80
MN301905 Rev A
Appendix (continued)
Step Ten
RESET
This function allows the configuration (basic or factory)
settings and memory (peak values measured) to be
reset. Below are the three reset types:
Basic Reset – Used to reset the basic configuration
settings, process adjustment settings, and peak level
values in memory (retaining any advanced adjustment
settings).
Factory Settings – Used to reset ALL settings and memory to factory default.
Note: Only perform the Factory Setting after consulting with a Flowline Representative. Make sure to record
all of your settings including the Distance Adjustment (4.9) setting before performing the Factory Reset.
Peak Values Measured – Used to reset the minimum and maximum peak level values in memory (retaining
any basic configuration, process adjustment and advanced adjustment settings).
UNITS OF MEASUREMENT
This function allows the units of measurement to be changed between Metric and
English system units.
LANGUAGE
This function sets the display language.
Default is English.
OPERATIONAL MODE
This function allows for the sensor’s digital address to
be changed from the Standard mode with an address of
0 to a Multidrop mode where the address can be set
from 1 to 15.
Default is Address 0.
Note: This function
should only be performed by a trained technician.
COPY SENSOR DATA
This function allows configuration and memory data to
be uploaded to or downloaded from the sensor.
Note:
This function should only be performed by a trained
technician.