Technical Guide
CN-IC1-12
Title
:
i-Controller Visograph Navigation REV.201.05
EXTERNAL
27
1-5JULY2021
Damper Test Mode
Damper Test Mode is used to open dampers to the user
specified position.
Figure 66. Damper Test Mode screen
Condenser Fan Test Mode
The Condenser Fan Test Mode is used to verify condenser
fan operation. NOTE: Some condenser fans are wired
directly to compressor outputs
–
this mode will activate
the associated compressor to activate the chosen
condenser fan.
Figure 67. Condenser Fan Test Mode screen
Heat Test Mode
Figure 68.Heat Test Modes screen
Full capacity heat test mode turns ON all heating stages.
Staged heat test mode is used to turn ON each stage of
heat individually.
Reheat/ Reclaim Test
Energizes the Reheat/ Reclaim output. During a Reheat
test, heat will only be available if the compressor is