Low Voltage DC Loads
Figure 17: Low Voltage DC Loads
Use a diode with a reverse breakdown voltage two to three times the
circuit voltage and forward current at least as large as the load cur-
rent.
RC Networks
Suppressors are available from FLOWLINE and should be applied to
each relay that switches an inductive load.
Lockout Jumper
Once the meter has been completely programmed, a lockout jumper
can be installed to restrict further modification to the meter. This
jumper is located at the rear of the instrument and is labeled J3.
When
ENTER
is pushed with the lockout jumper in place, only
ALArS
and
ovtPvt
routines are displayed. These routines may be entered to
view their settings, but the settings may not be altered.
SWITCHING INDUCTIVE LOADS
The meter has the ability to suppress electrical noise generated by
switching inductive loads. However, installing Resistor Capacitor (RC)
Networks improves this performance and prolongs the life of the
meter's relay contacts. This suppression can be obtained with RC
networks assembled by the user or purchased as a complete assembly.
Refer to the following circuits for RC network assembly and installation:
AC & DC Loads
Figure 16: AC & DC Loads
Choose R and C as follows:
R: 0.5 to 1 ohm for each volt across the contacts
C: 0.5 to 1 microfarad for each 1 A through closed contacts
Notes:
1. Use capacitors rated for 240 VAC.
2. Snubbers may affect load release time of solenoid loads, check to
confirm proper operation.
3. Install the RC network right at the meter's relay screw terminals. An RC
network may also be installed across the load.
Model LI1X Universal Process Meter
Instruction Manual
Model LI1X Universal Process Meter
Instruction Manual