Figure 85. Sensor Settings screen 1
T1: Go to Field Tech Menu
T4: Scroll Up/Increase Value
T5: Enter (Select and Set Value)
T6: Scroll Down/Decrease Value
T7: Go to Previous Page
T8: Go to Next Page
Figure 86. Sensor Settings screen 2
Figure 87. Sensor Settings screen 3
Set Damper Positions and Exhaust Fan
Interlocks
The “Set Damper Position and Exhaust Interlocks” screen
is used to set the min/max percentage of the return air
damper, the min position for the bypass damper, and
additional outdoor air damper opening for exhaust fan
interlocks. The Exhaust fan interlock options will not be
visible if none are available. If exhaust fan interlocks exist
on the
Flō
unit, only the number of interlocks for the unit
will appear on the screen. An asterisk will appear to the
right of the damper percentage if the damper position is
in override.
To adjust the outdoor damper opening or exhaust
interlock opening:
1.
Using the
and
buttons (T4 and T6,
respectively) navigate to the value that you wish to
change.
2.
Once the value is highlighted, press the
(T5)
button and the value should blink.
3.
Using the
and
buttons increase and
decrease the value as desired.
4.
Once the desired value has been reached press the
button to set the value.
5.
Use the
(T7) and
(T8) buttons to navigate
to the second page if more than 4 exhaust fan
interlocks exist on the unit.
6.
Repeat steps 1-4 until all desired values have been
updated.
7.
Once all changes have been completed, press the
(T1) to return to the Field Tech Options
Menu.