FlinSlim Edge Solar Hybrid Inverter with In-Built Stabilizer
FLIN ENERGY
18
19
Auto return to default
display screen
Return to default
display screen
(default)
If selected, no matter how users
switch display screen, it will
automatically return to default display
screen (Input voltage /output voltage)
after no button is pressed for 1
minute.
Stay at latest screen
If selected, the display screen will stay
at latest screen user finally switches.
20
Backlight control
Backlight on
(default)
Backlight off
22
Beeps while primary source
is interrupted
Alarm on (default)
Alarm off
23
Overload bypass:
When enabled, the unit will
transfer to line mode if
overload occurs in battery
mode.
Bypass disable
(default)
Bypass enable
25
Record Fault code
Record enable
Record disable (default)
26
Bulk charging voltage (C.V
voltage)
24V model default setting: 28.2V
48V model default setting: 56.4V
If self-defined is selected in program 5, this program can be set
up. Setting range is from 24.0V to 29.2V for 24V model and
48.0V to 58.4V for 48V model. Increment of each click is 0.1V.
27
Floating charging voltage
24V model default to 27.0V
48V model default setting: 54.0V
If self-defined is selected in program 5, this program can be set
up. Setting range is from 24.0V to 29.2V for 24V model,
48.0V to 58.4V for 48V model. Increment of each click is 0.1V.
29
Low DC cut-off voltage
24V model default setting: 21.0V
48V model default setting: 42.0V