Sensor is broken 
or short circuit

 

Check or change the temp. Sensor

 

Discharge Temp. Sensor 
Fault

 

P081

 

The temp. Sensor is broken 
or short circuit

 

Check or change the temp. Sensor

 

High Pressure Prot.

 

E01

 

The high-preesure switch is 

broken

 

Check the pressure switch and cold circuit

 

Low Pressure Prot.

 

E02

 

Low pressure1 protection

 

Check the pressure switch and cold circuit

 

Flow Switch Prot.

 

E03

 

No water/little water in 
water system

 

Check the pipe water flow and water pump

 

Anti-freezing Prot

 

E07

 

Water flow is not enough

 

Checkth ep ipew aterfl owa ndw hether 

waters ystemi sja mmedo rn ot

 

Primary Anti-freezing Prot.

 

E19

 

The ambient temp. Is low

 

 

Secondary Anti-freezing Prot.

 

E29

 

The ambient temp. Is low

 

 

Inlet and outlet temp. too big

 

E06

 

Water flow is not enough

 

and low differential pressure

 

Check the pipe water flow and whether 
water system is jammed or not

 

Low temperature protection

 

Non

 

The environment temp. is low

 

 

Comp. Overcurrent Prot.

 

E051

 

The compressor is overload

 

Check whether the system of the compressor 
running normally

 

Exhaust Air over Temp Prot.

 

P082

 

The compressor is overload

 

Check whether the system of the compressor 
running normally

 

Communication Fault

 

E08

 

Communicat ion failure between 

wire controller and mainboard

 

Check the wire connection between

 

remote wire controller and main board

 

Antifreeze Temp. Sensor Fault

 

P09

 

antifreeze temp sensor is 

broken or short circuited

 

check and replace this temp sensor

 

Waterway Anti-freezing Prot.

 

E05

 

water temp.or ambient temp. is 
too low

 

 

EC fan feedback Fault

 

F051

 

There is something wrong with fan 

motor and fan motor stops running

 

Check whether fan motor is broken or locked or 
not

 

Pressure sensor Fault

 

PP

 

The pressure Sensor is broken

 

Check or change the pressure Sensor or 
pressure

 

 

Fan Motor1 Fault

 

 

F031

 

1. Motor is in locked-rotor state 
2.The wire connection between 
DC-fan motor module and fan 
motor is in bad contact

 

1. 

Change a new fan motor

 

2. 

Check the wire connection and make sure 

they are in good contact

 

Содержание ASTRALPOOL 78572

Страница 1: ...ntended for use by young children 3 08 2017 VIRON RANGE INVERTER HEAT PUMPS Installation Instruction manual INSTALLATION AND OPERATING INSTRUCTIONS I INSTALLATION AND OPERATING INSTRUCTIONS Viron Rang...

Страница 2: ......

Страница 3: ...ol 10 3 4 Swimming Pool Heat Pumps Plumbing 11 3 5 Swimming Pool Heat Pumps Electrical Wiring 12 3 6 Initial Start up of the Unit 12 4 Operation and Use 13 4 1 Color screen wire controller interface i...

Страница 4: ...type unit The indoor unit can be Discretely hidden or semi hidden to suit a luxury house Our heat pump has following characteristics 1 Durable The heat exchanger is made of PVC Titanium tube which ca...

Страница 5: ...pliance shall be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Appliance sha...

Страница 6: ...seful life must be handled separately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6...

Страница 7: ...Power Input kW 0 25 1 5 0 33 1 95 COP 5 68 4 07 5 7 4 1 Power Supply 220 240V 50Hz 220 240V 50Hz Compressor Quantity 1 1 Compressor rotary rotary Fan Number 1 1 Noise 1m dB A 40 50 42 52 Water Connect...

Страница 8: ...eating Power Input kW 0 45 2 64 0 62 3 62 COP 5 56 4 05 5 45 3 98 Power Supply 220 240V 50Hz 220 240V 50Hz Compressor Quantity 1 1 Compressor rotary rotary Fan Number 1 1 Noise dB A 44 53 45 56 Water...

Страница 9: ...Heating Power Input kW 0 75 4 4 0 87 5 1 COP 5 6 4 05 5 63 4 08 Power Supply 220 240V 50Hz 380 415V 3N 50Hz Compressor Quantity 1 1 Compressor rotary rotary Fan Number 2 2 Noise dB A 46 57 48 58 Water...

Страница 10: ...2 The dimensions for Swimming Pool Heat Pump Unit UNIT 78572 78573 unit mm 1046 615 UNIT 78574 78575 unit mm 1161 790 Water outlet 48 3 Water inlet 48 3 470 Water outlet 48 3 Water inlet 48 3 435 110...

Страница 11: ...8 2 SPECIFICATION 2 2 The dimensions for Swimming Pool Heat Pump Unit UNIT 78576 78577 1161 775 unit mm Water outlet 48 3 Water inlet 48 3 470 97 550 1274...

Страница 12: ...ipe have been filled with water 3 Close the valve and start the unit ATTN It is necessary that the water in pipe is higher than the pool surface The schematic diagram is for reference only Please chec...

Страница 13: ...nlet These locations deny the unit of a continuous source of fresh air which reduces it efficiency and may prevent adequate heat delivery 3 3 How Close To Your Pool Normally the pool heat pump is inst...

Страница 14: ...provide easier access should servicing be required To pool PVC COUPLER RECOMMENDED Provided From pump CONDENSATION DRAIN BARB FTG Condensation Since the Heat pump cools down the air about 4 5 water m...

Страница 15: ...ial startup of the Unit NOTE In order for the unit to heat the pool or spa the filter pump must be running to circulate water through the heat exchanger Start up Procedure After installation is comple...

Страница 16: ...lock button Parameter Click this button to view the unit state and the parameter CLOCK Press to set the clock the timer on or timer off Fault display Click to view fault history Silent setting Click t...

Страница 17: ...ure Setting 2 2 1 Mode switch In the main interface click mode button or inlet water temperature setting button interface displays as follows Click the refrigeration mode button automatic mode button...

Страница 18: ...ing Click on the time Settings button interface displays as follows Click the value to set time directly the click confirm button to save the Settings For example setup time the 30 11 2016 16 00 00 in...

Страница 19: ...End gray Click this button to start or end timing start setting function Timing on setting Click to set start time of the timing Timing end button Open red End gray Click this button to start or end t...

Страница 20: ...nd silent timing setting Click the silent setting button and the interface displays as follows 2 4 1 The silent button Click the silent button the unit will enter the silent mode and interface display...

Страница 21: ...Timing silent start time Click this button to set the timing silent start time Timing silent end time Click this button to set the timing silent end time Start time and end time setting value must be...

Страница 22: ...re record themain interface will display static if you check the failurerecord the main interface will displays static Failure record is in reverse order according to the happening time Press the Clea...

Страница 23: ...2 7 1 Temperature recording curve is as follows 2 7 2 Comp Frequency curve Temperature curve automatically updates every one hour and the curve record can be stored for 60 days Start from the latest...

Страница 24: ...w aterfl owa ndw hether waters ystemi sja mmedo rn ot Primary Anti freezing Prot E19 The ambient temp Is low Secondary Anti freezing Prot E29 The ambient temp Is low Inlet and outlet temp too big E06...

Страница 25: ...low causing the inputcurrent is high Checkthe input voltagemeasurement Inv Input Overvolt F10 The input voltage is too high more than outage protection current RMS Checkthe input voltagemeasurement I...

Страница 26: ...85B G GND power 4 OPERATIONAND USE 2 Parameter list Meaning 4 4 Interface drawin 1 Wire control interface diagram and definition 2 Controller interface diagram and definition 12V 5V 0 10V OUT PWM OUT...

Страница 27: ...input temperature input 14 AI DI07 Water output temperature input 15 AI DI08 System fan coil temperature input 16 AI DI09 Ambient temperature input 17 AI DI10 Mode switch input 18 AI DI11 Master slave...

Страница 28: ...25 4 OPERATIONAND USE Controller interface diagram and definition...

Страница 29: ...26 4 OPERATIONAND USE Controller interface diagram and definition...

Страница 30: ...27 4 OPERATIONAND USE Main board of the input and output interface instructions below Number Sign Meaning 22 23 Color line controller communication...

Страница 31: ...g fl am mabl e refrigerants safety c hecks are neces sary to ens ure that the risk of ignition is mini mised For repai r to t he refrigerating sy stem the foll owing pr ec auti ons shall be complied w...

Страница 32: ...ns tal lati ons us ing fl am mabl e refrigerants The charge si ze is in acc ordanc e with the room s ize wi thin whic h the refr igerant containing parts are i nstalled The ventilation machinery and o...

Страница 33: ...w ith parts spec ifi ed by the manufacturer Other parts may resul t in the ignition of refrigerant i n the atmosphere f rom a leak Cabling Check that cabling will not be s ubject to wear corr os ion...

Страница 34: ...gerants are removed saf ely When t ransferring refrigerant into cy linders ens ure that only appropri ate refr igerant recov ery cy linders are employed Ens ure that the correc t number of cy linders...

Страница 35: ...ac cordance with manufac turer s i nstructions h Do not overfill cyli nders N o more than 80 volume l iquid charge i Do not ex ceed the maximum work ing press ur e of the cy linder even temporari ly j...

Страница 36: ...0A 30mA less than 0 1 sec 186 224A 2 95mm2 95mm2 280A 30mA less than 0 1 sec 2 Three phase unit Nameplate maximum current Phase line Earth line MCB Creepage protector Signal line No more than 10A 3 1...

Страница 37: ...0 3 0 5 0 8 1 1 3 1 5 1 8 2 2 3 Temperature R410A 51 3 20 9 4 11 19 24 31 35 39 Temperature R32 52 5 20 9 3 5 10 18 23 29 5 33 3 38 7 Pressure MPa 2 5 2 8 3 3 3 3 5 3 8 4 4 5 5 5 5 Temperature R410A...

Страница 38: ...Note...

Страница 39: ......

Страница 40: ...Code 83900023...

Отзывы: