The firmware version
of each inverter is not
the same.
1.
2.
Update all inverter firmware to the same version.
Check the version of each inverter via LCD setting and make sure the
CPU versions are same. If not, please contact your instraller to provide
the firmware to update.
3.
After updating, if the problem still remains, please contact your installer.
72
The output current of
each inverter is
different.
1.
2.
Check if sharing cables are connected well and restart the inverter.
If the problem remains, please contact your installer.
80
CAN data loss
1.
2.
Check if communication cables are connected well and restart the
inverter.
If the problem remains, please contact your installer.
81
Host data loss
82
Synchronization data
loss
83
The battery voltage of
each inverter is not the
same.
1.
2.
Make sure all inverters share same groups of batteries together.
Remove all loads and disconnect AC input and PV input. Then, check
battery voltage of all inverters. If the values from all inverters are close,
please check if all battery cables are the same length and same material
type. Otherwise, please contact your installer to provide SOP to calibrate
battery voltage of each inverter.
3.
If the problem still remains, please contact your installer.
84
AC input voltage and
frequency are detected
different.
1.
2.
Check the utility wiring conncetion and restart the inverter.
Make sure utility starts up at same time. If there are breakers installed
between utility and inverters, please be sure all breakers can be turned
on AC input at same time.
3.
If the problem remains, please contact your installer.
85
AC output current
unbalance
1.
2.
Restart the inverter.
Remove some excessive loads and re-check load information from LCD
of inverters. If the values are different, please check if AC input and
output cables are in the same length and material type.
3.
If the problem remains, please contact your installer.
86
AC output mode
setting is different.
1.
2.
Switch off the inverter and check LCD setting #28.
For parallel system in single phase, make sure no 3P1, 3P2 or 3P3 is
set on #28.
For upporting three-phase system, make sure no “PAL” is set on #28.
3.
If the problem remains, please contact your installer.
Appendix II: Approximate Back-up Time Table
Model
Load (VA)
Backup Time @ 24Vdc 100Ah (min)
Backup Time @ 24Vdc 200Ah (min)
3KVA
300
449
1100
600
222
525
900
124
303
1200
95
227
1500
68
164
1800
56
126
2100
48
108