FlowLine LI1 Series Скачать руководство пользователя страница 14

Model LI1X Universal Process Meter

Instruction Manual

Model LI1X Universal Process Meter

Instruction Manual

26

Alarm Programming

Overview

The meter is equipped with four alarm points as a standard feature.
Each alarm may be programmed for either a high or low alarm and
for 0-100% deadband. Front panel LEDs indicate alarm status.

Options for two or four relays are available.

To program a high alarm, program the set point above the reset point.
To program a low alarm, program the set point below the reset point.
To program the alarm deadband, set the reset point above or below
the set point by an amount equal to the desired deadband value.

Example:

Alarm 2 is a high alarm that trips at 1500 and has a dead-

band of 100. Alarm 2 set point is set at 1500 and its reset point at
1400.

Setting Alarm Set & Reset Points (

Alars

)

Alarm Set and Reset points are programmed using the 

Five Basic

Digit/Display-setting Instructions described on page 19.

1. Push 

ENTER

and when 

ALArS

appears, push 

ENTER

again. This 

starts a scan of the four alarm set & reset points. The scan 
sequence begins with a flashing display of alarm #1 set point. The 
"1" LED and "S" LED below the display are illuminated to indicate 
the meter is flashing alarm #1 set point value. Program the desired
value for alarm #1 set point using the 

Five Basic Digit/Display-

setting Instructions described on page 19.

2. After Alarm #1 set point has been programmed, the meter displays

Alarm #1 reset point, as indicated by the "1" LED and "R" LED 
below the display. Program the desired value for alarm #1 reset 
point using the 

Five Basic Digit/Display-setting Instructions

described on page 19.

3. Program the remaining alarm set and reset points in a similar 

fashion.

4. When alarm programming is complete the meter will display the 

process input signal and the front panel LEDs will indicate alarm 
status.

Isolated 4-20 mA Transmitter Output Programming (

ovtpvt

)

The Isolated 4-20 mA Transmitter Output option can be programmed
without a calibrator. This option can be calibrated so that a 4 mA out-
put is produced for any number displayed by the meter. The 20 mA
output may be programmed to correspond to any number that is at
least 501 counts greater or smaller than the number corresponding to
4 mA. (Ex. 4 mA = 0, 20 mA = 501 or -501) If the span between 4 and
20 mA is less than 501 counts, an 

error

message will appear and the

previously programmed values will be retained in memory until a
new set of values is accepted.

Setting 4 mA Output Value

1. Push 

ENTER

, when 

ovtPvt

appears push 

ENTER

again.

2. All digits flash for 3 seconds, a green LED labeled "4" illuminates 

indicating the flashing display is the value at which the meter will 
produce a 4 mA output. Program desired value per 

Five Basic 

Digit/Display-setting Instructions on page 19.

Setting 20 mA Output Value

1. When 

ENTER

is pushed to complete the programming for 4 mA 

output, the green LED labeled "20" illuminates indicating the 
flashing display is the value at which the meter will produce a 20 
mA output.

2. Program desired value per 

Five Basic Digit/Display-setting 

Instructions on page 19.

3. An Error message will be displayed if the 4-20 mA output span is 

smaller than 501 counts.

Programming Confirmation

The values that have been programmed to produce the 4 & 20 mA
outputs can be quickly checked to make sure they are the desired val-
ues. To do this, enter the 

ovtPvt

routine by pushing 

ENTER

and then

pushing 

ENTER

again when 

ovtPvt

appears.

The green "4" LED illuminates indicating the meter is displaying the
value at which it will produce a 4 mA output. Confirm that this is the
desired value. Push 

ENTER 

(within 3 seconds) before the entire dis-

play stops flashing and the green "20" LED illuminates indicating the
meter is displaying the value at which it will produce a 20 mA output.
Confirm that this is the desired value. Push 

ENTER

(within 3 seconds)

before the entire display stops flashing and the meter returns to indi-
cation mode.

27

Spec Tech Industrial Electric

               www.spectechind.com

888-773-2832

Spec Tech Industrial Electric

               www.spectechind.com

888-773-2832

Содержание LI1 Series

Страница 1: ...Display to 199 990 11 Point Linearization Square Root Extraction with Low flow Cutoff 41 2 Digit Extra Zero Type NEMA 4X Front Panel 2 or 4 Relays 4 20 mA Output Options Lockout Feature Non volatile M...

Страница 2: ...nt dECPt 21 Select Linear Input L or S 21 Select Number Of Calibration Points no PtS 21 General Calibration Scaling Instructions 22 Scale Using Internal Calibration I Cal 22 Calibrate Using an Externa...

Страница 3: ...rs valves etc It is recommended to use this meter in a fail safe system that accommodates the possibility of meter failure or power failure WARNING Hazardous voltages exist within enclosure Installati...

Страница 4: ...Cutoff point will CUTOFF result in a display of zero May be set from 1 count to 100 of full scale user selectable 6 11 POINT Input Range Minimum Span LINEARIZATION Between Inputs 4 20 mA 1 6 mA Number...

Страница 5: ...POWER SUPPLY OUTPUT LOOP Power supply Min loop Max loop RESISTANCE resistance resistance 24 VDC 10 ohms 600 ohms 35 VDC external 600 ohms 1000 ohms 8 Model LI1X Universal Process Meter Instruction Ma...

Страница 6: ...on Manual 11 10 SETUP AND PROGRAMMING Power Signal External Functions Options Connections Disconnect power to the meter before making any connections Do not connect power or earth ground to any unused...

Страница 7: ...AC 4 20 mA Transmitter 3 2 1 Signal Input Selection Array Lockout Jumper L L P P S S C H A O L C M D K Signal Input Selection Array Loop Power Supply 4 20 mA Transmitter AC 3 2 1 Lockout Jumper L L P...

Страница 8: ...Powered Meters Power Signal External Functions Figure 6 Transmitter and Meter Powered from Same DC Power Supply Figure 7 Transmitter and Meter Powered from Separate DC Power Supplies 14 15 24 VDC Powe...

Страница 9: ...tely programmed using just the ENTER button The general method behind SBS is to push ENTER when the meter reads the desired value This value may be a menu title the entire display or just a single dig...

Страница 10: ...ore it starts to scroll to accept it 4 If a flashing digit is not OK or if ENTER was not pushed in time to accept it wait for the digit to scroll and push ENTER when OK 5 Digits will scroll until ENTE...

Страница 11: ...is necessary to first complete an Initial Calibration see Initial Calibration with External Source If Needed on page 20 Scale or Calibrate the Meter To select a Calibration Method apply power with AC...

Страница 12: ...uction Manual 22 23 General Calibration Scaling Instructions Calibration is performed from the front panel using the ENTER but ton It does not require any tools or disassembly of the meter A calibrate...

Страница 13: ...ero flow rate usually zero the high flow rate and the Low flow Cutoff point To program the meter for square root extraction push ENTER When L or S appears push ENTER again The meter will flash L or S...

Страница 14: ...put option can be programmed without a calibrator This option can be calibrated so that a 4 mA out put is produced for any number displayed by the meter The 20 mA output may be programmed to correspon...

Страница 15: ...ct on the alarm status LEDs Automatic Manual Reset Programming There are two ways to reset the relays 1 Automatically when the signal passes through the reset point 2 Automatically manually via the fr...

Страница 16: ...ng inductive loads However installing Resistor Capacitor RC Networks improves this performance and prolongs the life of the meter s relay contacts This suppression can be obtained with RC networks ass...

Страница 17: ...ur screws and washers 11 Reassemble front covers and install connectors Figure 18 Removing Front Bezel Model LI1X Universal Process Meter Instruction Manual Figure 19 Internal View of Meter Option Car...

Страница 18: ...ut 7 set point display 7 Input 8 set point display 8 Input 9 set point display 9 Input 10 set point display 10 Input 11 set point display 11 Alarms Alarm 1 set point reset point Alarm 2 set point rese...

Страница 19: ...truction Manual LIM690FL Rev B 6 99 10500 Humbolt Street Los Alamitos CA 90720 Tel 562 598 3015 Fax 562 431 8507 Spec Tech Industrial Electric www spectechind com 888 773 2832 Spec Tech Industrial Ele...

Отзывы: