Model LI1X Universal Process Meter
Instruction Manual
Model LI1X Universal Process Meter
Instruction Manual
SPECIFICATIONS
Except where noted all specifications apply to operation at +25ºC
Basic Meter
INPUTS
Field selectable:
4-20 mA, 0-20 mA, 0-5 V, 1-5 V, 0-10 V.
DISPLAY
Bright, large, 0.56" (14.2mm) high efficiency red
LEDs. 4
1
/
2
extra zero may be switched
on to d/- 19,999(0). Leading zero
blanked.
DECIMAL POINT
Decimal point may be placed in any of the
following positions. 1.9999, 19.999,199.99,
1999.9, 19999 or 199990 with extra zero.
CALIBRATION
4 mA (1 V) input may be set anywhere in range
RANGE
of the meter. 20 mA (5 V) may be set anywhere
in range of the meter above or below 4 mA
input. An Error message will appear if Input 1
signal and Input 2 signal are too close together.
Input
Minimum Difference Between
Range:
Input 1 & Input 2:
0-5 V
0.16 V
0-10 V
0.32 V
4-20 mA
1.60 mA
INPUT
Voltage ranges, greater than 300 Kohms;
IMPEDANCE
current ranges, 100 ohms.
LOOP POWER
(AC Meters only), Isolated 24 VDC ± 5% @ 20
mA regulated. Maximum loop resistance is
1200 ohms. Available for either signal input or
4-20 mA output, but not both.
HOLD READING
Connect terminals H and CM
ACCURACY
±0.05% of calibrated span, ±1 count.
SQUARE ROOT
±0.1% F.S. ± 1 count from 10-100% of flow.
EXTRACTION
LOW FLOW
Any input below the Low-flow Cutoff point will
CUTOFF
result in a display of zero. May be set from 1
count to 100% of full scale, user selectable.
6
11 POINT
Input Range
Minimum Span
LINEARIZATION
Between Inputs
4-20 mA
(1.6 mA / (Number of points –1))
0-5 V
(0.16 V / (Number of points -1))
0-10 V
(0.32 V / (Number of points -1))
e.g. Minimum span for an 11-point, 4-20 mA calibration is 0.16 mA between inputs.
ALARM POINTS
Four, any combination of high or low alarms.
ALARM POINT
0-100% of full scale, user selectable.
DEADBAND
ALARM STATUS
Front panel LED.
INDICATION
LOCKOUT
Jumper J3 restricts modification of
calibration values.
NON-VOLATILE
All programming values are stored in non-
MEMORY
volatile memory for a minimum of ten years if
power is lost. No battery needed.
NORMAL MODE
64 db. at 50-60 Hz.
REJECTION
POWER
AC power, 115 or 230 VAC ±10%, 50/60 Hz, 10 VA.
DC Power, 18-36 VDC; 6 watts maximum.
ENCLOSURE
1/8 DIN, High Impact plastic, UL 94V-0
FRONT PANEL
Type 4X, NEMA 4X, Panel Gasket provided
ENVIRONMENTAL
Operational ambient temperature range: 0
to +60°C. Storage temperature range: -40 to
+85°C. Relative humidity: 0 to 90%
non-condensing.
CONNECTIONS
Removable screw terminal blocks (provided)
accept 22 to 12 AWG wire.
WARRANTY
1 year parts & labor.
UL FILE NUMBER
E193723; 508 Industrial Control Equipment
Options
Relays
RATING
2 or 4 SPDT (form C); rated 2 Amp @ 30 VDC
or 2 Amp @ 250 VAC resistive load;
1
/
14
HP @
125 / 250 VAC for inductive
loads.