Appendix (continued)
Step Ten
DIAGNOSTICS MENU
This menu provides information about the operational status of the sensor and diagnostic tools. The below
tree shows the 5 function settings and how to navigate between them.
PEAK VALUES
This function displays the lowest and highest level height distances (d) that the
sensor has measured during operation. To reset these values, use the Reset >>
Peak Measured Values option found under the Service Menu.
MEASUREMENT STATUS
This function displays the signal strength (dB) of the echo returns (Measurement
Reliability) and the operational status of the sensor (Sensor Status). A signal
strength of 10dB or higher is acceptable. Anything under 10dB is considered a
weak signal. The cause of a weak signal is often obstructions within the beam path
or a poor installation.
Sensor status confirms whether the sensor is operating as expected. If normal, the
descriptor will be OK. If abnormal, the descriptor will be one of the following error
codes:
E11
– Insufficient power
E12
– Sensor open circuit
E14
– Weak return echo
E15
– ROM
error
E17
– ROM error