2. Operation (Restoration & Discharge)
MANUAL MODE – RESTORATION PROCESS
Manual Mode : Restoration is performed with Constant Current and Constant Voltage form,
•
This Graph shows Restoration
Step 1
Constant Current
Step 2
Constant Voltage
Explanation for the Graph of Restoration
①
[Step 1] Keep Restoring with Set Ampere until it reaches Set Voltage
②
[Step 2] When it reaches Set Voltage, it will maintain Set Voltage by controlling Active
Ampere until Set Time.
③
This process is same as Pulse 2 in Program Mode.
Xtender checks temperature of Battery every five(5) minutes and it will decrease Active Ampere by
10% when temperature reaches over 50
℃
(adjustable in Setup menu)
Install temperature sensor connected with back side of Xtender unit on the top or good place on
batteries to check the temperature of battery. If connecting to a large multiple cell battery place the
temperature sensor over the middle cell.
Don’t let temperature sensor get exposed to the electrolyte acid solution to prevent damage to the
sensor.