Appendix (continued)
Step Ten
SCALING
This function sets the span values for 0% and 100% as an alternative method
of adjusting the
Empty Configuration
and
Full Configuration
settings.
Defaults are 0% and 100%
.
RANGE
This function sets the maximum range that the sensor can measure which is
typically the distance from the bottom of the sensor to the empty tank bottom.
Default is the maximum range of the sensor
.
DEAD BAND
This function sets the dead band or the minimum distance that the sensor will
measure.
Default is 12” (30cm).
Minimum setting is 2” from the bottom of
the antenna.
Consult factory when setting the dead band less than the factory
setting
.
SENSOR ID
This function sets an 11-digit identification code. The setting can use
alphanumeric values from A to Z and 0 to 9.
Default is the sensor’s 4-digit
Series number
.