background image

Fläkt Woods 

8061 GB  2009.05 

19 

Specifications are subject to alteration without further notice.

RoomMaster ABR-2 

COMMISSIONING

 Wind.  Description 

Default 

Own

  No.   

value 

setting

 36  

Set time/activity Saturday

 36a   Change-over time 1 Saturday 

8:00

 36b   Activity 1 Saturday 

Standard flow

 36c   Change-over time 2 Saturday 

17:00

 36d   Activity 2 Saturday 

Reduced flow

 37  

Set time/activity Sunday

 37a   Change-over time 1 Sunday 

8:00

 37b   Activity 1 Sunday 

Reduced flow

 37c   Change-over time 2 Sunday 

17:00

 37d   Activity 2 Sunday 

Reduced flow

Annual rhythm

 40  

Main menu  Set annual rhythm

 41  

Set time/activity period 1 

 41a   Activity period 1 

No effect

 41b   Starting time period 1 

01-01

 41c   Stopping time period 1 

01-01

 42  

Set time/activity period 2

 42a   Activity period 2 

No effect

 42b   Starting time period 2 

01-01

 42c   Stopping time period 2 

01-01

 43  

Set time/activity period 3

 43a   Activity period 3 

No effect

 43b   Starting time period 3 

01-01

 43c   Stopping time period 3 

01-01

 44  

Set time/activity period 4

 44a   Activity period  4 

No effect

 44b   Starting time period 4 

01-01

 44c   Stopping time period 4 

01-01

 45  

Set time/activity period 5

 45a   Activity period  5 

No effect

 45b   Starting time period 5 

01-01

 45c 

Stopping time period 5 

01-01

Clock

 50  

Main menu  Set clock

 51  

Set year 

Current year

 52  

Set date 

Current date

 53  

Set weekday 

Current day

 54  

Set time 

Current time

Summer night-time cooling

 60  

Main menu Set summer night-time cooling

 61  

Summer night-time cooling 

No

 62  

Exhaust air temp. - outd.temp. 

5,0

o

C

 63  

Exhaust air temp. greater than 

22,0

o

C

 64  

Temp.reduction in room 

2,0

o

C

 65  

Outdoor temp. not below 

12,0

o

C

Test / Calibration / Default values

 70  

Main menu Test/Default

 71  

Self-test

 72  

Calibration

 73  

Set default values

 75 

Electric coil installed 

No

 76  

Cooling coil installed 

No

 77 

Program version 

1.0

Language

 80  

Main menu  Select language

 81  

Language 

English

Procedure - setting

 Wind.  Description 

Default 

Own

  No.   

value 

setting

Air flow

 10  

Main menu  Set desired value 

 11 

Standard flow: exhaust air 

200 l/s

 12  

Reduced flow: exhaust air 

100 l/s

13 

Ratio: Supply/Exhaust 

1.0

Temperature regulation

 14  

Temperature regulation 

Room regul.

15 

Set room temperature

 15a   Room temperature (room regul.) 

20

o

C

15b 

Loweat supply air temp. (room reg.) 

19°C

15c 

Supply air temp (supply air regul.) 

19°C

16 

Set supply air regulation parameters

 146a  Temp.reg.  P-band 

1,0

o

C

 16b 

Temp.reg. I-time 

5,0 Min.

 16c   Compensation factor k1 

4,2

 16d 

Compensation factor k2 

3,2

 16e   Compensation factor k3 

0,3

Actual values

 20  

Main menu  Read actual values 

Value read off

 21  

Temperature, exhaust air (

o

C) 

"

 22  

Temperautre, supply air (

o

C) 

"

 23  

Air flow, exhaust air  (l/a) 

"

 24 

Air flow, supply air  (l/a) 

"

 25  

Heat exch. rotor speed(U/min) 

"

 26  

Electric coil output  (%) 

"

 27  

Control for cooling coil (V) 

"

Weekly rhythm

 30  

Main menu  Set weekly rhythm

 31 

Set time/activity Monday

 31a 

Change-over time 1 Monday 

8:00

 31b   Activity 1 Monday  

Standard flow

 31c 

Change-over time 2 Monday 

17:00

 31d   Activity 2 Monday 

Reduced flow

 32  

Set time/activity Tuesday

 32a   Change-over time 1 Tuesday 

8:00

 32b   Activity 1 Tuesday 

Standard flow

 32c   Change-over time 2 Tuesday 

17:00

 32d   Activity 2 Tuesday 

Reduced flow

 33  

Set time/activity Wednesday

 33a   Change-over time 1 Wednesday 

8:00

 33b   Activity 1 Wednesday 

Standard flow

 33c   Change-over time 2 Wednesday 

17:00

 33d   Activity 2 Wednesday 

Reduced flow

 34  

Set time/activity Thursday

 34a   Change-over time 1 Thursday 

8:00

 34b   Activity 1 Thursday 

Standard flow

 34c   Change-over time Thursday 

17:00

 34d   Activity 2 Thursday 

Reduced flow

 35  

Set time/activity Friday

 35a   Change-over time 1 Friday 

8:00

 35b   Activity 1 Friday 

Standard flow

 35c   Change-over time 2 Friday 

17:00

 35d   Activity 2 Friday 

Reduced flow

List of parameters

Содержание RoomMaster ABR-2

Страница 1: ...RoomMaster ABR 2 Commissioning...

Страница 2: ...PROCEDURE SETTING Setting of temperature regulation of desired value for temperature 7 Setting of exhaust air flow standard and reduced flow and supply air exhaust air flow ratio 8 Reading actual valu...

Страница 3: ...ed at any time for a new operating status by pressing the appropriate operating mode key Five setting keys are provided to set and read the air flows and temperatures etc to increase and reduce the va...

Страница 4: ...ng Fig 21 10 50 20 40 80 60 30 70 11 14 12 17 13 15 12d Huvudmeny Undermeny 1 Undermeny 2 12e 12b 12a 12c 16 Function of setting keys Sub menu 2 Sub menu 1 Main menu Fig 22 Main menu and sub menu Next...

Страница 5: ...which interrupts calibration before it is com plete the calibration procedure must be repeated Unit self test Self test is intended to be used for checking important components in the unit during serv...

Страница 6: ...ing has been left lying inside the unit 3 Push the plug into an earthed wall socket 4 Activate the setting keys 3 5 Choice of language in text window 14 81 6 Perform setting of Standard flow and Reduc...

Страница 7: ...s the key Window 15 is displayed 6 Press the key Window 15a is displayed 10 0 30 0 C 20 0 C 7 Change to the desired value with and confirm with cursor stops flashing 8 Press the key Window 15b is disp...

Страница 8: ...is displayed 2 Press the key Window 20 is displayed 3 Press the key Window 21 is displayed current exhaust air temperature can be read 4 Press the key Window 22 is displayed current supply air temper...

Страница 9: ...Window 31d is displayed Standard flow Reduced flow Stop 11 Change to desired activity 2 with and confirm with cursor stops flashing 12 Press the key Window 31 is displayed 13 Press the key Window 32...

Страница 10: ...firm with cursor stops flashing 10 Press the key Window 41 is displayed 11 Press the key Window 42 is displayed 12 Repeat the above procedure to set the desired operating times and operating modes for...

Страница 11: ...irm with cursor stops flashing 5 Press the key Window 52 is displayed Month Day 6 Set the date with and confirm with cursor stops flashing 7 Press the key Window 53 is displayed Weekday 8 Set the week...

Страница 12: ...temperature with and confirm with cursor stops flashing 7 Press the key Window 63 is displayed 16 0 32 0 C 22 0 C 8 Change to the desired temperature with and confirm with cursor stops flashing 9 Pre...

Страница 13: ...prox 5 minutes Self test of unit Window 71a 1 Press the keys at the same time for approx 5 seconds Window 10 is displayed 2 Press the key 6 times until window 70 is displayed 3 Press the key Window 71...

Страница 14: ...00 34b Activity 1 Thursday Standard flow 34c Change over time 2 Thursday 17 00 34d Activity 2 Thursday Reduced flow Window Description Default value No 35a Change over time 1 Friday 8 00 Weekly rhythm...

Страница 15: ...the operating window Activation of electric coil and cooling coil 1 Press the keys at the same time for approx 5 seconds Window 10 is displayed 2 Press the key 6 times until window 70 is displayed 3...

Страница 16: ...key to confirm Press the key twice to return to the operating window Function The unit operates at reduced flow when the presence sensor does NOT sense any movement in the room N B For normal air hand...

Страница 17: ...be due to low room Check the heat exchanger and electric temperature and setting of operating coil see Alarm heat exchanger and data such as stopping the unit electric coil without a damper lowest su...

Страница 18: ...Outdoor temperature not below 12 0 C 43 Set time activity period 3 53 Set weekday Monday 54 Set time 14 34 h m 71a Self test 71 Test Calibration Default value 71c Reset to default values 71b Calibrati...

Страница 19: ...No 76 Cooling coil installed No 77 Program version 1 0 Language 80 Main menu Select language 81 Language English Procedure setting Wind Description Default Own No value setting Air flow 10 Main menu...

Страница 20: ...Fl kt Woods AB 551 84 J nk ping t 036 19 30 00 f 036 19 36 20 w www flaktwoods com FWG_AHU_ABR2 Technical instruction_2009 05_GB_8061 Condesign Info Productions AB ABF5533...

Отзывы: