OPTION CARD INSTALLATION
Options may be ordered installed at the factory or as separate items.
Instructions
1
.
Disconnect power to the meter.
2.
Remove all connectors from the back of the meter.
3.
Remove the Front Cover, simply pry the top and pull it back.
4.
Remove the two screws that retain the PCB.
5.
Slide the Main PCB out of case (set it down with display facing
forward).
6.
Lay the Option PCB to the right of the Main PCB.
7.
Connect flexible cable connector CT1 to J5 connector on Main
PCB.
8.
Check that all the pins are properly seated in the connector.
9.
Fold the option board over onto the Main PCB.
10. Slide the two PCBs into the case and secure with four screws and
washers.
11. Reassemble front covers and install connectors.
Figure 18: Removing Front Bezel
Model LI1X Universal Process Meter
Instruction Manual
Figure 19: Internal View of Meter (Option Card Socket)
MOUNTING DIMENSIONS
Figure 20: Mounting Dimensions
Notes:
1. Panel cutout required: 1.772" X 3.622" (45 mm x 92 mm) 1/8 DIN
2. Panel thickness: 0.125" - 0.250" (3.17 mm - 6.34 mm)
3. Allow 6 inches (152 mm) behind the panel
4. Weight 16 oz. (454 g)
33
Latch
Snap-off Cover
Latch Plate
Notch
Retaining Screws and Washers
(2 plcs.)
Config. Jumpers
Transformer
Socket for
Option Card
Display Board
Internal View of Meter for
Locating Option Connector
Panel Thickness –
.125"-.250" (3.17mm-6.34mm)
6" (152mm)
SIDE VIEW
FRONT VIEW
4.25" (108mm)
4.30" (109mm) Installed
4.83" (123mm) Req'd for Inst.
2.30"
(59mm)
.575"
(14.6mm)
32