COMMISSIONING
Wind. Description
Default
Own
No.
value
setting
36
Set time/activity Saturday
36a Change-over time 1 Saturday
8:00
36b Activity 1 Saturday
Standard flow
36c Change-over time 2 Saturday
17:00
36d Activity 2 Saturday
Reduced flow
37
Set time/activity Sunday
37a Change-over time 1 Sunday
8:00
37b Activity 1 Sunday
Reduced flow
37c Change-over time 2 Sunday
17:00
37d Activity 2 Sunday
Reduced flow
Annual rhythm
40
Main menu Set annual rhythm
41
Set time/activity period 1
41a Activity period 1
No effect
41b Starting time period 1
01-01
41c Stopping time period 1
01-01
42
Set time/activity period 2
42a Activity period 2
No effect
42b Starting time period 2
01-01
42c Stopping time period 2
01-01
43
Set time/activity period 3
43a Activity period 3
No effect
43b Starting time period 3
01-01
43c Stopping time period 3
01-01
44
Set time/activity period 4
44a Activity period 4
No effect
44b Starting time period 4
01-01
44c Stopping time period 4
01-01
45
Set time/activity period 5
45a Activity period 5
No effect
45b Starting time period 5
01-01
45c
Stopping time period 5
01-01
Clock
50
Main menu Set clock
51
Set year
Current year
52
Set date
Current date
53
Set weekday
Current day
54
Set time
Current time
Summer night-time cooling
60
Main menu Set summer night-time cooling
61
Summer night-time cooling
No
62
Exhaust air temp. - outd.temp.
5,0
o
C
63
Exhaust air temp. greater than
22,0
o
C
64
Temp.reduction in room
2,0
o
C
65
Outdoor temp. not below
12,0
o
C
Test / Calibration / Default values
70
Main menu Test/Default
71
Self-test
72
Calibration
73
Set default values
75
Electric coil installed
No
76
Cooling coil installed
No
77
Program version
1.0
Language
80
Main menu Select language
81
Language
English
Procedure - setting
Wind. Description
Default
Own
No.
value
setting
Air flow
10
Main menu Set desired value
11
Standard flow: exhaust air
200 l/s
12
Reduced flow: exhaust air
100 l/s
13
Ratio: Supply/Exhaust
1.0
Temperature regulation
14
Temperature regulation
Room regul.
15
Set room temperature
15a Room temperature (room regul.)
20
o
C
15b
Loweat supply air temp. (room reg.)
19°C
15c
Supply air temp (supply air regul.)
19°C
16
Set supply air regulation parameters
146a Temp.reg. P-band
1,0
o
C
16b
Temp.reg. I-time
5,0 Min.
16c Compensation factor k1
4,2
16d
Compensation factor k2
3,2
16e Compensation factor k3
0,3
Actual values
20
Main menu Read actual values
Value read off
21
Temperature, exhaust air (
o
C)
"
22
Temperautre, supply air (
o
C)
"
23
Air flow, exhaust air (l/a)
"
24
Air flow, supply air (l/a)
"
25
Heat exch. rotor speed(U/min)
"
26
Electric coil output (%)
"
27
Control for cooling coil (V)
"
Weekly rhythm
30
Main menu Set weekly rhythm
31
Set time/activity Monday
31a
Change-over time 1 Monday
8:00
31b Activity 1 Monday
Standard flow
31c
Change-over time 2 Monday
17:00
31d Activity 2 Monday
Reduced flow
32
Set time/activity Tuesday
32a Change-over time 1 Tuesday
8:00
32b Activity 1 Tuesday
Standard flow
32c Change-over time 2 Tuesday
17:00
32d Activity 2 Tuesday
Reduced flow
33
Set time/activity Wednesday
33a Change-over time 1 Wednesday
8:00
33b Activity 1 Wednesday
Standard flow
33c Change-over time 2 Wednesday
17:00
33d Activity 2 Wednesday
Reduced flow
34
Set time/activity Thursday
34a Change-over time 1 Thursday
8:00
34b Activity 1 Thursday
Standard flow
34c Change-over time Thursday
17:00
34d Activity 2 Thursday
Reduced flow
35
Set time/activity Friday
35a Change-over time 1 Friday
8:00
35b Activity 1 Friday
Standard flow
35c Change-over time 2 Friday
17:00
35d Activity 2 Friday
Reduced flow
List of parameters